Calculate Size of Main ELCB & Brach MCB of Distribution Box

Design Distribution Box of one House and Calculation of Size of Main ELCB and branch Circuit MCB as following Load Detail. Power Supply is 430V (P-P), 230 (P-N), 50Hz. Consider Demand Factor 0.6 for Non Continuous Load & 1 for Continuous Load for Each Equipment.

  • Branch Circuit-1: 4 No of 1Phase, 40W, Lamp of Non Continues Load + 2 No’s of 1Ph, 60W, Fan of Non Continues Load.
  • Branch Circuit-2: 2 No of 1Ph, 200W, Computer of Non Continues Load.
  • Branch Circuit-3: 1 No of 1Ph, 200W, Freeze of Continues Load.
  • Branch Circuit-4: 8 No of 1Ph, 40W, Lamp of Non Continues Load + 2 No’s of 1Ph  60W, Fan of Non Continues Load.
  • Branch Circuit-5: 4 No of 1Ph , 40W, Lamp of Non Continues Load + 1 No’s of 1Ph 60W, Fan of Non Continues Load.+ 1 No’s of 1Ph 150W, TV of Continues Load
  • Branch Circuit-6: 1 No of 1P , 1.7KW, Geyser of Non Continues Load.
  • Branch Circuit-7: 1 No of 1Ph, 3KW, A.C of Non Continues Load.
  • Branch Circuit-8: 1 No of 3Ph, 1HP, Motor-Pump of Non Continues Load.

Untitled

Fault Current
Voltage Fault Current
230V 6KA
430V 10KA
11KV 25KA
Class of MCB/ELCB/RCCB
Type of Load Class Sensitivity
Lighting B Class I∆n:30ma
Heater B Class I∆n:30ma
Drive C Class I∆n:100ma
A.C C Class I∆n:30ma
Motor C Class I∆n:100ma
Ballast C Class I∆n:30ma
Induction Load C Class I∆n:100ma
Transformer D Class I∆n:100ma
     
     
Size of MCB/ELCB
Current (Amp) Lighting Load MCB/ELCB (Amp) Heating/Cooling/Motor-Pump Load MCB/ELCB (Amp)
1.0 to 4.0 6 16
6.0 10 16
10.0 16 16
16.0 20 20
20.0 25 25
25.0 32 32
32.0 40 40
40.0 45 45
45.0 50 50
50.0 63 63
63.0 80 80
80.0 100 100
100.0 125 125
125.0 225 225
225.0 600 600
600.0 800 800
800.0 1600 1600
1600.0 2000 2000
2000.0 3000 3000
3000.0 3200 3200
3200.0 4000 4000
4000.0 5000 5000
5000.0 6000 6000
6000.0 6000 6000

Calculation:

Size of MCB for Branch Circuit-1:

  • Load Current of Lamp= (No X Watt X Demand Factor)/Volt =(4X40X0.6)/230=0.40Amp
  • Load Current of Fan= (No X Watt X Demand Factor)/Volt =(2X60X0.6)/230=0.31Amp
  • Branch Circuit-1 Current as per NEC = Non Continues Load+125% Continues Load
  • Branch Circuit-1 Current as per NEC =(0.4+0.31)+125%(0) =0.73Amp
  • Type of Load=Lighting Type
  • Class of MCB=B Class
  • Size of MCB=6 Amp
  • No of Pole of MCB=Single Pole

Size of MCB for Branch Circuit-2:

  • Load Current of Computer = (No X Watt X Demand Factor)/Volt =(2X200X0.6)/230=1.04Amp
  • Branch Circuit-2 Current as per NEC = Non Continues Load+125% Continues Load
  • Branch Circuit-2 Current as per NEC =(1.04)+125%(0) =1.04Amp
  • Type of Load=Lighting Type
  • Class of MCB=B Class
  • Size of MCB=6 Amp
  • Breaking Capacity: 6KA
  • No of Pole of MCB=Single Pole

Size of MCB for Branch Circuit-3:

  • Load Current of Freeze= (No X Watt X Demand Factor)/Volt =(1X200X0.6)/230=0.87Amp
  • Branch Circuit-3 Current as per NEC = Non Continues Load+125% Continues Load
  • Branch Circuit-3 Current as per NEC =(0.87)+125%(0) =0.87Amp
  • Type of Load=Lighting Type
  • Class of MCB=B Class
  • Size of MCB=6 Amp
  • Breaking Capacity: 6KA
  • No of Pole of MCB=Single Pole

Size of MCB for Branch Circuit-4:

  • Load Current of Lamp= (No X Watt X Demand Factor)/Volt =(8X40X0.6)/230=0.83Amp
  • Load Current of Fan= (No X Watt X Demand Factor)/Volt =(2X60X0.6)/230=0.31Amp
  • Branch Circuit-4 Current as per NEC = Non Continues Load+125% Continues Load
  • Branch Circuit-4 Current as per NEC =(0.83+0.31)+125%(0) =1.15Amp
  • Type of Load=Lighting Type
  • Class of MCB=B Class
  • Size of MCB=6 Amp
  • Breaking Capacity: 6KA
  • No of Pole of MCB=Single Pole

Size of MCB for Branch Circuit-5:

  • Load Current of Lamp= (No X Watt X Demand Factor)/Volt =(4X40X0.6)/230=0.42Amp
  • Load Current of Fan= (No X Watt X Demand Factor)/Volt =(1X60X0.6)/230=0.16Amp
  • Load Current of TV = (No X Watt X Demand Factor)/Volt =(1X150X1)/230=0.65Amp
  • Branch Circuit-5 Current as per NEC = Non Continues Load+125% Continues Load
  • Branch Circuit-5 Current as per NEC =(0.42+0.16)+125%(0.65) =0.57+0.82=1.39Amp
  • Type of Load=Lighting Type
  • Class of MCB=B Class
  • Size of MCB=6 Amp
  • Breaking Capacity: 6KA
  • No of Pole of MCB=Single Pole

Size of MCB for Branch Circuit-6:

  • Load Current of Geyser= (No X Watt X Demand Factor)/Volt =(1X1700X0.6)/230=4.43Amp
  • Branch Circuit-6 Current as per NEC = Non Continues Load+125% Continues Load
  • Branch Circuit-6 Current as per NEC =(4.43)+125%(0) =4.43Amp
  • Type of Load=Heating & Cooling Type
  • Class of MCB=C Class
  • Size of MCB=16 Amp
  • Breaking Capacity: 6KA
  • No of Pole of MCB=Single Pole

Size of MCB for Branch Circuit-7:

  • Load Current of A.C= (No X Watt X Demand Factor)/Volt =(1X3000X0.6)/230=7.83Amp
  • Branch Circuit-7 Current as per NEC = Non Continues Load+125% Continues Load
  • Branch Circuit-7 Current as per NEC =(7.83)+125%(0) =7.83Amp
  • Type of Load=Heating & Cooling Type
  • Class of MCB=C Class
  • Size of MCB=16 Amp
  • Breaking Capacity: 6KA
  • No of Pole of MCB=Single Pole

Size of MCB for Branch Circuit-8:

  • Load Current of Motor-Pump = (No X Watt X Demand Factor)/(1.732XVolt ) =(1X746X0.6)/(1.732X430)=0.60Amp
  • Branch Circuit-8 Current as per NEC =Non Continues Load+125% Continues Load
  • Branch Circuit-8 Current as per NEC =(0.60)+125%(0) =0.60Amp
  • Type of Load=Motor-Pump Type
  • Class of MCB=C Class
  • Size of MCB=16 Amp
  • Breaking Capacity: 10KA
  • No of Pole of MCB= Three Pole

Size of Main ELCB/RCCB:

  • Total Brach Circuit Load & MCB Detail is
Brach Circuit Total

Current (Amp)

Size of MCB (Amp) Class of MCB Breaking Capacity of MCB Pole of MCB
circuit-1 0.73 6 Amp B Class 6KA SP
circuit-2 1.04 6 Amp B Class 6KA SP
circuit-3 0.87 6 Amp B Class 6KA SP
circuit-4 1.15 6 Amp B Class 6KA SP
circuit-5 1.39 6 Amp B Class 6KA SP
circuit-6 4.43 16 Amp C Class 6KA SP
circuit-7 7.83 16 Amp C Class 6KA SP
circuit-8 0.63 16 Amp C Class 10KA TP
Total 18.04        
  • Total Load Current as per NEC= 18.04Amp——–(A)
  • Max Size of Branch circuit MCB=16Amp
  • Total Current of Panel as per Branch Circuit= 2X Max Size of Branch circuit MCB
  • Total Load Current of Panel as per Branch Circuit =2X16=32Amp——(B)
  • Total Load Current of Panel as per NEC = Maximum of (A) and (B)
  • Total Load Current of Panel as per NEC=32Amp
  • Min Size of ELCB/RCCB as per NEC=40Amp
  • Class of ELCB/RCCB= B or C Class
  • No of Pole of ELCB/RCCB=TP or FP
  • Sensitivity( I∆n)=30ma
  • Breaking Capacity=10KA

Size of Distribution Board:

  • No of Single Pole Branch Circuit MCB (SP)= 7 No’s
  • No of Three Pole Branch Circuit MCB (TP)= 1 No’s
  • Main ELCB (TP)=1 No’s
  • Total No of Way of D.B (SPN)= (SP)+3X(TP)=7+(3X2)=13Way SPN
  • Total No of Way of D.B (TPN)= (SP)/3+ (TP)=(7/3)+(2)=4+2=6Way SPN
  • Select Either 14Way SPN or 6 Way TPN

Load Balancing of Distribution Board:

  • To Balance Load We need to try distribute Single Phase load on each Phase.
  • Suppose We connect Branch Circuit load on following Phase
Brach Circuit Current (Amp) Type of Load Connection on
Branch circuit-1 0.73 Single Phase        Y Phase
Branch circuit-2 1.04 Single Phase B Phase
Branch circuit-3 0.87 Single Phase Y Phase
Branch circuit-4 1.15 Single Phase B Phase
Branch circuit-5 1.39 Single Phase Y Phase
Branch circuit-6 4.43 Single Phase B Phase
Branch circuit-7 7.83 Single Phase R Phase
Branch circuit-8 0.63 Three Phase RYB Phase
Summary of Load
R Phase Load 8.5 Amp
Y Phase Load 3.5 Amp
B Phase Load 7.23 Amp
Total Load 18.04 Amp

Summary of Distribution Box :

Untitled - Copy

  • Size of Distribution Box : 14Way SPN or 6 Way TPN
  • Size of Main ELCB: 40A,B or C Class,30ma,10KA
  • Size & No of Branch MCB: 5 No’s of 6A,SP, B Class,6KA
  • Size & No of Branch MCB: 2 No’s of 16A,SP, C Class,6KA
  • Size & No of Branch MCB: 1 No’s of 16A,TP, C Class,10KA

99 Responses to Calculate Size of Main ELCB & Brach MCB of Distribution Box

  1. Vilas Garde's avatar Vilas Garde says:

    Dear Sir, Very Nice information on Electrical. Do you have such link for Instrumentation also if so please send link..? RegardsVilas Garde

    • Battakalanda Muthanna's avatar Battakalanda Muthanna says:

      Very elaborate, precise and complete information about the calculation of size of MCB, ELCB, RCCB has been given to the knowledge of users for various load options. Kindly can you give us what current rating or amparage and milliamps MCB, ELCB and RCCB to be used for residential wiring with heating and lighting circuits/ loads at main panel outside the house (electric pole to main panel), Main panel to Distribution Board or Box inside the house, from distribution board to heating load/ circuit and lighting load/ circuits.

    • Durga Khatri's avatar Durga Khatri says:

      So Useful tips for electrical power distribution design of residential and commercial Building

  2. Raju's avatar Raju says:

    Thank you Sir,

  3. V.P Selvam's avatar V.P Selvam says:

    Dear Jignesh sir,,,
    I m selvam working in ISRO as an Electrical Engineer, It is very useful material for everyone who wants to select the ELMCB nd MCB, DB…i really enjoy reading ur all blogs nd it gives me a clear idea and all practical concepts..i wish to continue ur valuable nd wonderful efforts…thanking u sir…

  4. vijay s's avatar vijay s says:

    That is a good example. How to design an Electrical panel board and do the wiring ? Also, what are the useful software available in the market to do that?
    Thanks and regards,

  5. naga mahesh's avatar naga mahesh says:

    SUPER SIR IT IS REALLY VERY HELP FULL TO ME SIR . BECAUSE I AM A FRESHER AND I STARTED MY WORKING WITH OUT PRACTICAL KNOWLEDGE……AND ONE MORE HON ABLE REQUEST IS PLEASE MAIL BUILDING CONSTRUCTION RELATED ELECTRICAL TOPICS MEAS CALCULATION……………………PLEASE SIR

  6. Eng.Elifuraha Mmary's avatar Eng.Elifuraha Mmary says:

    Am very interested on article of sizing CB,
    My request is, if possible let me have full topic of switchgear where I can help other on proper electrical installation and utilisation as well.
    Thanks
    Even a short course as right now am working in academic institution from Tanzania.

  7. bharat bhushan's avatar bharat bhushan says:

    hello sir,
    I am using a 2 pole,30ma sensitive rccb on the main line for the entire house.All the phase and neutral connections are done from the output of the rccb.I have one inverter/ups also which is getting the power supply from the output of the rccb.I want to connect a separate rccb on the output side of the inverter connection,but for this i am not able to find the proper way to connect the new rccb. if i am connecting the o/p from inverter and the same neutral,which is used for the power supply of the inverter as the i/p of new rccb and the single load wire(phase) at the output with leaving the neutral pole as it is then the new rccb trips.If i short both the i/p and o/p neutral of the new rccb and connecting the phase as above then also the new rccb trips .i guess there is some problem regarding neutral looping.please suggest me the proper way of connecting the rccb.

  8. Mahesh's avatar Mahesh says:

    good info. Is it possible to conduct basic design induction in Mumbai? In case interested then it can be discussed

  9. Gladwin's avatar Gladwin says:

    can you please tell me why you are not multiplying the calculated load current with 125% for branch Ckt calculation. as its non continuous load mentioned by you in the beginning.

  10. Eswaran's avatar Eswaran says:

    This is very useful for those who are in construction field.

  11. Eswaran's avatar Eswaran says:

    Where to fix the Z CT in HT Cable. i.e only three core or three core with earth. please explain with diagram sir.

  12. Naga Mahesh's avatar Naga Mahesh says:

    sir send and update s of electrical calculations please

  13. Noor khan's avatar Noor khan says:

    Sir for Current Calculation we use formula I =P/V x (Power factor )
    Or I =P/V x (Power Factor) x(1.73)
    But here You used I =P x (Power Factor)/V
    Plz Sir explain

  14. Muthazhagan's avatar Muthazhagan says:

    dear sir,
    what size of wire should be used for Light Points,fan points,etc and how many runs [ 2 or 3 runs]

  15. Deepak's avatar Deepak says:

    hello Sir,

    Can we use a 400v main mcb double pole in a 240v supply.will it trip or work same as a 240v breaker?

    Thnx fr

    Deepak

  16. MS Karoly's avatar MS Karoly says:

    Is there an article who to do this calculation as per IEC?

    • mohamed sherbini's avatar mohamed sherbini says:

      Overload calculation for MCCB in case using it on the primary side of small dry type transformer by IEC code.

  17. MS Karoly's avatar MS Karoly says:

    Do you have calculation as per IEC standards?

  18. Navnath M T's avatar Navnath M T says:

    Your notes r very useful for to study for any kind of installation of an electrical equipment. Thanking you

  19. B.D.'s avatar B.D. says:

    ur notes are awesum

  20. Mufutau Ibrahim Engn. Techn's avatar Mufutau Ibrahim Engn. Techn says:

    Tanx for a very wonderful job. May Almighty Allah guide you right

  21. farhad's avatar farhad says:

    good

  22. sandaruwan's avatar sandaruwan says:

    sir, very nicely understand every things thanks for u

  23. Phyoko's avatar Phyoko says:

    Thank you very much for your kindly Sir;

  24. Phyoko's avatar Phyoko says:

    Thanks

  25. Hussain's avatar Hussain says:

    Dear Sir,

    Thanks for the useful informations. But the formula for calculating the load you used in all circuits the demand factor must be down not up! Am I correct? I= (no. * P)/(1.7*V*Factor)

  26. Dhruvesh patel's avatar Dhruvesh patel says:

    Hi……..SIR…..
    I WORK IN ONGC AS ELECTRICIAN.ON A FIRST DATY OF
    MY JOB I FOUND THAT THERE IS TWO PHASE SHOWS IN 5A AND 15 A PLUG
    SOCKET OF 110 VOLTS EACH . HOW CAN AMPLIENCES WORK ON TWO PHASE OF
    110 VOLTS WITHOUT NEUTRAL.?? AND WHEN I ASK FOR THAT TO MY SENIOR HE
    TOLD ME THAT THIS IS RULE IN ONGC THAT THEY CAN NOT USE NEUTRAL FOR
    LIGHTING PURPOSE. BUT HE HAD NO REASONE FOR THAT. CAN YOU HELP ME TO
    UNDERSTAND THIS

  27. rao mohan's avatar rao mohan says:

    why multiplie 125 %

  28. Prashant's avatar Prashant says:

    Dear Jignesh sir,,,
    I m selvam working in ISRO as an Electrical Engineer, It is very useful material for everyone who wants to select the ELMCB nd MCB, DB…i really enjoy reading ur all blogs nd it gives me a clear idea and all practical concepts..i wish to continue ur valuable nd wonderful efforts…thanking u sir…

  29. Farooq Ahmed's avatar Farooq Ahmed says:

    Dear sir please let me know for 20hp power what
    size of elcb rccb is required
    Asap

  30. fazal rehman's avatar fazal rehman says:

    fault currents are given for 1second or more time plz add answer?

  31. arif's avatar arif says:

    sir can u please suggest if i have 30 volt bulb then how to count watt and ampere for it

  32. dr.pvs raju's avatar dr.pvs raju says:

    dear parmer,it is wondrful information given by u.i think crores of indian population need to read and learn about this house electricity information.i am 71yrs and i learn from u which i have been waiting to learn this basics.thanks

  33. Nadeeshan's avatar Nadeeshan says:

    Dear Sir, Thanks alot for providing a clear article on this topic. I enjoyed reading.

  34. sandeep's avatar sandeep says:

    Sir,
    I think all the phases (R,Y,B) have to be equal load and balanced. but here r=8.5,Y=3.5,B=7.23 Watts. For a balanced connection phases should have equal loads.

  35. SHIVANNA's avatar SHIVANNA says:

    Nice sir,
    Sir i need how to calculate the cable sizing for the building from transformer centre .

  36. harsha's avatar harsha says:

    can you tell me formula to calculate breaking capacity of MCB for load 200W 415V with 5% impedance n transformer ratings are 1500KV

  37. er mohd irfan wani's avatar er mohd irfan wani says:

    Current rating of mcb

  38. How much ELCB required for 48 AMP load extension

  39. Ritesh M Patel's avatar Ritesh M Patel says:

    I’m working for many years but no one explain me like this, thank u so much sir.

  40. Victor Alwyn's avatar Victor Alwyn says:

    Sir should you go for mcb board for Microwave oven

  41. gladwynn's avatar gladwynn says:

    Good day Sir,

    I am trying to size a MCB for a 3 phase 380Vac, 2.5kW motor. and based on what I ended up calculating was a MCB of the size 16A with a fault current of 10kA, will this work?

  42. saurav's avatar saurav says:

    sorry ac is single phase load.

  43. Smruti Samal Bhuyan's avatar Smruti Samal Bhuyan says:

    Dear Sir,
    Could you explain the load balancing. Here load is not balanced, in a ckt the load current is 3.5 A which is more less than other two ckts.???

  44. selvakumar's avatar selvakumar says:

    Hi how to determine demand factor ?

  45. ashok kumar's avatar ashok kumar says:

    thank s

  46. Mahendran Ravichandran's avatar Mahendran Ravichandran says:

    Thanks alot sir

  47. Aasif khan's avatar Aasif khan says:

    Sir in your above calculation of selection of MCB i want to ask a question i.e. in your branch circuit no. 3 you have include the freeze in a non continuous load why? and what is the us

  48. Sukanta Chanda's avatar Sukanta Chanda says:

    Its very useful article or information to choose proper mcb,rccb etc. I am a local electrician . Its increase my confidence more than before. Its very very helpful fo me. Thank you.

  49. yogesh nagare's avatar yogesh nagare says:

    thanks sir

  50. TONY JOSEPH's avatar TONY JOSEPH says:

    63A MCCB 25 KA- WHAT IS 25 KA ? How will i find out the ka rating of MCCB?

  51. siti faezan noor farah mohd noor's avatar siti faezan noor farah mohd noor says:

    Branch Circuit-3: 1 No of 1Ph, 200W, Freeze of Continues Load.

    but why did u calculate its load current as a non continuous load sir? can u explain?

  52. laxman Dhawale's avatar laxman Dhawale says:

    sir
    this is very helpful and nice
    and can you give details of cable size and selection all like internal wiring and LT/HT cable.
    please sir.
    Laxman

  53. how to choose the right mcb rating for drawing

  54. pn iyengar's avatar pn iyengar says:

    Dear Jignesh ji, My requirement may be a very very small problem for you as I am not an Elect. Engineer but has ample curiosity to know about basic electricals. My question is about the Ceiling Fan connection with Capacitor. Generally there are 3 wires given from the Ceiling Fan coil I.e. Starting Coil / Running Coil and Combination of Running and Starting coil wires. While connecting with the capacitor and Connector ( on 3 points – 1. Phase 2. Neutral and third dummy ) please advice which are the wires connected with phase / neutrals of the fan connector – 3 holes ( after connecting with Capacitors ) Some electricians says Running and Common on Phase/Neutral and the remaining in dummy and some says Starting and Common in phase/neutral and other in dummy whole. Pls. explain. I am very much eager to hear from you about this. . If I am confusing, my requirement is in the 3 whole connector which are the two wires to be inserted in the phase / neutral and which in dummy whole ).

  55. Kumar SK's avatar Kumar SK says:

    Our light switch is 10 amps and MCB is 20 Amps
    My question is if current increase in the circuit due to blasting chock sort circuit in some turns than what happened, As per me switch suppose to be meet the MCB ampacity as as NEC same thing

  56. Subhabrata Sarkar's avatar Subhabrata Sarkar says:

    Dear Jignesh Sir,

    I require to know as per IE rules what should be the circuit distribution system for residential building?Is it mandatory to provide separate MCB for power ckt to different rooms in a flat?

  57. Akhil p m's avatar Akhil p m says:

    What you mean by continuos load & non continuous load ? Can u explain selection of demand factor too

  58. monir's avatar monir says:

    I am not clear that,
    1 why incoming Circuit Breaker 40A and
    2 Out going circuit breaker total 78A (6+6+6+6+6+16+16+16)

  59. Carol's avatar Carol says:

    Hi, can i check why total current is 18.04 amp instead if 18.07? Is it due to rounding off?

  60. Rinzin Chophel's avatar Rinzin Chophel says:

    Sir,
    Nice information on electrical power system and network of distribution. I look forward seeing more information on distribution network.

  61. Please prepare and upload a form (online/offline) for calculating the requirement.

  62. Sachin's avatar Sachin says:

    My Panel here has 2 nos of 250 A outgoings, 2 Nos of 100 A outgoins, 2 nos of 63 A outgoings and 1 no 200 Amps outgoing. How can I calculate Incomer rating.

  63. Vishnu's avatar Vishnu says:

    The article is in detail and easy to understand.please tell me the NEC details taken as reference in the article.

  64. Sahil husain's avatar Sahil husain says:

    Very nice infarmatio, keep on!

  65. Akshay kolte's avatar Akshay kolte says:

    Beautifully explained

  66. Found your post interesting to read. I cant wait to see your post soon. Good Luck for the upcoming update.This article is really very interesting and effective.

  67. Vkdass's avatar Vkdass says:

    You sound so practical a teacher , parmar .

  68. Angad's avatar Angad says:

    Can you explain about demand factor and nec

  69. MOHD RIZWAN ABDULLAH's avatar MOHD RIZWAN ABDULLAH says:

    Great help sir
    Thanks very much

  70. Gaurav Kumar's avatar Gaurav Kumar says:

    Hi Jignesh ji,
    I am working in a electrical project Company. Pls upload the NEC Codes with Brief Description.

  71. Mhayat's avatar Mhayat says:

    Branch circuit-8
    how to select 16A TP MCB as per current rating 0.60Amp.

  72. Mustafiz Hayat's avatar Mustafiz Hayat says:

    In Branch circuit 8 how to select 16A TP MCB but given current value 0.60Amp.

  73. Rakesh kumar's avatar Rakesh kumar says:

    I Want witch type of use mcb

  74. srinivas's avatar srinivas says:

    please provide the coordination chart for replacement of fuses with MCBs

  75. Gulzar Ahmad's avatar Gulzar Ahmad says:

    Thanks sir very informative article, but why are not taking power factor in calculation ?

  76. sathiyamoorthi's avatar sathiyamoorthi says:

    dear sir i need to know ups operating please

  77. Nicholas Ho's avatar Nicholas Ho says:

    how do we know we need 10A SPN MCB Type B for lighting?

  78. K Banerjee's avatar K Banerjee says:

    Why spare MCB are not considered?
    Should we take spare MCB load in the calculation.
    Please clarify.

  79. David's avatar David says:

    If one of the brach circuit rating is 40A, then what will be the main RCCB rating? please advise.

  80. Nityanand Prasad's avatar Nityanand Prasad says:

    Any book where i can read this kind of stuff.

  81. Pabitrar paul's avatar Pabitrar paul says:

    Dear sir
    Thank you

  82. Mwady's avatar Mwady says:

    Are u sure we can use 30mA rating for earth leakage sensitivity at the main incomer of this circuit, especially when you have 1 no. of 1 hp 3-phase motor? I think later will create frequent nuisance tripping. 30mA is ok for the individual circuit.

  83. Vishnu patil's avatar Vishnu patil says:

    Nice one

  84. Kiran's avatar Kiran says:

    for a current of 4.43 A in Circuit 6 , a 16A MCB is used please clarify. is there is constant to be multiplied.

  85. Adekunle A.O's avatar Adekunle A.O says:

    Thank you much for this article..I WOULD LIKE TO KNOW HOW TO CALCULATE THE MAIN RCB SIZE IF THE TOTAL BRANCH CURRENT IS GREATER THAN TWICE THE MAXIMUM MCB

  86. Pavan Kumar Rao's avatar Pavan Kumar Rao says:

    Sir,
    why did you not considering Power factor in the calculation

  87. Vishal Bhatkar's avatar Vishal Bhatkar says:

    Nice information

  88. Syed muddu's avatar Syed muddu says:

    Suitable Mcb and Rccb for 3phase 30 kw

  89. Yasin's avatar Yasin says:

    ummmm can I find the PDF yeah I learnt a lot here thanks to the author

  90. P Sudalaimani's avatar P Sudalaimani says:

    Dear sir,
    This material is very informative and useful me. Thank you for your service.

  91. Soundhararajan Navaneethakrishnan's avatar Soundhararajan Navaneethakrishnan says:

    its really valuable info to us , keep update sir
    thanks

  92. Neeraj rai's avatar Neeraj rai says:

    Very good explanation,

  93. AK's avatar AK says:

    This is a good stuff but there is a mistake in the calculation which is overseen.

    Current as per NEC = Non Continues Load+125% Continues Load

Leave a Reply

Discover more from Electrical Notes & Articles

Subscribe now to keep reading and get access to the full archive.

Continue reading