Calculate Main Fire Pump Capacity with Head and other Characteristic as per NBC 2016 / IS 12469 / IS 15301.
January 31, 2025 1 Comment
EXAMPLE:
Calculate Main Fire Pump Capacity with Head and other characteristic as per NBC 2016 / IS 12469 / IS 15301 for following Details.
- Type of Hazard:
- Fire Type is Light hazard
- Fire Protection Area (Building) Detail:
- There are 4 Nos of Residency Building having 12 Nos floor and each floor have of 3.2 Meter height. (Building Height 38.40 Meter).
- Fire Fighting Pipe Network Detail:
- The maximum horizontal length of fire System header is 50 Meter.
- Up to Furthest Location in Fire Network System, the maximum bend in Horizontal Line are 6 Nos and Vertical Line /Header are 2 No. The Losses on each bend is 1.5 to 2 Meter.
- The Water Friction losses are approximately 3%
CALCULATION:
- We will derive calculation as per following sequence.
- Calculate Size of Main Fire Pump.
- Calculate Head of Fire Pump.
- Calculate RPM of Pump.
- Calculate Pump Pressure.
- Check Pump Characteristic as per Clauses.
(1) Calculate Size of Main Fire Pump:
- Type of Building occupancy is Residency and type of hazard is Light. The Building Height is 38.40 Meter.
- AS PER NBC-2016:
- As per NBC 2016, Table-7, Note No 10 , The Main Fire Pump Capacity will be 2850 Liter/Min.
- AS PER IS: 12469:
- Total No of Hydrant for Building = 1 No for Each Floor, hence approximate 1×12 (Floor) x4 (Tower) =48 No’s,
- As per IS 12469 , Fire Pump Capacity Shall be 137 M3/Hour = 2282 Liter / Min
- From Above consideration Capacity Main Fire Pump Shall be 2850 Liter /Min.
(2) Calculate Head of Main Fire Pump:
- Vertical Head
- Vertical Head =No floor x Floor Height
- Vertical Head =12 x 3.2 = 38.40 Meter.
- Head Losses due to Bend= 2 x Head Losses of Each Bend
- Head Losses due to Bend= 2 x 1.5 = 2.06 Meter.
- Equivalent Vertical Head=Vertical Head+ Head Loss due to bend
- Equivalent Vertical Head=38.40+2.06 =40.46 Meter.
- Total Vertical head= Equivalent Vertical Head x Friction Losses.
- Total Vertical head= =40.46 x 1.03= 41.67 Meter——-(A)
- Horizontal Head
- Horizontal Head=Maximum Horizontal Length
- Horizontal Head=50 Meter
- Head Losses due to Bend= 6x Head Losses of Each Bend
- Head Losses due to Bend= 6 x 1.5 = 9 Meter.
- Equivalent Horizontal Head= Horizontal Head+ Head Loss due to bend
- Equivalent Horizontal Head=50+9 =59 Meter.
- Total Horizontal head= Equivalent Horizontal Head x Friction Losses.
- Total Horizontal head= =59 x 1.03= 60.77 Meter——-(B)
- Total Head:
- Total Head =Horizontal Head + Vertical Head
- Total Head =41.67+60.77= 102 Meter.
- As per above Calculation Head for Fire Pump shall be 110 Meter.
(3) Calculate Speed of Main Fire Pump:
- As per IS 15301:
- As per IS 15301 (Clause 6.2) , Electric motors required to feed the pump up to 2280 Liter/Min are usually running at 2900 RPM and the pumps required to match the motors must also run at the same revolutions per minute.
- As per above Consideration Fire Pump speed shall be 2900 RPM.
(4) Calculate Main Fire Pump Pressure:
- As per IS 12469:
- As per IS 15301 (Clause 6.2) , Fire Pump Delivery Pressure shall be 7.0 Kg/cm2
- As per above Consideration Fire Pump speed shall be 7.0 Kg/cm2.
(5) Check Pump Characteristic as per Clauses.
- For Calculation consider Pump Flow rate 171 M3/Hour and head is 110 Meter.
- As per IS 12469:
- As per IS 12469 ,Following Two Condition shall be satisfied for Fire Main Pump.
- Pump shall be capable of not less than 150% of rated Capacity at Head of not Less than 65% of Rated Head.
- The Shut off Head Shall not exceed 140% of Rated Head.
- Pump Graph for 171 m3/hour is as per following.
- Condition-1:
- Pump shall be capable of not less than 150% of rated Capacity at Head of not Less than 65% of Rated Head.
- Pump Shall be capable to supply =150% of rated Capacity
- Pump Shall be capable to supply =150% x 171 = 256.5 M3/Hour.
- Pump shall capable of Head not less than=65% of Rated Head
- Pump shall capable of Head not less than=65% x 110 = 72 Meter
- As per Graph for flow rate of 256.5 M3/Hour Pump head is 95 Meter ( Which is less than 72 Meter)
- Condition-1 is satisfied.
- Condition-2:
- The Shut off Head Shall not exceed 140% of Rated Head.
- The Shut off Head Shall not higher =110×1.40 =154 Meter.
- As per Graph for flow rate of 256.5 M3/Hour, shut off Pump head is 120 Meter (Which is less than 154 Meter)
- Condition-2 is satisfied.
CONCLUSION:
- Size of Main Fire Pump: 2850 Liter/Min
- Head of Fire Pump: 110 Meter.
- RPM of Pump & Motor: 2900 RPM
- Calculate Pump Pressure: 7.0 Kg/cm2
- Check Pump Characteristic as per Clauses: Satisfied.