Earthing Strip /Wire / Pit Quick Reference-(Part-1)

Transformer-Earthing Wire / Strip Size:

Size of T.C or DG

Body Earthing

Neutral Earthing

<315 KVA 25×3 mm Cu / 40×6 mm GI Strip 25×3 mm Cu Strip
315 KVA to 500 KVA 25×3 mm Cu / 40×6 mm GI Strip 25×3 mm Cu Strip
500 KVA to 750 KVA 25×3 mm Cu / 40×6 mm GI Strip 40×3 mm Cu Strip
750 KVA to 1000 KVA 25×3 mm Cu / 40×6 mm GI Strip 50×3 mm Cu Strip

 Motor- Earthing Wire / Strip Size:

Size of Motor

Body Earthing

< 5.5 KW

85 SWG GI Wire

5.5 KW to 22 KW

25×6 mm GI Strip

22 KW to 55 KW

40×6 mm GI Strip

>55 KW

50×6 mm GI Strip

 Panel- Earthing Wire / Strip Size:

Type of Panel

Body Earthing

Lighting & Local Panel

25×6 mm GI Strip

Control & Relay Panel

25×6 mm GI Strip

D.G & Exciter Panel

50×6 mm GI Strip

D.G & T/C Neutral

50×6 mm Cu Strip

 Electrical Equipment Earthing:

Equipment

Body Earthing

LA (5KA,9KA)

25×3 mm Cu Strip

HT Switchgear

50×6 mm GI Strip

Structure

50×6 mm GI Strip

Cable Tray

50×6 mm GI Strip

Fence / Rail Gate

50×6 mm GI Strip

 Earthing Wire (As per BS 7671)

Cross Section Area of Phase, Neutral Conductor(S) mm2

Minimum Cross Section area of Earthing Conductor (mm2)

S<=16

S (Not less than 2.5 mm2)

16<S<=35

16

S>35

S/2

 Earthing Resistance value:

Earthing Resistance Value

Power Station 0.5 Ω
Sub Station Major 1.0 Ω
Sub Station Minor 2.0 Ω
Distribution Transformer 5.0 Ω
Transmission Line 10 Ω
Single Isolate Earth Pit 5.0 Ω
Earthing Grid 0.5 Ω
As per NEC Earthing Resistance should be <5.0 Ω

 

21 Responses to Earthing Strip /Wire / Pit Quick Reference-(Part-1)

  1. siva muthusamy's avatar siva muthusamy says:

    Dear sir/madam l had received electrical thump rules 4,5,6. so i want electrical thump rules 1,2,3. so plase kindly send me. thankyou M.SIVA

  2. Alex's avatar Alex says:

    Thank you for the valuable notes.

  3. Amit Khari's avatar Amit Khari says:

    Dear Sir,
    Thanks for valuable info.Kindly send me SLD of PCC in LT panel…….

  4. KRISHNA R's avatar KRISHNA R says:

    Sir .. Thank u for the Valuable information.. Can u pls upload details of Panel fabrication.

  5. farooq ahmed rather's avatar farooq ahmed rather says:

    dear sir .
    the thumb rule of electrical note is very help full

  6. abdul khadeer's avatar abdul khadeer says:

    thankx so much RESPECTED SIR
    to share ur lot of experience with us

  7. angelito Cortez's avatar angelito Cortez says:

    Thank you so much for the very interesting information.More power and God Bless.Can you give me information on how to calculate cables size current capacity in meters.

    Regards, Angelito

  8. Yasir Liaquat's avatar Yasir Liaquat says:

    Sir Thanks alot for Shairing Such a Very very helpful Informative… ALLAH bless you… and keep on sir… Once again Thanks

  9. syed shahbaz hussain's avatar syed shahbaz hussain says:

    Hi!Sir.Hope you are doing good.I’m very much thankful to you for this kind information regarding Electrical system. My question to you is my transformer is 315KVA so, what should be the size of the HT Cable.And also please let me know that how to select the HT cable?

    Thanks & Regards
    Shahbaz Hussain.

  10. Aravind's avatar Aravind says:

    Sir
    We have a cold storage with all the electrical load @ 197 hp.
    Right now we have a 185 Sq.mm cable from the transformer to the panel.
    When we are operating at full load the 185Sq.mm cable is heating up & mains are getting burnt out. Can you suggest suitable cable, & mains size.

  11. pradeep kumar's avatar pradeep kumar says:

    Dear Sir,

    how we calculate earthing strip size and wire size for ESD (electrostatic discharge) and EPA (earth protection area) in electronics assembly line. We are using ESD mat, ESd tile to discharge electrostatic charge.

  12. nagendra's avatar nagendra says:

    in two same capacity dg synchronization, what should be the rating of between 2 dg bus coupler,.
    is same of single dg or double of that.

  13. shailendra sengar's avatar shailendra sengar says:

    contactor voltage is ac or dc in contactor coil section as you indicated suffix

  14. Rajat's avatar Rajat says:

    Dear Sir,

    It will be helpful if you will share reference standard for earth conductor size for motors.

  15. ANIL kUMAR PATEL's avatar ANIL kUMAR PATEL says:

    How are You..sir….I am very much impressed with your notes on electrical ….

    Kindly send me a total date in pdf format for my reference

    Eamil Id : anilkumar_33@rediffmail.com
    Ph: 9491392855,9441063197

    I will be much thank full to you if your provide the same.

    With regard
    Anil Kumar Patel,

    Manager Marketing -Cables & Conductor
    Polywires & Metal Industry,
    Hyderabad.

  16. Balu G's avatar Balu G says:

    sir,

    how to derive body earthing conductor size for 4000A incomer power panel.

  17. Dipak Singh's avatar Dipak Singh says:

    Hi Sir,
    i need one help.
    how to select motor body earthing sizing of motor.

  18. pradeep's avatar pradeep says:

    how to calculate earth strip when there are 500 person on floor and avg static volate is 500V

  19. Sunil's avatar Sunil says:

    How much resistance per unit gi and copper stip.

  20. Shashidhar C's avatar Shashidhar C says:

    Dear Sir