Quick Reference -HVAC (Part-2)
November 17, 2020 7 Comments
|
A.C Capacity |
||
| Ton | KW | H.P |
| 0.64 | 2.1 | 0.8 |
| 0.80 | 2.8 | 1 |
| 1.00 | 3.7 | 1.25 |
| 1.28 | 4.6 | 1.6 |
| 1.60 | 5.6 | 2 |
| 2.00 | 7.31 | 2.5 |
| 2.56 | 9.35 | 3.2 |
| 3.20 | 11.6 | 4 |
| 4.00 | 14.4 | 5 |
| 4.48 | 16.7 | 5.6 |
| 6.40 | 22.1 | 8 |
| 8.00 | 29.1 | 10 |
| 1TON= | 1TON=3000 K.Cal/Hr | |
| 1TON=1200 BTU/Hr | ||
| 1TON=3.516 KW | ||
| 1TON=1.25 HP (VRV / VRF Only) | ||
| 1TON=4.7 HP | ||
| 1TON=12660 KJ/Hr | ||
|
Split AC Copper Pipe Size (Blue Star) |
||
| A.C Capacity | Suction Pipe | Discharge Pipe (Liquid) |
| Up to 1 Ton | 12.7mm (1/2″) | 6.4mm (1/4″) |
| 1 To 4 Ton | 15.9mm (5/8″) | 9.5mm (3/8″) |
| 5 To 6 Ton | 19.1mm (3/4″) | 9.5mm (3/8″) |
| 7 To 8 Ton | 22.2mm (7/8″) | 12.7mm (1/2″) |
| 9 To 11 Ton | 28.6mm (1 1/8″) | 12.7mm (1/2″) |
| 12 To 19 Ton | 28.6mm (1 1/8″) | 15.9mm (5/8″) |
| 20 To 27Ton | 34.9mm (1 3/8″) | 19.1mm (3/4″) |
| 28 To 42Ton | 41.5mm (1 5/8″) | 19.1mm (3/4″) |
| Normal Split A.C Copper Pipe Maximum Length = 15Meter | ||
| VRV System Copper Pipe Maximum Length = 150Meter | ||
|
Split AC Copper Pipe Length |
||
| A.C Capacity | Maximum Pipe Length | Maximum Indoor & Outdoor Height Difference |
| 0.5 Ton | 15 Meter | 5 Meter |
| 0.6 Ton | 15 Meter | 5 Meter |
| 0.75 Ton | 15 Meter | 5 Meter |
| 1 Ton | 20 Meter | 10 Meter |
| 1.5 Ton | 25 Meter | 10 Meter |
| 2 Ton | 25 Meter | 10 Meter |
| 2.5 Ton | 30 Meter | 10 Meter |
| 3 Ton | 30 Meter | 20 Meter |
| 3.5 Ton | 30 Meter | 20 Meter |
| 4 Ton | 30 Meter | 20 Meter |
|
Split AC Copper Pipe Additional Refrigerant Charge |
|||
| Total Pipe Length | 50 Meter | 60 Meter | 70 Meter |
| Additional Refrigerant | None | 250 gm (25gm/Meter) | 500 gm (25gm/Meter) |
|
Copper Pipe Thickness |
|||
| Pipe Size | Thickness | Tube Gauge | Type |
| 6.4mm (1/4″) | 0.8 mm | 21 | Soft |
| 9.5mm (3/8″) | 0.8 mm | 21 | Soft |
| 12.7mm (1/2″) | 0.8 mm | 21 | Soft |
| 15.9mm (5/8″) | 1 mm | 19 | Soft |
| 19.1mm (3/4″) | 1 mm | 19 | Soft |
| 22.2mm (7/8″) | 1 mm | 19 | Hard |
| 28.6mm (1 1/8″) | 1.2 mm | 18 | Hard |
| 34.9mm (1 3/8″) | 1.2 mm | 18 | Hard |
| 41.5mm (1 5/8″) | 1.3 mm | 18 | Hard |
| De-Oxidized Copper Tubes (DHP) , Copper 99.9% | |||
| Soft Copper as per ASTM B68 | |||
| Hard Copper as per ASTM B75 / ASTM280 / BS 2871 | |||
|
Gas Pressure For any Ton Capacity |
|||
| Refergerent | Suction Pressure (PSI) | Discharge Pressure (PSI) | Standing Pressure (PSI) |
| M/C ON | M/C ON | M/C OFF | |
| R 22 | 60 To 70 | 250To 300 | 156 |
| R 32 | 120 | 490 | 260 |
| R 134A | 35 | 158 To 199 | 95 |
| R 290 | 65 | 275 To 300 | 125 |
| R 404A | 87 | 270 To 356 | 190 |
| R 407C | 63 | 247 To 307 | 153 |
| R 410A | 110 To 120 | 400 To 500 | 250 |
| R 417A | 65 | 261 | 140 |
| Nitrogen Pressure Test |
Vacuum |
||
| 3 Minutes | 150 PSI | <= 500 Micron | for 24 Hours |
| 5 Minutes | 325 PSI | ||
| 24 Hours | 500 PSI | ||
| vacuum | < 500 Micron | ||
|
System Problems |
||||
| System Problem | Discharge Line Pressure | Suction Line Pressure | Suction Line Temperature | Compressor Amp |
| Over Gas Charge | High ↑ | High ↑ | Low ↓ (Ice on Suction Pipe) | High ↑ |
| Under Gas Charge | Low ↓ | Low ↓ | High ↑ | Low ↓ |
| Capillary Block | Low ↓ | Low ↓ | High ↑ | Low ↓ |
| Less Air Flow on Evaporator (Indoor Unit) | Low ↓ | Low ↓ | Low ↓ | Low ↓ |
| Less Air Flow on Condenser (Outdoor Unit) | High ↑ | High ↑ | High ↑ | High ↑ |
| Dirty Condenser (Outdoor Unit) | High ↑ | High ↑ | High ↑ | High ↑ |
| Low Ambient Temperature | Low ↓ | Low ↓ | Low ↓ | Low ↓ |
| High Ambient Temperature | High ↑ | High ↑ | High ↑ | High ↑ |
| Insuffient Compressor | Low ↓ | High ↑ | High ↑ | Low ↓ |
|
Insulation Thickness |
|||
| Refrigerant Pipe | Insulation | Drain Pipe | Insulation |
| 22.22mm To 28.58mm | 19mm | 25mm / 32mm /40mm | 6mm |
| 12.7mm To 19.05mm | 13mm / 19mm | ||
| 6.35mm To 9.2mm | 9mm / 13mm | ||
|
Referent Pipe Insulation |
|||
| Pipe | Pipe size | Insulation Type (EPDM or NBR) | |
| Standard conditions 86°F (30°C), < 85% | High humidity conditions(a) 86°F (30°C), >85% | ||
| Liquid Pipe | 1/4″ (6.35 mm) To 3/8″ (9.52 mm) | 3/8″ (9 mm) | 3/8″ (9 mm) |
| 1/2″ (12.70 mm) To 2″ (50.80 mm) | 1/2″ (13 mm) | 1/2″ (13 mm) | |
| Vapor Pipe | 1/4″ (6.35 mm) To 7/8″ (22.23) | 1/2″ (13 mm) | 3/4″ (19 mm) |
|
The distance between the supports of the copper pipes. |
|
| Diameter | Distance (m) |
| ≤ 20 mm | 1 Meter |
| 20 To 40 mm | 1.5 Meter |
| ≥ 40 mm | 2 Meter |
|
The permitted length and drop difference |
||
| Pipe length | Max. pipe length | <= 240 Meter |
| Equivalent length from the first branch to the farthest indoor unit | <= 40 Meter | |
| Drop height | Drop height between indoor unit and outdoor unit | <= 110 Meter |
| Drop height between indoor units | <= 30 Meter | |
|
Factory Fabricated |
|
| Duct Size | Gauge of GI sheet |
| 1 – 900 mm | 26 |
| 901 -1200 mm | 24 |
| 1201 -1800 mm | 22 |
| 1801 – 2100 mm | 20 |
| 2101 – above | 18 |
|
Site Fabricated |
|
| Duct Size | Gauge of GI sheet |
| Upto 750mm | 24 |
| 750mm- 1500 mm | 22 |
| 1510 mm- 2250 mm | 20 |
| above 2250 mm | 18 |
|
Horizontal Ductwork |
||
| Ducts Size | Maximum Spacing | |
| Area (m2) | Diameter | |
| less than 0.4 | less than 125 mm | 2.5 Meter |
| 0.4 to 1 | 125 to 1000 mm | 2 Meter |
| more than 1 | more than 1000 mm | 1.2 Meter |
|
Vertical Ductwork |
|
| Ducts Type | Maximum Spacing (Meter) |
| round | 3.6 Meter |
| rectangular | 3 Meter |
|
Rectangular Duct Sheet Thickness as per CPWD |
||
| Longest side (mm) | Minimum sheet thickness | |
| Galvanized Sheet Steel (GSS) IS: 277 | For Aluminum IS:737 | |
| 750 mm and below | 0.63mm (22 Gauge) | 0.8mm (20 Gauge) |
| 751 mm to 1500 mm | 0.8mm (20 Gauge) | 1mm (18 Gauge) |
| 1501 mm to 2250 mm | 1mm (18 Gauge) | 1.5 mm (15 Gauge) |
| 2251 mm & above | 1.25mm (16 Gauge) | 1.8 (13 Gauge) |
|
Round Duct Sheet Thickness as per CPWD |
||
| Longest side (mm) | Minimum sheet thickness | |
| Galvanized Sheet Steel (GSS) IS: 277 | For Aluminum IS:737 | |
| 150 mm to 500 mm | 0.63mm (22 Gauge) | 0.8mm (20 Gauge) |
| 501 mm to 750 mm | 0.8mm (20 Gauge) | 1mm (18 Gauge) |
| 751 mm to 1000 mm | 0.8mm (20 Gauge) | 1mm (18 Gauge) |
| 1001 mm to 1250 mm | 1mm (18 Gauge) | 1.5 mm (15 Gauge) |
| 1251 mm and above | 1.25mm (16 Gauge) | 1.8 (13 Gauge) |
|
DUCT Support OR Gripple Wire Support |
|||
| Duct Size (mm) | Spacing (M) | Size of MS Angle (mm x mm) | Size of Rod Dia (mm) |
| Up to 750 | 2.4 | 32x32x3 | 8 |
| 751 to 1000 | 2 | 40x40x5 | 10 |
| 1000 to 1500 | 2 | 40x40x5 | 10 |
| 1501 to 2250 | 2 | 50x50x6 | 12 |
| 2251 to above | 2 | 50x50x6 | 12 |
|
Round Duct Support |
|||
| Round Duct Size (mm) | Spacing of Supports (m) | Size of M.S. Angle (mm) | Dia. of Hanger Rod (mm) |
| Up to 500 | 1.5 | 40 x 40 x 6 | 12 |
| 501 to 1200 | 1.5 | 40 x 40 x 6 | 12 |
| 1201 to 2250 | 1.5 | 50 x 50 x 6 | 15 |
|
Normal Ducting: |
||
| Larger duct-dimension | Spacing of Supports (m) | Sheet thickness, SWG (mm) |
| Up to 750 mm | 1.5 To 2 | 2 24 G (0.63 mm) (25×25 GI flanges acceptable) |
| 751 to 1500 mm | 1.5 To 2 | 22 G (0.80 mm) (25x25x3 MS flanges up to 1000mm; 40x40x5 MS flanges beyond 1000mm) |
| 1501 mm to 2250 mm | 1.5 To 2 | 20 G (1.00 mm) (40x40x5 MS flanges) |
| Above 2250 mm | 1.5 To 2 | 18 G (1.20 mm) (50x50x6 MS flanges) |
|
Supporting details for Low-Pressure system |
|||
| LARGER SIDE OF DUCT mm | SUPPORTING ANGLE mm |
VERTICAL ROD DIAMETER mm |
MAXIMUM SPACING BETWEEN SUPPORTS mm |
| Upto 900 | 40x40x6 | 10 | 3000 |
| 901 to 1500 | 50x50x6 | 10 | 3000 |
| 1501 to 2400 | 50x50x6 | 10 | 2400 |
| 2401 and above | 65x65x6 | 12 | 2400 |
|
Supporting details for Round Duct |
|||||
| DUCT DIAMETER mm | STRAP | ROD | |||
| No | WIDTH mm | THICKNESS G | No | DIAMETER mm | |
| Upto 600 | 1 | 25 | 22 | 1 | 7 |
| 601 to 900 | 1 | 25 | 20 | 1 | 10 |
| 901 to 1250 | 2 | 25 | 20 | 2 | 10 |
| 1251 t o1500 | 2 | 25 | 18 | 2 | 10 |
| 1501 to 2100 | 2 | 25 | 18 | 2 | 10 |
|
Diffuser size |
||
| Area | Ceiling Height | Diffuser size(dia.) |
| Up to 12 sqmm | 2.4 – 2.7m | 200mm |
| Up to 12 sqmm | 3m | 250mm |
| Up to 20 sqmm | 2.4m – 2.7m | 250mm |
| Up to 20 sqmm | 3m | 300mm |
| Over 20 sqmm | multiple diffusers | |
|
Additional refrigerant charged volume |
|
| Liquid pipe Size | R410A (kg/m) |
| 6.4 mm | 0.022 |
| 9.5 mm | 0.057 |
| 12.7 mm | 0.11 |
| 15.9 mm | 0.18 |
| 19.1 mm | 0.26 |
| 22.2 mm | 0.37 |
| 25.4 mm | 0.45 |
|
Drain Pipe Capacity |
||
| Condensate water volume : V (L/h)=Indoor Unit (HP)x2 | I.D (mm) | Thickness (mm) |
| V ≤ 14 | Φ 25 | 3 |
| 14 < V ≤ 88 | Φ 30 | 3.5 |
| 88 < V ≤ 175 | Φ 40 | 4 |
| 175 < V ≤ 334 | Φ 50 | 4.5 |
| 334 < V | Φ 80 | 6 |
| *If Slop is <1% than select next higher Size of Drain Pipe | ||