Guideline for Installation of Hooter-Telephone Jack-Fire Alarm Panel

 

FIRE HOOTER / FIRE SOUNDER & STOBER / AUIDABLE REFERENCE

Area

Code Clause No

Descriptions

Mounting Height NFPA-72 18.5.5.1 Wall-mounted appliances shall be mounted such that the entire lens is not less than 2.03 Meter and not greater than 2.44 Meter above the finished floor or at the mounting height specified using the performance-based alternative of NFPA-72 (18.5.5.7).
NFPA-72 18.5.5.2 Where low ceiling heights do not permit wall mounting at a minimum of 2.03 Meter wall mounted visual notification appliances shall be mounted within 150 mm of the below Ceiling.
NFPA-72 18.5.5.3 Where low ceiling heights do not permit wall mounting at a minimum of 2.03 Meter the room size covered by a visual notification appliance of a given value shall be reduced by twice the difference between the minimum mounting height of 2.03 Meter and the actual lower mounting height.
NFPA-72 18.5.5.4 Visual notification appliances listed for mounting parallel to the floor shall be permitted to be located on the ceiling or suspended below the ceiling.
NFPA-72 18.7.2 Supplementary visual notification appliances shall be permitted to be located less than 2.03 Meter above the floor.
Canadian standard CAN/ULC-S524-01/06 Not less than 2.3Meter above the floor (where ceiling heights allow) measured to the centre of the device.  Not less than 150 mm from the ceiling measured from the top of the assembled device (top edge of gong if the device is a bell
Distance NFPA-72 18.5.5.6.5 Visual notification appliances shall be located not more than 4.6 Meter from the end of the corridor with a separation not greater than 30.5 Meter between appliances.
NFPA-72 18.5.5.8.4 For rooms with a linear dimension greater than 4.9 Meter the visual notification appliance shall be located within 4.9 Meter of the measured point.
Sound Level IS 15908 C-3.2 Sound Level:  The sound level (peak value) shall be not less than 65 dB(A) and not more than 120 dB(A) when measured at a distance of 1.5 meter.
IS 2189 4.3 General occupancies: A minimum sound level of either 65 dB (A) or 5 dB (A) above any other noise likely to persist for a period longer than 30 second, whichever is greater should be produced by the sounders at any point which can be occupied in a building
IS 2189 4.3 Sleeping areas: If the fire routine for the premises requires the audible alarm to arouse sleeping persons, the minimum sound level should be 75 dB (A) at the bed head with all doors shut. A large number of quieter sounders rather than a few very loud sounders may be preferable to prevent noise levels in some areas from becoming too loud.
NFPA-72 18.4.4.1 Public (most commercial) : Sound level at least 15 dBA above average ambient sound or 5 dBA above maximum sound level for durstion of at least 60 sec ,Measured 1.5 Meter above floor
NFPA-72 18.4.5.1 Private (most commercial) : Sound level at least 10 dBA above average ambient sound or 5 dBA above maximum sound level for duration of at least 60 sec ,Measured 1.5 Meter above floor
NFPA-72 18.4.6.1 Sleeping Area : Sound level at least 15 dBA above average ambient sound or 5 dBA above maximum sound level for duration of at least 60 sec or Sound level at least 75 dBA, which is greater measured at pillow level with door closed. Low-frequency 520 Hz preferred (better arousal)
NFPA-72 18.4.4.1 Industrial / high-noise / Mechanical rooms : Sound level at least 15 dBA above average ambient sound or 5 dBA above maximum sound level for durstion of at least 60 sec
OSHO The limit of 110 dBA has been set as a reasonable upper limit for the performance of a system

 

FIRE TELEPHONE JACK REFERENCE

Area

Code Clause No

Descriptions

Mounting Height NFPA-72 24.8.17 Wall-mounted telephone appliances or related jacks shall be not less than 910 mm and not more than 1.68 Meter above floor level with clear access to the appliance that is at least 760 mm wide.
NFPA-72 24.8.18 If accessible to the general public, one telephone appliance per location shall be not more than 1.22 Meter above floor level.
Canadian standard CAN/ULC-S524-01/06 Mounted so that the height from the floor to the center line of the enclosure is between 1350 mm and 1500 mm.

 

FIRE ALARM PANEL REFERENCE

Area

Code Clause No

Descriptions

Mounting Height NFPA-72 10.4.4 the fire alarm control unit shall be installed so that the highest switch, indicator lamp, or top of any textual display is no more than 1.8 meter above the finished floor, and the distance to the lowest switch, lamp, or bottom of any textual display is not within 375 mm of the finished floor.
NEC / NFPA 70 110.26 In Front of FAP: Minimum 915mm of clear working space in front of equipment.
Vertical Clearance: Minimum vertical clearance of 2000mm from the floor to any overhead obstruction.
Side to Side Clearance: Minimum 760mm clearance from side to side or the width of the equipment, whichever is greater.