Calculate Lightning Protection for Building / Structure

Example: Calculate Whether Lightning Protection is required or not for following Building. Calculate No of Down Conductor for Lightning Protection

Area of Building / Structure:

  • Length of Building (L) = 60 Meter.
  • Width of Building ( W ) = 28 Meter.
  • Height of Building (H) = 23 Meter.

Lightning Stock Flushing Density

  • Number of Thunderstorm (N)= 80.00 Days/Year
  • Lightning Flash Density   (Ng)=69 km2/Year
  • Application of Structure (A)= Houses & Buildings
  • Type of Constructions (B)= Steel framed encased without Metal Roof
  • Contests or Consequential Effects (C)= Domestic / Office Buildings
  • Degree of Isolation (D)= Structure in a large area having greater height
  • Type of Country (E)= Flat country at any level
  • Maximum Acceptable Overall Risk Factor =0.00000001
Reference Table As per IS:2309
Thunder Storm Days / Year Lightning Flash Density (Flashes to Ground /km2/year)
5 0.2
10 0.5
20 1.1
30 1.9
40 2.8
50 3.7
60 4.7
80 6.9
100 9.2
Application of Structure Factor
Houses & Buildings 0.3
Houses & Buildings with outside aerial 0.7
Factories / workshop/ Laboratories 1
Office blocks / Hotel 1.2
Block of Flats / Residences Building 1.2
Churches/ Hall / Theaters / Museums, Exhibitions 1.3
Departmental stores / Post Offices 1.3
Stations / Airports / Stadium 1.3
Schools / Hospitals / Children’s Home 1.7
Others 1.2
Type of Constructions Factor
Steel framed encased without Metal Roof 0.2
Reinforced concrete without Metal Roof 0.4
Steel framed encased with Metal Roof 0.8
Reinforced concrete with Metal Roof 1
Brick / Plain concrete or masonry without Metal Roof 1.4
Timber framed or clad without Metal Roof 1.7
Brick / Plain concrete or masonry with Metal Roof 2
Timber framed or clad with Metal Roof
Contests or Consequential Effects Factor
Domestic / Office Buildings 0.3
Factories / Workshop 0.3
Industrial & Agricultural Buildings 0.8
Power stations / Gas works 1
Telephone exchange / Radio Station 1
Industrial key plants, Ancient monuments 1.3
Historic Buildings / Museums / Art Galleries 1.3
Schools / hospitals / Children Homes 1.7
Degree of Isolation
Factor
Structure in a large area having greater height 0.4
Structure located in a area of the same height 1
Structure completely Isolated 2

Calculation:

Collection Area (Ac)=(L x W) + 2 (L x H) + 2(W x H) +(3.14 x H2)

  • Collection Area (Ac) = (60×28)+2x(60×23)+2x(28×23)+(3.14x23x23)
  • Collection Area (Ac) =7389 Meter2

Probable No of Strikes to Building / Structure (P)= Ac x Ng x 10-6 No’s / Year

  • Probable No of Strikes to Building / Structure (P)= 7389x69x106 No’s / Year
  • Probable No of Strikes to Building / Structure (P)= 05098 No’s / Year

Overall Multiplying Factor (M) =A x B x C x D x E

  • Application of Structure (A)= Houses & Buildings as per Table Multiplying Factor = 0.3
  • Type of Constructions (B)= Steel framed encased without Metal Roof as per Table Multiplying Factor =0.2
  • Contests or Consequential Effects (C)= Domestic / Office Buildings as per Table Multiplying Factor =0.3
  • Degree of Isolation (D)= Structure in a large area having greater height as per Table Multiplying Factor =0.4
  • Type of Country (E)= Flat country at any level so as per Table Multiplying Factor =0.3
  • Overall Multiplying Factor (M) =0.3×0.2×0.3×0.4×0.3
  • Overall Multiplying Factor (M) =0.00216

Overall Risk Factor Calculated (xc)= M x P

  • Overall Risk Factor Calculated (xc)= 0.00216 x0.05098
  • Overall Risk Factor Calculated (xc)= 000110127

 Base Area of Structure (Ab) = (LxW)

  • Base Area of Structure (Ab)=60×28
  • Base Area of Structure (Ab)=1680 Meter2

Perimeter of Structure (P) =2x (L+W)

  • Perimeter of Structure (P)=2x(60+28)
  • Perimeter of Structure (P)=176 Meter

Lightning Protection Required or Not

  • If Calculated Overall Risk Factor Calculated > Maximum Acceptable Overall Risk Factor than only Lighting Protection Required
  • Here Calculated Overall Risk Factor is 0.000110127 > Max Acceptable Overall Risk Factor is 00000001
  • Lightning Protection is Required

 No of Down Conductor

  • Down Conductors As per Base Area of Structure (s) =1+(Ab-100)/300
  • Down Conductors As per Base Area of Structure (s) =1+(1680-100)/300
  • Down Conductors As per Base Area of Structure (s) =6 No’s
  • Down Conductors As per Perimeter of Structure (t)= P/30
  • Down Conductors As per Perimeter of Structure (t)= 176/30
  • Down Conductors As per Perimeter of Structure (t)= 6 No’s
  • Minimum No of Down Conductor is 6 No’s

 Results:

  • Lightning Protection is Required
  • Down Conductors As per Base Area of Structure (s) =6 No’s
  • Down Conductors As per Perimeter of Structure (t)= 6 No’s
  • Minimum No of Down Conductor is 6 No’s

57 Responses to Calculate Lightning Protection for Building / Structure

  1. Gopala Krishnan's avatar Gopala Krishnan says:

    Very useful datas

  2. Zaw Maung's avatar Zaw Maung says:

    Thanks a lot. Could you explian about selection of air terminal , surge arrester, please?

  3. Tushar Mahajan's avatar Tushar Mahajan says:

    Dear Sir,

    Nice Information

    Thanks Tushar Mahajan.

  4. Hello, do you have any software to simulate the artistic lighting of bridges? – Thank you!

  5. K R Nair's avatar K R Nair says:

    Any one interested to undertake insulation coordination study of HV andEHV Transmission Lines? If so please do contact. Though we performed in the past and performing at present, we wish to oursource this study, if find viable.

  6. Dinesh Kumar Sarda's avatar Dinesh Kumar Sarda says:

    Dear Sir,

    Thanks for the information. I humbly request you to provide me with a similar working on substations 220 KV and above DSLP calculation. urgently required for an interview. Please help

  7. Prathamesh Bagav's avatar Prathamesh Bagav says:

    Maximum Acceptable Overall Risk Factor =0.00000001 value is fixed or may change as par building type?

  8. Prathamesh Bagav's avatar Prathamesh Bagav says:

    Hi Sir, Maximum Acceptable Overall Risk Factor =0.00000001 value is fixed or may changed according to building type?

  9. ayman zaher's avatar ayman zaher says:

    there is a missing table
    you referred to 5 factors we already have 4 above
    where is the table of E factor (type of country ) your choice was ( flat country at any level = 0.3 ) its not stated above where is the fifth table

    before i also put a statement about the equation of voltage drop in wires and asked why we use (r cos phi + x sin phi ) instead of sqrt (( rcos phi) 2 + ( x sin phi ) 2 ) and still no answer

    anyways thanks alot for your efforts

  10. ayman zaher's avatar ayman zaher says:

    there is something make me confuse about the data input

    in the start of the data input you put
    Maximum Acceptable Overall Risk Factor =0.00000001 and this is 1 to the power -8

    and after the example near the end you put
    Here Calculated Overall Risk Factor is 0.000110127 > Max Acceptable Overall Risk Factor is 00000001

    in the excel sheet we have from your site as you are the author of it you put the overall risk factor is .000001 that means only 1 to the power of -6

    so please advice is it 0.00000001 or 0.000001

    thanks for the efforts in this blog

  11. Mustaqeem Shaikh's avatar Mustaqeem Shaikh says:

    Dear sir how to calculate the cable size of lightning arrestor ?

  12. Rupali Patil's avatar Rupali Patil says:

    Sir, Thanks for your guidelines. One thing i need to confirm this is for rectangular, square types of building. How to calculate No of Down Conductor for Lightning Protection for circular building?

  13. Debasis sahoo's avatar Debasis sahoo says:

    Is earthing of pure metallic structure required?

  14. devang's avatar devang says:

    Dear sir,

    1. Can we connect static earthing system and power [electrical] earthing system?

    2. Which of the earthing pits [Power, instrument, lightning, static, telecommunication] we can interconnect without hazard?

  15. khin shwe's avatar khin shwe says:

    Thank for your information.

  16. Bala's avatar Bala says:

    very informative..
    Could you explain about the rolling sphere method

  17. Mahipal's avatar Mahipal says:

    Thank you for your information.

    how to calculate the lightning protection calculation for tall metal structures? ex: Telecom towers

    please give some suggestions.

  18. Dick Ramirez's avatar Dick Ramirez says:

    what is the size of bare copper wire for 800 square meter area of a building and 10 meters in height?

  19. Abdalnasser shhwan's avatar Abdalnasser shhwan says:

    Dear Sir ,
    I would like to say thank you so much
    your website very useful
    God bless you

  20. bryan's avatar bryan says:

    how much the height of building required lightning protection

  21. hari's avatar hari says:

    Dear Sir
    Thanking for your information kindly provide the information about number of lighting arrester requirement

  22. sagar's avatar sagar says:

    sir this is sagar, I want to how many lights using in one bed room, L-50 MTR B-30 MTR H-40 MTR,, PLZ CAN U GIVE THE EXPLAIN THIS PROBLEM

  23. VEENA gore's avatar VEENA gore says:

    Jinesh
    Your notes compilation is excellent and I have downloaded that.
    However I want to highlight that this calculation as per is 2309 is no longer applicable now since this IS has become obsolete now. And is replaced by ICE 62305.
    Veena Gore

  24. Sunil R Tripathi's avatar Sunil R Tripathi says:

    Dear Sir,
    Thanks for these nice information. Sir, what size of cable must be used if my Down conductor increases and whether earth pits are required for each DC. And the distance between these earth pits if applicable.

    Kindly do the needful.

    Sunil.

  25. shivraj's avatar shivraj says:

    jignesh
    Can u pl give an excel sheet for lightening protection as per IEC 62305. as it is latest for lightening Protection.

  26. gopal's avatar gopal says:

    Sir, required design accordingly IS 62305, could you help me on the same?

  27. SATISH TIWARI's avatar SATISH TIWARI says:

    how many lightening arrestor required if the area of the building is 500 m2

  28. SATISH TIWARI's avatar SATISH TIWARI says:

    what will happen if earth pit of electronic equipment and telecommunication system is not seperated.

  29. rifky's avatar rifky says:

    need a calculation for steel bridge tower(height=35m)

  30. saji's avatar saji says:

    I would like to get an EPC scope of work for Lightning protection scope reference.

  31. Simrat pal singh's avatar Simrat pal singh says:

    Sir,
    our steel frame with metal roof building Length is 150 mtr, Width is 62 mtr, height is 20 mtr.
    i calculate as per above given Example
    Down Conductors As per Base Area of Structure (s) =31 No’s
    Down Conductors As per Perimeter of Structure (t)= 13 No’s

    please reply my calculation is correct or not.

    Regards,
    Simratpal Singh,
    Mobile 9914825522.

  32. azrin's avatar azrin says:

    Dear Sir,

    I have a question which is can we use copper dc clip to tighten the aluminium tape on the wall instead of aluminium dc clip? If can, is there any side affect?

    Thank you.

    Regards.

  33. kapil tayade's avatar kapil tayade says:

    How to calculate no of Air terminals please explain

  34. basavaraja Pattar's avatar basavaraja Pattar says:

    Thanking for your information

  35. Akshay Patil's avatar Akshay Patil says:

    is this calculation according to NBC 2016?

  36. win lae khaing's avatar win lae khaing says:

    may I known how to select the lightning protection cable size?

  37. Mani R. Y's avatar Mani R. Y says:

    Excellent model. Thanks.

  38. Roshan Kumar's avatar Roshan Kumar says:

    sir,

    This was really very helpful.please suggest a building height above 30 mtrs.(as per IS2309)

  39. Annavarapu Kishore's avatar Annavarapu Kishore says:

    Thank You SIr, Very Good Information Clearly explained. I have two doubts
    1) in regards to fixing the GI Flat on roof ( Grid Type) of Metal Sheets, can we fix directly to sheet or insulator to be used.?
    2) How to determine the height of VAT(LA) over shed and how to arrive to number of Vertical Air Terminals Required.

    Thanking You
    Regards
    Kishore A

  40. SSEBULIBA m. PETER's avatar SSEBULIBA m. PETER says:

    Why use the 300 in the Area equation and 30 in the perimeter equation denominator?

  41. Subburaj P's avatar Subburaj P says:

    Sir.,
    Is this calculation method been to IEC 62305.?

  42. Rashid's avatar Rashid says:

    Hello everyone, my house is 3 story and 2000 square feet’s. I installed only one airtarminal and one earthing rod with aluminum bar. Is it ok or any suggestions please?

  43. SM's avatar SM says:

    Sir,

    how can arrive cu flat (25x3mm) in the calculation..

  44. Kiran's avatar Kiran says:

    Hi,

    This calculation is applicable for new IEC 62305

  45. Mohsin's avatar Mohsin says:

    Hi,
    Thank you for the details provided above. your posts are always useful .

    regarding above equations, The above formula used for calculating the down conductor numbers is deviating from IEC 62305. Also can you please explain how we can derived the level of protection and protective efficiency from the above equation.

    Many Thanks.

  46. Dear sir,

    For my building I calculated and it comes 4 down leads, whether 4 leads should connect to one earth pit or 4 down leads need to connect separate 4 earth pits.

  47. collins O's avatar collins O says:

    very educative. thanks sir

  48. Riyadh sabry's avatar Riyadh sabry says:

    hello sir
    I have question about connected between earthing system(grounding )and lightning protection system (rods) is it OK safe .
    because i have hospital design so there are two system on for earthing another for lightning thank you

  49. nimisha's avatar nimisha says:

    Now IS:2309 is void, IEC 62305 is using please shre sample calculation as per IEC 62305

    • T SUNDARAPANDIYN's avatar T SUNDARAPANDIYN says:

      IS 2309 IS NOT VOID. IEC 63205 – IS IT APPROVED BY CENTRAL ELECTRICITY AUTHORITY OR BY NATIONAL BUILDING CODE

  50. Abdul Maruf Molla's avatar Abdul Maruf Molla says:

    Dear Sir
    Thanking for your information, kindly provide a calculation method about number of lighting arrester requirement

  51. Ardy's avatar Ardy says:

    number of air terminal will be dependent on the length and width of the building. if you use 254mm height of air teminal which is the minimum height of air terminal to be used as per UL 96 standard, spacing would be 6mtr in between terminal; but if you are using 600mm height air terminal it will now be 7.6mtr apart.

  52. Budhaji Parab's avatar Budhaji Parab says:

    How to calculate CT and pt size calculation

  53. K K MEHTA's avatar K K MEHTA says:

    Calculation of LA is same as per IS:2309 and IEC 62305

  54. Saad Anjum's avatar Saad Anjum says: