Calculate Cable Voltage Drop for Street Light Pole

Example: Calculate Voltage drop of Cable for Street Light Pole. System Voltage is 230V (P-N), Power Factor=0.75. Allowable Voltage Drop = 4% .The Detail of Pole & cable are

Pole Detail:

  • Section feeder Pillar is 50 meter away from Pole-1
  • Distance between each Pole is 50 Meter Distance
  • Luminar of Each Pole Fitting = 2 No’s
  • Luminar Watt =250 Watt

Cable Detail:

  • Size of Cable= 4CX10 Sq.mm.
  • First Pole is connected in R Phase Next Pole is connected in Y Phase Than Next Pole is connected in B Phase. Next Pole is connected again R Phase.
  • Resistance of Cable=3.7 Ω/Km
  • Reactant of Cable=0.1 Ω/Km

214

Calculation:

Load of Each Pole

  • Load of Each Pole = (Watt of Each Luminar X No of Luminar ) / Volt X P.F
  • Load of Each Pole = (250X2) /(230X0.75)
  • Load of Each Pole = 2.9 Amp

For Pole Pole-1:

  • Pole Connected on “R” Phase
  • Total Distance of Pole for “R” Phase =50 Meter ,
  • % Voltage drop of Cable= (Current X (Rcosᴓ + JSinnᴓ) X Distance ) / (Volt X No of Cable X 1000)
  • % Voltage drop of Cable= (2.9x(3.7×0.75+0.1×0.66)X50 / (230x1x1000)
  • % Voltage drop of Cable= 0.18% ———————————(1)

For Pole Pole-2:

  • Pole Connected on “Y” Phase
  • Total Distance of Pole for “Y” Phase =50+50=100 Meter ,
  • % Voltage drop of Cable= (Current X (Rcosᴓ + JSinnᴓ) X Distance ) / (Volt X No of Cable X 1000)
  • % Voltage drop of Cable= (2.9x(3.7×0.75+0.1×0.66)X100 / (230x1x1000)
  • % Voltage drop of Cable= 0.36% ———————————(2)

For Pole Pole-3:

  • Pole Connected on “B” Phase
  • Total Distance of Pole for “B” Phase =50+50+50=150 Meter ,
  • % Voltage drop of Cable= (Current X (Rcosᴓ + JSinnᴓ) X Distance ) / (Volt X No of Cable X 1000)
  • % Voltage drop of Cable= (2.9x(3.7×0.75+0.1×0.66)X150 / (230x1x1000)
  • % Voltage drop of Cable= 0.54% ———————————(3)

For Pole Pole-4:

  • Pole Connected on “R” Phase
  • Total Distance of Pole for “R” Phase =150+50=200 Meter ,
  • % Voltage drop of Cable= (Current X (Rcosᴓ + JSinnᴓ) X Distance ) / (Volt X No of Cable X 1000)
  • % Voltage drop of Cable= (2.9x(3.7×0.75+0.1×0.66)X200 / (230x1x1000)
  • % Voltage drop of Cable= 0.72% ———————————(4)

For Pole Pole-5:

  • Pole Connected on “Y” Phase
  • Total Distance of Pole for “Y” Phase =200+50=250 Meter ,
  • % Voltage drop of Cable= (Current X (Rcosᴓ + JSinnᴓ) X Distance ) / (Volt X No of Cable X 1000)
  • % Voltage drop of Cable= (2.9x(3.7×0.75+0.1×0.66)X250 / (230x1x1000)
  • % Voltage drop of Cable= 0.9% ———————————(5)

For Pole Pole-6:

  • Pole Connected on “B” Phase
  • Total Distance of Pole for “B” Phase =250+50=300 Meter ,
  • % Voltage drop of Cable= (Current X (Rcosᴓ + JSinnᴓ) X Distance ) / (Volt X No of Cable X 1000)
  • % Voltage drop of Cable= (2.9x(3.7×0.75+0.1×0.66)X300 / (230x1x1000)
  • % Voltage drop of Cable= 1.07% ———————————(6)

For Pole Pole-7:

  • Pole Connected on “R” Phase
  • Total Distance of Pole for “R” Phase =300+50=350 Meter ,
  • % Voltage drop of Cable= (Current X (Rcosᴓ + JSinnᴓ) X Distance ) / (Volt X No of Cable X 1000)
  • % Voltage drop of Cable= (2.9x(3.7×0.75+0.1×0.66)X350 / (230x1x1000)
  • % Voltage drop of Cable= 1.25% ———————————(7)

For Pole Pole-8:

  • Pole Connected on “Y” Phase
  • Total Distance of Pole for “Y” Phase =350+50=400 Meter ,
  • % Voltage drop of Cable= (Current X (Rcosᴓ + JSinnᴓ) X Distance ) / (Volt X No of Cable X 1000)
  • % Voltage drop of Cable= (2.9x(3.7×0.75+0.1×0.66)X400 / (230x1x1000)
  • % Voltage drop of Cable= 1.43% ———————————(8)

For Pole Pole-9:

  • Pole Connected on “B” Phase
  • Total Distance of Pole for “B” Phase =400+50=450 Meter ,
  • % Voltage drop of Cable= (Current X (Rcosᴓ + JSinnᴓ) X Distance ) / (Volt X No of Cable X 1000)
  • % Voltage drop of Cable= (2.9x(3.7×0.75+0.1×0.66)X450 / (230x1x1000)
  • % Voltage drop of Cable= 1.61% ———————————(9)

Total Voltage Drop:

  • Voltage Drop in “R” Phase = 0.18+0.72+1.25 =2.15 %
  • Voltage Drop in “Y” Phase =0.36+0.90+1.43 =2.69 %
  • Voltage Drop in “B” Phase =0.54+1.07+1.61 =3.22 %
  • % Voltage drop in each Phase is Max 3.22% Which is less than 4%

Results:

Phase No of Pole Load (Amp) Voltage Drop
R 3 9 2.15 %
Y 3 9 2.69 %
B 3 9 3.22 %
Total 9 9 2.55 %

26 Responses to Calculate Cable Voltage Drop for Street Light Pole

  1. Atiku Muiz's avatar Atiku Muiz says:

    Sent from my BlackBerry 10 smartphone. From: Electrical Notes & ArticlesSent: Monday, 8 February 2016 16:01To: kabolag@yahoo.comReply To: Electrical Notes & ArticlesSubject: [New post] Calculate Cable Voltage Drop for Street Light Pole‎

    a:hover { color: red; } a { text-decoration: none; color: #0088cc; } a.primaryactionlink:link, a.primaryactionlink:visited { background-color: #2585B2; color: #fff; } a.primaryactionlink:hover, a.primaryactionlink:active { background-color: #11729E !important; color: #fff !important; }

    /* @media only screen and (max-device-width: 480px) { .post { min-width: 700px !important; } } */ WordPress.com

    Jignesh.Parmar posted: “Example: Calculate Voltage drop of Cable for Street Light Pole. System Voltage is 230V (P-N), Power Factor=0.75. Allowable Voltage Drop = 4% .The Detail of Pole & cable are

    Pole Detail:

    Section feeder Pillar is 50 meter away from Pole-1 Distance b”

    • mafumo Hlengani Thomas's avatar mafumo Hlengani Thomas says:

      what size of cable can i use to connect 30 street lights on 6m pole .
      the street light are 40watts led and 18m between poles.
      the total length is 540m

  2. ayman zaher's avatar ayman zaher says:

    dear engineer Jignesh.Parmar

    I really appreciate that so much knowledge and experience you gave for all the follower

    only i have 1 confuse about the equation of ( r cos phi + j xsin phi ) actually i found some website use the direct summation not vectorial i mean they use rcos phi + xsin phi

    instead of sqrt ( (rcos phi) ^2 + ( x sin phi ^2) even the values you used in the example is like that

    is it an approximation or what because I think the right is using the vectorial formula
    pls advice
    best regards
    ayman zaher

  3. Abdul Kalam's avatar Abdul Kalam says:

    As more and more number of poles gets connected to each phase, load on the previous sections of the cable also will increase…. it is not reflected here…only cable length increase is noted.

  4. Amit Gupta's avatar Amit Gupta says:

    Dear Sir the value of current that you have used for calculating voltage drop is the current that an individual fixture required but before first pole the value of current should be 2.9*3=8.7 amps. Correct me if I’m wrong pls.
    Thank you

    • Ankit Tripathi's avatar Ankit Tripathi says:

      Your question is right but think again…this is a calculation of voltage drop at each individual pole due to the fixtures on that particular pole and then we sum up all of them. Your point is valid if we were using a single core cable.

  5. Dear Jignesh sir
    what should be the resistance & capacitance between a motor to earth. how it is measured

  6. md.rahmat ullah's avatar md.rahmat ullah says:

    calculation is not perfect please specify at the end how did you calculate because at end it comes 411.945/230000=0.0017910652 % how i find it 18% for 1st pole pleasereply

  7. md.rahmat ullah's avatar md.rahmat ullah says:

    Calculation is not perfect please specify at the end how did you calculate because at end it comes 411.945/230000=0.0017910652 % how i find it 18% for 1st pole please reply

  8. Referring to %VD for the street lighting, 2.9A current per pole is a single phase current. In this case, you have to multiply the %VD by 2 to comply with single phase VD formula.
    Commented by:
    Engr. B. M. Rashad
    Electrical Section Head
    B.Sc.pk., B.Sc.Engg.phil., M.Sc.Engg.phil.
    Sr. Electrical Design Engineer
    for Building Services & Infrastructure Networks (23 years of experience with US Army Corps of Engineers Design Consultants and European Design Consultants
    Contact email: mr@adeng.com.sa

    • ayman zaher's avatar ayman zaher says:

      Hello mr B? M.Rashed
      Mo current suposed to pass in neutral because its 3 phase balanced load up to the fuse box of the lighting pole

      • JUN.19, 2016
        Dear Engr. Ayman Zaher

        It is understood that for 3-phase balanced circuits, the neutral current turns out to be zero, but the issue is not that at all. Since your %VD is based on single phase, so going back to IEC-60364, you have to use single phase formula for calculating the single phase %VD. So, do revise your single phase %VD calculation accordingly to meet with the code requirements of IEC-60364 for the 1-phase %VD of street lighting poles. You cannot change the 1-phase %VD formula.

        Awaiting for your feedback.
        Engr. BMR

    • Shafi Khan's avatar Shafi Khan says:

      your are right. if single phase so multiply by 2. if 3 phase so multiply by sqrt(3)

  9. JUNE 05, 2016
    Dear Engr. Jignesh,

    I am a Sr. Electrical Design Engineer. I am into the design of building services and infrastructure networks having 23 years of electrical design experience with international foreign design consultants. The design is based on CIE, IESNA, NFPA, IEEE, IEC standards and codes.

    I have gone through your calculations for %VD and my comment is that you have to multiply the %VD by 2 based on VD formula for single phase.

    Awaiting for your feedback.
    Regards

    Engr. B. M. Rashad
    Electrical Section Head
    B.Sc.(pk.), B.Sc.Engg.(phil.), M.Sc.Engg.(phil.)
    Sr. Electrical Design Engineer
    for Building Services and Infrastructure Networks

    Contact email: mr@adeng.com.sa

  10. AYMAN ZAHER's avatar AYMAN ZAHER says:

    thanks for nice reply
    no one can change the formula of voltage drop calculation at single phase
    BUT IF IT REALLY THE CASE FOR SINGLE PHASE

    why vd for single phase is 2*I *L (RCOS PHI + X SIN PHI ) ?
    BECAUSE THE CURRENT GO IN LINE AND RETURN IN NEUTRAL SO THE TOTAL PATH IS DOUBLE LENGTH AND WE USE 2 ,
    NOTHE THIS IS NOT THE CASE WE DISCUSS

    SUPPOSE WE HAVE BALANCED 3 PHASE (NO AMPERS IN NEUTRAL )
    THE PATH WILL ONLY BE LINE AND VOLTAGE DROP WILL BE I*L (RCOS PHI + X SIN PHI )
    FOR 1 PHASE AS PHASE VALUE

    FOR LINE VALUE VOLTAGE DROP = SQRT3 * I * L ( R COS PHI + X SIN PHI)

    AND AS YOU CAN NOTICE THIS IS THE FORMULA FOR THREE PHASE ALSO
    SO THERE IS NO CONTRADICTION THE CASE OF SINGLE PHASE IN OUR EXAMPLE IS NOT AS IT APPEARS SINGLE PHASE ITS ACTUALLY HALF SINGLE PHASE

    YOU CAN SEE THEY ARE IDENTICAL AND THAT IS THE LOGIC

    AMAAZ1972@GMAIL.COM

    SENIOR ELECTRICAL ENGINEER
    KHATIB ALAMI CONSULTANTS

    • Eng.Rashad Bhatti's avatar Eng.Rashad Bhatti says:

      Dear Engr. Ayman Zaher

      Pls. refer to the attached VD calculation sheets for your info. and further discussions, if any.

      Regards

      Engr. BMR

    • vishnu's avatar vishnu says:

      Sir, we are planning to replace over head LT line with UG cables for a length of 2.5KM perimeter lights. can you guide me to estimate the cable sizes and other details

  11. Helmy nizad ismail's avatar Helmy nizad ismail says:

    Fyi,Three-phase system with neutral point completely unbalanced is considered single-phase system…thanks.

  12. Pavan Kumar's avatar Pavan Kumar says:

    Dear Sir,
    How to calculate the power Losses in Transmission Line. For Ex. i am running 12MVA at 132KV transmission line for 25KM using ACSR Panther Conductor. What will be losses. Is there any Calculation

  13. isaac's avatar isaac says:

    Going through a document, I discover that the cable used on a circuit for street light were varied; i.e 4 x 25mmsq, 4 x 16mmsq…. Is that standard? at what point do we have to varied the cable if it is a standard

  14. Gamal's avatar Gamal says:

    dear Mr. Jingesh,
    How to calculate voltage drop for each pole individually without considering the total current entering the cable for the remaining phase poles? regards

  15. Gokul Gopi's avatar Gokul Gopi says:

    thank you very much for your effort here MR. Jignesh .

  16. GAJENDRA SINGH's avatar GAJENDRA SINGH says:

    Dear Mr. Jignesh,

    You are considering the 2.9A Load on pole 1 to calculate the voltage drop from feeder pillar to first pole. If you see that on this cable (Feeder Pillar to first pole), load will be come for all the 9 nos. poles.

    Regards,
    Gajendra Singh
    Mob: 8130282606

  17. NITEESH's avatar NITEESH says:

    Sir please help me

Leave a Reply

Discover more from Electrical Notes & Articles

Subscribe now to keep reading and get access to the full archive.

Continue reading