Calculate Size of Contactor, Fuse, C.B, Over Load Relay of DOL Starter

Calculate Size of Contactor, Fuse, C.B, O/L  of DOL Starter

  • Calculate Size of each Part of DOL starter for The System Voltage 415V ,5HP Three Phase House hold Application Induction Motor ,Code A, Motor efficiency 80%,Motor RPM 750 ,Power Factor 0.8 , Overload Relay of Starter is Put before Motor.

Basic Calculation of Motor Torque & Current:

  • Motor Rated Torque (Full Load Torque) =5252xHP/RPM
  • Motor Rated Torque (Full Load Torque) =5252×5/750=35 lb-ft.
  • Motor Rated Torque (Full Load Torque) =9500xKW/RPM
  • Motor Rated Torque (Full Load Torque) =9500x(5×0.746)/750 =47 Nm
  • If Motor Capacity is less than 30 KW than Motor Starting Torque is 3xMotor Full Load Current or 2X Motor Full Load Current.
  • Motor Starting Torque=3xMotor Full Load Current.
  • Motor Starting Torque==3×47=142Nm.
  • Motor Lock Rotor Current =1000xHPx figure from below Chart/1.732×415

Locked Rotor Current

Code

Min

Max

A

1

3.14

B

3.15

3.54

C

3.55

3.99

D

4

4.49

E

4.5

4.99

F

5

2.59

G

2.6

6.29

H

6.3

7.09

I

7.1

7.99

K

8

8.99

L

9

9.99

M

10

11.19

N

11.2

12.49

P

12.5

13.99

R

14

15.99

S

16

17.99

T

18

19.99

U

20

22.39

V

22.4

 
  • As per above chart Minimum Locked Rotor Current  =1000x5x1/1.732×415=7 Amp
  • Maximum Locked Rotor Current =1000x5x3.14/1.732×415=22 Amp.
  • Motor Full Load Current (Line) =KWx1000/1.732×415
  • Motor Full Load Current (Line) = (5×0.746)x1000/1.732×415=6 Amp.
  • Motor Full Load Current (Phase)=Motor Full Load Current (Line)/1.732
  • Motor Full Load Current (Phase)==6/1.732=4Amp
  • Motor Starting Current =6 to 7xFull Load Current.
  • Motor Starting Current (Line)=7×6=45 Amp

(1) Size of Fuse:

Fuse  as per NEC 430-52

Type of Motor Time Delay Fuse Non-Time Delay Fuse

Single Phase

300%

175%

3 Phase

300%

175%

Synchronous

300%

175%

Wound Rotor

150%

150%

Direct Current

150%

150%

  • Maximum Size of Time Delay Fuse =300% x Full Load Line Current.
  • Maximum Size of Time Delay Fuse =300%x6= 19 Amp.
  • Maximum Size of Non Time Delay Fuse =1.75% x Full Load Line Current.
  • Maximum Size of Non Time Delay Fuse=1.75%6=11 Amp.

(2) Size of Circuit Breaker:

Circuit Breaker as per NEC 430-52

Type of Motor Instantaneous Trip Inverse Time

Single Phase

800%

250%

3 Phase

800%

250%

Synchronous

800%

250%

Wound Rotor

800%

150%

Direct Current

200%

150%

  • Maximum Size of Instantaneous Trip Circuit Breaker =800% x Full Load Line Current.
  • Maximum Size of Instantaneous Trip Circuit Breaker =800%x6= 52 Amp.
  • Maximum Size of Inverse Trip Circuit Breaker =250% x Full Load Line Current.
  • Maximum Size of Inverse Trip Circuit Breaker =250%x6= 16 Amp.

(3) Thermal over Load Relay:

  • Thermal over Load Relay (Phase):
  • Min Thermal Over Load Relay setting =70%xFull Load Current(Phase)
  • Min Thermal Over Load Relay setting =70%x4= 3 Amp
  • Max Thermal Over Load Relay setting =120%xFull Load Current(Phase)
  • Max Thermal Over Load Relay setting =120%x4= 4 Amp
  • Thermal over Load Relay (Phase):
  • Thermal over Load Relay setting =100%xFull Load Current (Line).
  • Thermal over Load Relay setting =100%x6= 6 Amp

(4) Size and Type of Contactor:

Application

Contactor

Making Cap

Non-Inductive or Slightly Inductive ,Resistive Load

AC1

1.5

Slip Ring Motor

AC2

4

Squirrel Cage Motor

AC3

10

Rapid Start / Stop

AC4

12

Switching of Electrical Discharge Lamp

AC5a

3

Switching of Electrical Incandescent Lamp

AC5b

1.5

Switching of Transformer

AC6a

12

Switching of Capacitor Bank

AC6b

12

Slightly Inductive Load in Household or same type load

AC7a

1.5

Motor Load in Household Application

AC7b

8

Hermetic refrigerant Compressor Motor with Manual O/L Reset

AC8a

6

Hermetic refrigerant Compressor Motor with Auto O/L Reset

AC8b

6

Control of Restive & Solid State Load with opto coupler Isolation

AC12

6

Control of Restive Load and Solid State with T/C Isolation

AC13

10

Control of Small Electro Magnetic Load ( <72VA)

AC14

6

Control of Small Electro Magnetic Load ( >72VA)

AC15

10

  • As per above Chart
  • Type of Contactor= AC7b
  • Size of Main Contactor = 100%X Full Load Current (Line).
  • Size of Main Contactor =100%x6 = 6 Amp.
  • Making/Breaking Capacity of Contactor= Value above Chart x Full Load Current (Line).
  • Making/Breaking Capacity of Contactor=8×6= 52 Amp.

72 Responses to Calculate Size of Contactor, Fuse, C.B, Over Load Relay of DOL Starter

  1. asimali856's avatar asimali856 says:

    thanks……sir

      Thanks & regards  

    Asam Ali

    Al Mariah United Group Abu Dhai – U.A.E Cell No.: +971 567077962

    ________________________________

  2. Chauhan Ajit's avatar Chauhan Ajit says:

    well………..

  3. Tamer's avatar Tamer says:

    why did you eliminate the efficiency of the motor & the p.f value from your calculations ?

    I think the rated current =(5*746)/(1.732*415*0.8*0.8)=8 Amp.

    Thanks

  4. Rudru Naikar's avatar Rudru Naikar says:

    send me diploma cet question papers

  5. dushyant kumar's avatar dushyant kumar says:

    good materil

  6. Mohan's avatar Mohan says:

    very useful notes u provided, keep doing this

  7. Arun S's avatar Arun S says:

    Dear Sir,
    What is mean by Instantaneous Trip and Inverse Trip for Size of Circuit Breaker?

    Regards
    Arun S

  8. Krishna's avatar Krishna says:

    What does 3.31,3.7,4.6,0.37,2.95 values indicate sir in DOL Starter sizing calculations

  9. jaikumar's avatar jaikumar says:

    Interesting&knowledgeable hope to see more quality& informative articles

  10. viral makwana's avatar viral makwana says:

    Motor name plate do not indicate locked rotor current code, how to know that?

  11. BASANAGOWDA PATIL's avatar BASANAGOWDA PATIL says:

    Why normally relay setting is 1.3 times of the motor HP.Is there any exact formula to calculate the same ?

    How to calculate relay setting for motors with different RPM.Ex.10 HP/1000 RPM,10HP/1500 RPM, 10 HP/3000 RPM.

  12. mohd shamse alam's avatar mohd shamse alam says:

    Sir may you tell me to setting of relay 3 phase 10 hp motor 380 volts cos.8 And how to calculate please tell formula’s

  13. Harish's avatar Harish says:

    superbbbbbbbbbbbbbbb

  14. abbas's avatar abbas says:

    please tell me about overload, mcb, mccb,fuses selection about dol ,star delta starter in

  15. RAHUL's avatar RAHUL says:

    Dear sir

    Thanks for the valuable information.For 5 HP motor the letter code is A or F. This is my doubt. please make it clear if you are free sir.

    warm regards

  16. Hector's avatar Hector says:

    Hi, first of all, thanks for sharing this information. Second, I have a question: Doesn’t the contactor should be sized in comparison with the conductor size?, which must be 125% of the FLA of the load (If PF is higher or equal than 0.8). I make this cuestion because if the conductors are sized 125% of the FLA, and the contactor sized on 100%, there might be a voltage drop, or a hot spot in the contactor. What do you think, sir?

  17. Tuhin Mia's avatar Tuhin Mia says:

    Thank You Sir.
    Tuhin
    From
    Bangladesh
    Mobile:+8801712427773

  18. pankaj patel's avatar pankaj patel says:

    3+N

  19. Steve Arreola's avatar Steve Arreola says:

    Thank you Sir…Greetings from West Texas

  20. Jinesh akabari's avatar Jinesh akabari says:

    What is calculation of 5hp ,415v induction motor protection panel ?

  21. Henry's avatar Henry says:

    Hi there I have an under floor heating matt with a full load of 10000kw/ 42 amps.

    Wanted to no what size contactor I would need
    Thanks Henry

  22. sudesh's avatar sudesh says:

    how it can be possible that a 5 hp motor is rated for 47 A. as u have taken 47A. for calculating motor starting torque (i.e. at the Basic Calculation of Motor Torque & Current topic). Plz tell me sir..

  23. Mr. SOVANN's avatar Mr. SOVANN says:

    Hello Sir, I am Mr.Sovann,I am living in Cambodia. I would like to ask u some question. My country use 380v for three phase, and 220v for single phase, 50Hz, and Pf 0,85.
    Question: i have a motor thee phase, its power is 3kw. but i don’t know how to choose a Motor Circuit Breaker, a Contactor, an overload relay,and its cross-section area of wire to be suit with it. Could u show me how to choose all of that devices? or could i have some of formulas about them?
    Thanks in advance
    Good luck!

  24. dinesh das's avatar dinesh das says:

    Well.I hope,I will learn more….

  25. vicky's avatar vicky says:

    good

  26. Jagat's avatar Jagat says:

    wat is d difference between slip ring induction motor and squirrel cage.??

  27. waleed khalid's avatar waleed khalid says:

    what is the different will occure if we use method of starting like star delta or soft starter

  28. prabhu's avatar prabhu says:

    thanks

  29. Rohit's avatar Rohit says:

    sir pls tell me the overload relay size for 45 kw 3 ph motor

  30. Raj's avatar Raj says:

    Actually, it is very useful.

  31. Jignesh's avatar Jignesh says:

    Hi Sir,

    Good to know that you are tremedous on Electrical calculations tools in excel itself.

    Would like to have help on Motor FLA Calculation Sheet,Contactor sizes ( NEMA ).

    Sharing your knowledge in such a platform is appreciable matter.

    Thanks,
    Jignesh vaghela
    Jignesh22
    1085@gmail.com

  32. Sakthivel's avatar Sakthivel says:

    how to calculate power contactor coil current.

  33. manuel joseph's avatar manuel joseph says:

    it is very good for improving knowledge

    thanks

  34. Vinod Kumar's avatar Vinod Kumar says:

    Super sir

  35. Thaink you's avatar Thaink you says:

    Thaink you

  36. chirag chaniyara's avatar chirag chaniyara says:

    plz give 11 KW slip ring induction motor installation,commissioning and installed equipment list?

  37. sivasubramaniyam's avatar sivasubramaniyam says:

    sir, the fuse rating formula come ac and dc load or same?

  38. Durga Khatri's avatar Durga Khatri says:

    please give me the rating of MCCB contractor and types of starter for the squirrel cage induction motor of 112Kw ??? that need to operate blending blower in cement industry.

  39. D.SUGANYA's avatar D.SUGANYA says:

    how to find fuse rating of 3 phase induction motor

  40. Ken's avatar Ken says:

    Your information about fuse size for motors was helpful as I have been searching for a simple table to give me some sense of the accuracy of my calculations. Thank you. But I must inform you that I looked further and I now know that there is an error in your NEC 430.52 table. You have the multiplier factors under the wrong headings. In other words, they are reversed. For a Single Phase Motor (for example), your table shows a Non-Time Delay Fuse value of 175% of FLC and 300% for a Dual Element (Time Delay Fuse). In fact the NEC 430.52 table shows that For a Single Phase Motor a Non-Time Delay Fuse should be 300% of FLC and 175% for a Dual Element (Time Delay Fuse). Your math example below your table is also incorrect because it follows the reversed data from the table. I only point this out because I have much respect for you and have read good advice from you many times. I checked a few other sources and your table is the only one with the reversal. I would not want your readers to be misled as I know you would not either. Thank you for sharing your wisdom online. Be well,

  41. artium's avatar artium says:

    How to size conatctors for wound rotor motor 400V 132KW?

  42. ijaz ali's avatar ijaz ali says:

    thank u soo much it, s was too good!

  43. Chinnappan's avatar Chinnappan says:

    Thank you Sir.
    I have feed it in to Excel sheet with formulae for future reference.
    Similarly I want to know for resistive (heater) load. Kindly help me.

  44. karthick's avatar karthick says:

    Sir,
    How do i calculate the Contactor Ratting by only with the known values oh KW,V,& A

  45. sachidananda Pradhan's avatar sachidananda Pradhan says:

    what are the equipment required for 1 hp, 2 hp ,3 hp, 1/2 hp, 20 hp, 25 hp and 30 hp motors dol sarter. both power and control connection.

  46. Jadhav swapnil A's avatar Jadhav swapnil A says:

    very fine information of electrical

  47. Nayeem. Shaik's avatar Nayeem. Shaik says:

    How to get electrical license to commission electrical substation’s ? What is the process how they will give license? Sir please notify me sir.

  48. RIKIN SHARMA's avatar RIKIN SHARMA says:

    ACTUALLY IM ITI HOLDOR SO I DONT KNOW ABOUT STARTING TORQUE AND ETC , SO I WANTTO KNOW THAT HOW WE CAN CALCULATE CONTECTOR SIZE FROM HP/ KW OF MOTOR .

  49. Andrew's avatar Andrew says:

    xcellent reference. thank-you

  50. mano's avatar mano says:

    I have 3phase 415v 1 HP inductive motor.rpm 1440.so how to calculate a suitable d.o.l.starter and therma overloal relay?

  51. Amna Ali Butt's avatar Amna Ali Butt says:

    What happens when a synchronous generator stops? Does it
    (i) Supply MVA and MVAR
    (ii) absorb MVA and MVAR
    (iii) Absorb MVAR and supply MVA
    (iv) Absorb MVA and supply MVAR
    and why?

  52. Nirmal Choudhury's avatar Nirmal Choudhury says:

    I need to operate a 150 HP induction motor (Centrifugal motor pump set) having 185 Amp power rating. What contractor rating will be suitable along with overload relays etc.

    Thanks,
    Nirmal Choudhury.

  53. basith's avatar basith says:

    Dear all,

    if you have any excel formula for starter selection.please forward me

  54. Zia's avatar Zia says:

    can I use this for single phase 1 HP motor????
    thanks in advance.

  55. Nahidh's avatar Nahidh says:

    Thanks , useful post , but I think there is a printing mistake in Code F Min and Max values for locked rotor currents , the Max. cant be less than Min.

  56. Masud's avatar Masud says:

    Thanks

  57. m.praveen's avatar m.praveen says:

    i have 5 different ratings of motors i.e:15 kw,5.5 kw,4.0 kw,3.7 kw&3.27 kw ,for this mpcbs ,contactors &over load relays ratings should be done.please give me exact ratings details.ok

  58. syam's avatar syam says:

    I have 3 different types of single phase motors 1 hp ,2 hp,3 hp I need to contractor & thermal over load relay which rating i have selecting please
    suggest me…

  59. Manivannan's avatar Manivannan says:

    Very useful.

  60. Pingback: Pirating of Technical Works-2 | Electrical Notes & Articles

  61. Shatrughan kohar's avatar Shatrughan kohar says:

    15 Hp motor how many VA contactor, OLR, push bottom and SP mcb used please help us sir

  62. Star delt starter 15 hp motor how many va contactor used

  63. Lokesh verma's avatar Lokesh verma says:

    10 HP motar ke liye relay,contractor,fuse ,mcb salect kar ke do

  64. Iqbal's avatar Iqbal says:

    What kind of contactor and timer choose for 800W LED signage board make automatically switching

  65. Iqbal's avatar Iqbal says:

    Sir;
    What kind of contactor and timer choose for 800W LED signage board make automatically switching
    LED lights resistive load or inductive

  66. pramod kumar's avatar pramod kumar says:

    sir hp se ketne tayp ka contactor motor me lagega sir mujko formula batao sir pdf ke sath vedio sir

  67. Atul's avatar Atul says:

    According to NEC Max size of CB shown as 250%. But in reality if we check catalogs of particular companies like ABB,AB,Siemens etc. where all components are selected including CB but those are not 250%. Why this is so?

Leave a Reply

Discover more from Electrical Notes & Articles

Subscribe now to keep reading and get access to the full archive.

Continue reading