Quick Reference-Fire Fighting (Part-4)

 

Suction and Delivery Pipes of Pumps Fire Pump (CPWD)

Pump Capacity Suction (Minimum) Delivery (Minimum)
450 LPM 50 mm 50 mm
900 LPM 70 mm 50 mm
1400 LPM 100 mm 100 mm
2280 LPM 150 mm 150 mm
2850 LPM 200 mm 150 mm
4540 LPM 250 mm 200 mm

 

SELECTION OF ORIFICE PLATE (CPWD)

Pressure Loss Kg/cm2 Diameter of Orifice (mm)
80 MM PIPE 100 MM PIPE
3.5 41.9
3 43
2.5 44.8
2 46.4
1.5 48.9 56.2
1 52.3 57.6
0.9 53.2 59
0.8 54.1 60.4
0.7 55.3 62
0.6 56.6 63.9
0.5 58.2 66.5
0.4 59.8 69.7
0.3 62 74.2
0.2 65 81.1
0.1 82.2

 

FLANGE THICKNESS (CPWD)

Pipe diameter Flange Thickness
200 mm 24 mm
150 mm and 125 mm 22 mm
100 mm and 80 mm 20 mm
65 mm 18 mm
40 mm and below 16 mm
Gasket thickness shall not be less than 3 mm.
Mild steel flanges shall be in accordance with Table:17 of IS : 6392

 

Sprinkler Spacing, Arrangement, Distribution and Locations (CPWD)

(i) Maximum Area Coverage per Sprinkler
(a) Ceiling sprinkler 12 m2
(b) Side wall sprinkler :
Combustible ceiling 7.5 m2
Non-Combustible ceiling 9 m2
(ii) Maximum Distance between Sprinklers
(a) Ceiling sprinkler 3.5 Meter
(b) Side wall sprinkler
(i) Combustible ceiling 2.7 Meter
(ii) Non-combustible ceiling 3 Meter
(iii) Minimum Distance between Sprinklers (for Ceiling as well as Sidewall sprinklers)  1.8 Meter
Note: In case of intermediate ceiling suspended sprinklers, protecting commodities in racks, distance lower than 1.8 Meter may be considered if necessary.
Maximum distance of sprinklers from end walls : it shall not exceed half of the allowable distance between sprinklers
Note: For ceiling sprinklers:
a) where the external walls are combustible or built with metallic or otherwise or open sided; and in case of open joisted ceilings or where the roof has the rafters exposed, the distance between the boundary and the sprinklers shall not exceed 1.5 Meter.
b) Distance shall be measured perpendicular to the wall.
Sprinklers shall not be located at a distance less than 100 mm from the wall (for ceiling sprinklers).
Sprinklers shall not be located at a distance less than 100 mm from the end wall (for sidewall sprinklers)

 

Table 9.7 Guidelines for stocking spare sprinkler (CPWD)

HAZARD CLASS All state capitals and within 200 Km Other locations
Light 5 sprinklers of each type 15
Moderate/Ordinary 15 sprinklers of each type 25
High & storage 30 sprinklers of each type 50

 

Sidewall Sprinkler Location in Relation to Obstructions
(lighting, fan and similar fixtures) -Facing across the wall ( CPWD-Table 9.2)

Distance (A) between Sprinklers and the Obstruction on Side (mm) Maximum allowable Distance (B) between Deflector above bottom of Obstruction when Sprinkler can be allowed
Up to 1200 Not allowed
More than 1200 but less than 1500 25
More than 1500 but less than 1650 50
More than 1650 but less than 1800 80
More than 1800 but less than 1950 100
More than 1950 but less than 2100 150
More than 2100 but less than 2250 180
More than 2250 but less than 2400 230
More than 2400 but less than 2550 280
More than 2550 350

Sidewall Sprinkler Location in Relation to Obstructions (lighting, fan and similar fixtures)-Along the same wall (CPWD-Table 9.3 )

Distance (A) Between Sprinklers and the Obstruction on Side (mm) Maximum allowable Distance (B) between Deflector above bottom of Obstruction when Sprinkler can be allowed
100 to 150 25
More than 150 but less than 300 50
More than 300 but less than 450 80
More than 450 but less than 600 115
More than 600 but less than 750 150
More than 750 but less than 900 180
More than 900 but less than 1050 200
More than 1050 but less than 1200 230
More than 1200 but less than 1350 250
More than 1350 but less than 1500 300
More than 1500 but less than 1650 330
More than 1650 but less than 1800 350
More than 1800 but less than 1950 380
More than 1950 but less than 2100 430
More than 2100 but less than 2250 450

Sprinkler Location Below Ceilings [Clause 9.4.7.1],Table 9.1 (CPWD)

Type of ceiling Distance below ceilings (in mm)
MIN MAX PREFERRED
Combustible, asbestos cement sheets, wired glass and frangible 75 300 150
Combustible with exposed rafters and/or open joists 75 150
Non-combustible – either plane or arched or sloping 75 450 300

 

No of Sprinkler (NFPA-13)

PIPE SIZE Light hazard (Table 14.5.2.2.1)   Ordinary Hazard (Table 14.5.3.4) Extra Hazard
STEEL COPPER STEEL COPPER STEEL
25MM 2 Nos 2 Nos 2  Nos 2  Nos 1  Nos
32MM 3 Nos 3  Nos 3  Nos 3  Nos 2  Nos
40MM 5 Nos 5  Nos 5  Nos 5  Nos 5  Nos
50MM 10 Nos 12  Nos 10  Nos 12  Nos 8  Nos
65MM 30 Nos 40  Nos 20  Nos 25  Nos 15  Nos
80MM 60 Nos 65  Nos 40  Nos 45  Nos 27  Nos
85MM 100 Nos 115  Nos 65  Nos 75  Nos 40  Nos
100MM >100 Nos Check System Protection Area & Use Ordinary Hazard Pipe Schedule 100  Nos 115  Nos 55  Nos
125MM 160  Nos 180  Nos 90  Nos
150MM 275  Nos 300  Nos 150  Nos
200MM >275 Nos Check System Protection Area

 

Number of Sprinklers Above and Below a Ceiling (NFPA-13) Table 14.5.2.4

PIPE SIZE Light hazard (Table 14.5.4)   Ordinary Hazard (Table 14.5.7)
STEEL COPPER STEEL COPPER
25MM 2 Nos 2 Nos 2 Nos 2 Nos
32MM 4 Nos 4 Nos 4 Nos 4 Nos
40MM 7 Nos 7 Nos 7 Nos 7 Nos
50MM 15 Nos 18 Nos 15 Nos 18 Nos
65MM 50 Nos 65 Nos 30 Nos 40 Nos
80MM 60 Nos 65 Nos

 

Maximum and Minimum Distance for  Upright and Pendent sprinklers (NFPA 13) TABLE-10.2.4.2.1

Type of Hazard Sprinklers to Walls Sprinklers to Sprinklers Remarks
Minimum Distance Maximum Distance Minimum Distance Maximum Distance
Light Hazard 100 mm 2.3 Meter 1.8 Meter 4.6 Meter
Ordinary Hazard 100 mm 2.3 Meter 1.8 Meter 4.6 Meter
Extra Hazard 100 mm 1.8 Meter 1.8 Meter 3.7 Meter Water density ≥ 0.25 gpm/ft2
100 mm 2.3 Meter 1.8 Meter 4.6 Meter Water density < 0.25gpm/ft2
High-Piled Storage  1.8 Meter 3.7 Meter Water density ≥ 0.25gpm/ft2
1.8 Meter 4.6 Meter Water density < 0.25gpm/ft2

 

Fire Pipe Hanger Rod Size (NFPA-13) Table 17.2.3.5.1

PIPE SIZE Hanger Rod  Size Distance Between Hanger
Up to 32MM 10MM 3.7 Meter
40MM to 100MM 10MM 4 Meter
120MM to 200MM 13MM 5 Meter
250MM 16MM
300MM 20MM

 

U-Hook Rod Sizes (NFPA-13) Table 17.2.1.4

Pipe Size Diameter of Rod
UP TO 50 MM 8
65 to 150 MM 10
200 MM 13

 

PIPE SUPPORT SPACING (CPWD)

Nominal Pipe Size Spacing
Up to 25MM 2 METER
32MM  to 125MM 2.5 METER
150MM and above 3 METER
Extra supports shall be provided at the bends and at heavy fittings like valves to avoid undue stress on the pipes.

 

Distance Between Pipe Supports  IS 15105 (Clause 10.3.10)

Pipe Diameter Spacing
Upto65mm 4.0m
65mmto 100mm  6.0 m
100 mm to 250 mm 6.5 m
For Distribution Pipes
(a) The first support on a nominally horizontal distribution pipe shall not be more than 2 meters from the main distribution pipe.
(b) The last support on a nominally horizontal distribution pipe shall not be more than 450 mm from the end.
c) Drop or rise pipes shall be secured to the building structure either directly or indirectly at the adjacent nominally horizontal part of the pipe within 300 mm of the drop or rise.

 