Calculate Size of Neutral Earthing Transformer (NET)

Calculate Size of Neutral Earthing Transformer (NET) having following details

 Main Transformer Detail :

  • Primary Voltage(PVL): 33KV
  • Secondary Voltage (SVL): 11 KV
  • Frequency(f)=50Hz
  • Transformer Capacitance / Phase(c1)=0.006 µ Farad
  • Transformer Cable Capacitance / Phase(c2)= 0003 µ Farad
  • Surge Arrestor Capacitance / Phase(c3)=0.25 µ Farad
  • Other Capacitance / Phase(c4)=0 µ Farad

Required for Neutral Earthing Transformer:

  • Primary Voltage of the Grounding Transformer (Vp) =11KV
  • Secondary Voltage of the Grounding Transformer (Vs) =240V
  • Neutral Earthing Transformer % Reactance (X%)=40%
  • % of Force field condition for Neutral Earthing Transformer (ff) =30%
  • Neutral Earthing Transformer overloading factor(Of)=2.6
  • Neutral Earthing Transformer Base KV (Bv) =240V=0.240KV

Calculation:

  • Phase to Neutral Voltage (Vp1) =SVL /1.732
  • Phase to Neutral Voltage (Vp1) =11 /1.732 = 6.35 KV
  • Phase to Neutral Voltage under Force Field Condition (Vf) =Vp + (Vpxff)
  • Phase to Neutral Voltage under Force Field Condition (Vf)=6.35+ (6.35×30%) =8.26KV
  • Total Zero Sequence Capacitance (C)=C1+C2+C3+C4
  • Total Zero Sequence Capacitance (C)=0.006+0.0003+0.25+0=0.47730 µ Farad
  • Total Zero Sequence Capacitance Reactance to Ground (Xc)=10×6 / (2×3.14xfxC)
  • Total Zero Sequence Capacitance Reactance to Ground (Xc)=10×6 / (2×3.14x50x0.47730)=6672.35 Ω/Phase
  • Capacitive charging current/phase (Ic)=Vf / Xc
  • Capacitive charging current/phase (Ic)=8.26×1000 / 6672.35 = 1.24Amp
  • Total Capacitive charging current (It) =3xIc
  • Total Capacitive charging current (It) =3xIc =3×1.24 =3.71Amp
  • Rating of Neutral Earthing Transformer (Pr)=VpxIt
  • Rating of Neutral Earthing Transformer (Pr)=11×3.71=40.83KVA
  • Size of Neutral Earthing Transformer (P)=Pr/ Of
  • Size of Neutral Earthing Transformer (P)=40.83/ 2.6 = 16KVA
  • Residual Capacitive reactance (Xct) =Xc/3
  • l Capacitive reactance (Xct) = 6672.35 /3 =2224.12Ω
  • Turns Ratio of the Grounding Transformer (N)= Vp/Vs =11000/240 =45.83
  • Required Grounding Resistor value at Secondary side (Rsec)=Xct/NxN
  • Required Grounding Resistor value at Secondary side (Rsec)=2224.12 /45.83×45.83 =1.059 Ω
  • Required Grounding Resistor value at primary side (Rp)=Xct
  • Grounding Resistor value at primary side (Rp)= 2224.12Ω
  • Neutral Earthing Transformer Secondary Current=P/Vs
  • Neutral Earthing Transformer Secondary Current=16000/230= 65.44Amp
  • Neutral Earthing Transformer Secondary Resistor Current (for 30 Sec)=1.3xItxN
  • Neutral Earthing Transformer Secondary Resistor Current (for 30 Sec)=1.3×3.71×45.83=221.18Amp
  • Neutral Earthing Transformer Reactance Base(Base X)=BvxBv/P/1000
  • Neutral Earthing Transformer Reactance Base(Base X)=0.24×0.24/11/1000=3.67Ω
  • Neutral Earthing Transformer Reactance in PU (Xpu)=X% =40%=0.04Pu
  • Neutral Earthing Transformer Reactance (X)=Xpu x BaseX
  • Neutral Earthing Transformer Reactance (X)=0.04×3.67 =0.15Ω
  • Neutral Earthing Transformer X/R Ratio=X/Rsec
  • Neutral Earthing Transformer X/R Ratio=0.15/1.059 = 0.14
  • Fault current through Neutral (single line to ground fault) (If)=Vp1/Rp
  • Fault current through Neutral (single line to ground fault) (If)=6.35×1000/2224.12 =2.86Amp
  • Short time Rating of Neutral Earthing Transformer=PxOf =16×2.6 =41KVA

Result:

  • Rating of Neutral Earthing Transformer (P)=40.83/ 2.6 = 16KVA
  • Short time Rating of Neutral Earthing Transformer=41KVA
  • Ratio of Neutral Earthing Transformer =11000/240 Volt
  • Neutral Earthing Transformer Secondary Current=65.44A
  • Required Grounding Resistor value at primary side (Rp)=2224.12Ω
  • Required Resistance at secondary side (Rsec)= 1.059Ω
  • Neutral Earthing Transformer Secondary Resistor Current (for 30 Sec)= 221.2A

17 Responses to Calculate Size of Neutral Earthing Transformer (NET)

  1. bala raman's avatar bala raman says:

    Dear sir,             ATS   (auto transfer switch) symbol fill  in Single line diagram

    Thanks&Regards K.Balaraman Ayyan electricals 9840768817

  2. isaac chibwe's avatar isaac chibwe says:

    Thank you , Sir Jignesh .regard isaac chibwe ampnet electrical services.

  3. Dennis's avatar Dennis says:

    This could be a great guide for electrical engineers looking to calculate the size of a neutral earthing transformer. It’s awesome that you listed the specific calculations for the voltages and frequencies for the main transformer. This information could be helpful for technicians who are running data centers, and looking for the exact voltage to get the job done. Thank you for such precise breakdown of the numbers!

  4. Shiv kumar's avatar Shiv kumar says:

    Very good knowledge sir

  5. Vivekanand Pandey's avatar Vivekanand Pandey says:

    Thank you sir for value able post

  6. Anthony Dickson Ojih's avatar Anthony Dickson Ojih says:

    Kindly explain how you get the factors used in calculating the value of Xc

  7. N.dhetchinamoorthy's avatar N.dhetchinamoorthy says:

    Please help HV to trive vector meter multification factor Formula

  8. Dear Jignesh.Parmar
    thanks for your explaniation
    but what is the base for your equations which used in the calculation
    thanks again

  9. Mohammed Rafi's avatar Mohammed Rafi says:

    Sir, Here i found that the grounding transformer has secondary voltage. how can the grounding transformer have secondary winding. please reply

  10. Md. Mostaq's avatar Md. Mostaq says:

    ok, Thank you. But how can we calculate the three phase four wire (star) AC impedance (resistance & reactance). Please give me answer.

  11. Pankaj Pal's avatar Pankaj Pal says:

    Hello Jignesh sir how to calculate the connected load of passenger lift ( 8 persons). Please ,will wait for your reply.

  12. Rafael's avatar Rafael says:

    Hello Mr. Jignesh: Why is the earthing transformer primary voltage (11 kV) a third of the three phase main transformer primary voltage (33 kV)? I have seem that many other authors say that it has to be the line to ground voltage of the main transformer (33 kV/1,73)

  13. Edson B. Henriques's avatar Edson B. Henriques says:

    thanks. The primary winding of the earthing transformer is 11kV (line-to-line voltage) and not 11/sqrt(3) because during the ground fault, the voltage in non fault winding will increase from 11/sqrt(3) to about 11kV, correct? And where I can find references of the neutral Earthing Transformer overloading factor (of) ?.

  14. Kirren's avatar Kirren says:

    Not a bad explanation. There are however many errors in the calculations which makes the article difficult to trust.

    For example:
    “Total Zero Sequence Capacitance (C)=0.006+0.0003+0.25+0=0.47730 µ Farad”
    The actual maths is incorrect. It should be
    0.006+0.0003+0.25+0=0.0.2563 µ Farad

    Also the next line.
    (Xc)=10×6 / (2×3.14x50x0.47730)=6672.35 Ω/Phase
    The solution provided here is also incorrect.

    Due to the number of errors I would not trust these calculations.

  15. Satheesh Kumar's avatar Satheesh Kumar says:

    Good explanation, kindly inform which standard has been followed

  16. Simhadri's avatar Simhadri says:

    Dear sir ,what is the size of cu strip to use for 2000kva or2500kva size transformer or dg nutral earthing? And what is short circuit with stand time for cu and c factor of copper?

Leave a Reply

Discover more from Electrical Notes & Articles

Subscribe now to keep reading and get access to the full archive.

Continue reading