Gland Size Selection

Gland Selection Table:

600 / 1000v stranded copper conductors pvc insulated with steel wire amour and PVC sheathed overall. (BS 6346 : 1997)

Cable Size Conductor

Numbers of Cores

Nom. Area (mm2)

Neutral

1

2

3

31/2

4

5

7

10

12

19

27

37

48

1.5

16

16

20S

20S

20S

20

20

25

25

32

32

2.5

20S

20S

20S

20S

20

25

25

25

32

32

40

4

20S

20

20

20

25

25

25

32

40

6

20

20

20

10

25

25

25

16

25

25

25

25

16

25

32

32

32

35

16

32

32

32

40

50

25

25

32

32

32

40

70

35

25

32

40

40

40

95

50

25

40

40

50S

50S

120

70

32

40

50S

50

50

150

70

32

50S

50

50

63S

185

95

32

50

50

63S

63

240

120

40

50

63S

63

75S

300

150

40

63S

63

75S

75

300

185

40

63

63

75

75

400

185

50S

63

75S

75

75

500

50

630

50

800

63S

1000

63

                             
                             
                             

600 / 1000v stranded copper conductors xlpe/swa/pvc cable and PVC sheathed overall.  (BS 5467 : 1989)

Cable Size Conductor

Numbers of Cores

Nom. Area (mm2)

Neutral

1

2

3

31/2

4

5

7

10

12

19

27

37

48

1.5

20S

20S

20S

20S

20S

20

25

25

32

32

32

2.5

20S

20S

20S

20S

20

25

25

32

32

40

40

4

20S

20S

20

20

25

25

25

32

40

40

50S

6

20

20

20

10

20

25

25

16

25

25

25

25

16

25

32

32

32

35

16

32

32

32

32

50

25

25

25

32

32

32

70

35

25

32

32

40

40

95

50

25

32

40

50S

50S

120

70

32

40

40

50

50

150

70

32

40

50S

50

50

185

95

32

50S

50

63S

63S

240

120

40

50

63S

63

63

300

150

40

63S

63

75S

75S

300

185

40

63S

63

75S

75

400

185

50S

63S

75S

75

75

500

50

630

50

800

63S

1000

63

 

Single Compression Heavy Duty as per IS12943
Cable Overload Diameter (mm)  
From

To

Nipple Thread in (mm)
9.0 12.0 16 x 1.5
12.0 15.0 16 x 1.5
12.0 15.0 20 x 1.5
15.0 18.0 20 x 1.5
16.0 20.0 25 x 1.5
20.0 24.0 25 x 1.5
24.0 28.0 32 x 1.5
28.0 32.0 40 x 1.5
33.0 37.0 40 x 1.5
37.5 42.0 50 x 1.5
43.0 48.0 50 x 1.5
49.0 54.0 63 x 1.5
55.0 60.0 63 x 1.5
61.0 66.0 75 x 1.5
67.0 72.0 75 x 1.5
73.0 78.0 82 x 1.5
79.0 84.0 90 x 1.5
84.5 92.0 100 x 1.5
93.0 100.0 110 x 1.5
101.0 115.0 125 x 1.5

 

ARMOUR CABLE (Single Compression Medium Duty)
Cable Overload Diameter (mm)  
From

To

Nipple Thread in (mm)
6.0 9.0 3/8″
9.0 12.0 1/2″
12.0 14.0 5/8″
14.0 16.0 3/4″
16.0 18.0 7/8″
18.0 21.5 1″
21.5 26.0 1 1/8″
26.0 31.0 1 1/4″
31.0 34.0 1 3/8″
34.0 38.0 1 1/2″
38.0 42.0 1 3/4″
42.0 48.0 2″
48.0 54.0 2 1/4″
54.0 60.0 2 1/2″
60.0 66.0 2 3/4″
66.0 72.0 3″
72.0 78.0 3 1/4″
78.0 84.0 3 1/2″
84.0 92.0 4″

 

UN-ARMOUR CABLE (Double Compression Medium Duty)
Cable Overload Diameter (mm)  
From

To

Nipple Thread Size
5.0 11.0 3/4″
11.0 14.0 3/4″
14.1 18.0 1″
18.1 20.0 1″
20.1 23.0 28 mm
23.1 26.0 1 1/4″
26.1 30.0 1 1/2″
30.1 33.0 1 1/2″
33.1 36.0 42 mm
36.1 41.0 2″
41.1 44.0 2″
44.1 52.0 2 1/2″
52.1 55.0 2 1/2″
55.1 60.0 70 mm
60.1 66.0 3″
66.1 75.0 3 1/4″
75.0 80.0 3 1/2″
81.0 90.0 4″
90.0 100.0 4 1/2″

 

ARMOUR CABLE (Double Compression Medium Duty)
Cable Overload Diameter (mm)  
From

To

Nipple Thread Size
6.0 12.0 3/4″
12.0 16.5 3/4″
16.5 18.5 3/4″
16.5 18.5 1″
18.5 20.0 1″
18.5 20.0 3/4″
20.0 23.0 1″
23.0 26.0 1″
23.0 26.0 1 1/4″
26.0 30.0 1 1/4″
26.0 30.0 1 1/2″
30.0 33.0 1 1/2″
30.0 33.0 1 1/4″
33.0 37.0 1 1/2″
37.0 41.0 2″
41.0 46.0 2″
46.0 52.0 2″
46.0 52.0 2 1/2″
52.0 54.0 2 1/2″
54.0 61.0 2 1/2″
61.0 66.0 3″
66.0 72.0 3″
72.0 78.0 3 1/4″
78.0 84.0 3 1/2″
84.0 94.0 4″
94.0 104.0 4 1/2″

————————————————————————————————————————-

7 Responses to Gland Size Selection

  1. Bala's avatar Bala says:

    Dear Jigesh sir,

    Your work is really helpful coz I have just started my career in T&D field. I am facing difficult understanding the schemes can you please guide me ?

  2. ZSiddiki's avatar ZSiddiki says:

    Dear Engr. Jigesh,
    your work is highly commendable. You have covered all facets of Electrical Engineering & Technology.
    I would like to have some wiring circuits/schematic diagrams of Power transformer tests like Power frequency voltage withstand test, induced voltage ,no load loss/ loaded loss measurements and temperature rise tests.
    Thanks

  3. palla's avatar palla says:

    hello jignesh what is S in gland selection table for 120 sqmm cable 3 core pl reply

  4. majdi's avatar majdi says:

    thanks for all data

  5. Dhinakaran's avatar Dhinakaran says:

    Gland details

  6. Gururaj's avatar Gururaj says:

    Dear sir i need CT sizing calculation in 110/11 KV switchyard

  7. D. China kumar's avatar D. China kumar says:

    Sir
    Can you please sisgust me for 350kw motors cable size as well as cable gland. Waiting for your early response. Soon
    Thanks
    D. Chinna
    Kenya

Leave a Reply

Discover more from Electrical Notes & Articles

Subscribe now to keep reading and get access to the full archive.

Continue reading