XLPE Cable-Current Rating
April 24, 2011 200 Comments
XLPE Insulated Armored & Unarmored Cables:
|
1.1 KV SINGLE CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I) |
|||||||||
| Cross-sectional area (Sq MM) |
UN-ARMOURED CABLE |
||||||||
|
Overall Diameter (mm) |
Normal Current Rating in Amps |
Short Circuit Current Rating for 1Sec.duration in K. Amps |
|||||||
|
Aluminums Conductor |
Copper Conductor |
Aluminums |
Copper |
||||||
| Ground | Duct | Air | Ground | Duct | Air | ||||
| 1cX4 |
8 |
— | — | — | 48 | 47 | 45 | 0.376 | 0.572 |
| 1cX 6 | 9 | 48 | 45 | 45 | 60 | 59 | 57 | 0.564 | 0.858 |
| 1cX10 | 10 | 62 | 62 | 61 | 80 | 78 | 77 | 0.940 | 1.430 |
| 1cX16 | 11 | 81 | 80 | 83 | 104 | 102 | 106 | 1.504 | 2.288 |
| 1cX25 | 12 | 99 | 90 | 115 | 130 | 115 | 145 | 2.350 | 3.575 |
| 1cX 35 | 13 | 117 | 110 | 135 | 155 | 140 | 175 | 3.290 | 5.005 |
| 1cX50 | 15 | 138 | 125 | 170 | 185 | 165 | 215 | 4.700 | 7.150 |
| 1cX70 | 16 | 168 | 155 | 210 | 225 | 200 | 270 | 6.580 | 10.01 |
| 1cX 95 | 18 | 204 | 185 | 255 | 265 | 235 | 330 | 8.930 | 13.59 |
| 1cX120 | 20 | 230 | 210 | 300 | 300 | 265 | 380 | 11.28 | 17.16 |
| 1cX150 | 22 | 265 | 230 | 342 | 335 | 300 | 430 | 14.10 | 21.45 |
| 1cX185 | 24 | 295 | 260 | 385 | 380 | 335 | 495 | 17.39 | 26.46 |
| 1cX240 | 27 | 340 | 300 | 450 | 435 | 385 | 590 | 22.56 | 34.32 |
| 1cX300 | 30 | 390 | 335 | 519 | 490 | 430 | 670 | 28.20 | 42.90 |
| 1cX400 | 33 | 450 | 380 | 605 | 550 | 480 | 780 | 37.60 | 57.20 |
| 1cX 500 | 36 | 500 | 430 | 700 | 610 | 530 | 900 | 47.00 | 71.50 |
| 1cX 630 | 40 | 555 | 485 | 809 | 680 | 590 | 1020 | 59.22 | 90.09 |
| 1cX800 | 47 | 625 | 530 | 935 | 740 | 630 | 1140 | 75.20 | 114.40 |
| 1cX1000 | 51 | 690 | 570 | 1065 | 780 | 660 | 1250 | 94.00 | 143.00 |
|
1.1 KV SINGLE CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I) |
|||||||||
| Cross-sectional area (Sq MM) |
ARMOURED CABLE |
||||||||
|
Overall Diameter (mm) |
Normal Current Rating in Amps |
Short Circuit Current Rating for 1Sec.duration in K. Amps |
|||||||
|
Aluminums Conductor |
Copper Conductor |
Aluminums |
Copper |
||||||
| Ground | Duct | Air | Ground | Duct | Air | ||||
| 1cX4 | 10 | — | — | — | 48 | 47 | 45 | 0.376 | 0.572 |
| 1cX 6 | 11 | 45 | 45 | 40 | 60 | 59 | 57 | 0.56 | 0.858 |
| 1cX10 | 12 | 59 | 62 | 53 | 80 | 78 | 77 | 0.94 | 1.43 |
| 1cX16 | 13 | 76 | 80 | 73 | 104 | 102 | 106 | 1.50 | 2.29 |
| 1cX25 | 14 | 99 | 90 | 115 | 130 | 115 | 145 | 2.35 | 3.58 |
| 1cX 35 | 15 | 117 | 110 | 140 | 155 | 140 | 175 | 3.29 | 5.01 |
| 1cX50 | 17 | 138 | 125 | 170 | 185 | 165 | 215 | 4.70 | 7.15 |
| 1cX70 | 19 | 168 | 155 | 210 | 225 | 200 | 270 | 6.58 | 10.01 |
| 1cX 95 | 22 | 204 | 185 | 255 | 265 | 235 | 330 | 8.93 | 13.59 |
| 1cX120 | 24 | 230 | 210 | 300 | 300 | 265 | 380 | 11.28 | 17.16 |
| 1cX150 | 25 | 265 | 230 | 342 | 335 | 300 | 430 | 14.10 | 21.45 |
| 1cX185 | 28 | 295 | 260 | 385 | 380 | 335 | 495 | 17.39 | 26.46 |
| 1cX240 | 30 | 340 | 300 | 450 | 435 | 385 | 590 | 22.56 | 34.32 |
| 1cX300 | 33 | 390 | 335 | 519 | 490 | 430 | 670 | 28.20 | 42.90 |
| 1cX400 | 38 | 450 | 380 | 605 | 550 | 480 | 780 | 37.60 | 57.20 |
| 1cX 500 | 41 | 500 | 430 | 700 | 610 | 530 | 900 | 47.00 | 71.50 |
| 1cX 630 | 46 | 555 | 485 | 809 | 680 | 590 | 1020 | 59.22 | 90.09 |
| 1cX800 | 51 | 625 | 530 | 935 | 740 | 630 | 1140 | 75.20 | 114.40 |
| 1cX1000 | 56 | 690 | 570 | 1065 | 780 | 660 | 1250 | 94.00 | 143.00 |
|
1.1 KV Two CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I) |
|||||||||
| Cross-sectional area (Sq MM) |
UN-ARMOURED CABLE |
||||||||
|
Overall Diameter (mm) |
Normal Current Rating in Amps |
Short Circuit Current Rating for 1Sec.duration in K. Amps |
|||||||
|
Aluminums Conductor |
Copper Conductor |
Aluminums |
Copper |
||||||
| Ground | Duct | Air | Ground | Duct | Air | ||||
| 2cX4 | 13 | 34 | 28 | 30 | 44 | 37 | 39 | 0.376 | 0.572 |
| 2cX 6 | 14 | 43 | 37 | 40 | 55 | 47 | 50 | 0.564 | 0.858 |
| 2cX10 | 17 | 57 | 48 | 53 | 74 | 61 | 67 | 0.940 | 1.430 |
| 2cX16 | 17 | 78 | 61 | 70 | 94 | 78 | 85 | 1.50 | 2.29 |
| 2cX25 | 19 | 95 | 80 | 99 | 120 | 100 | 125 | 2.35 | 3.58 |
| 2cX35 | 20 | 116 | 94 | 117 | 145 | 120 | 155 | 3.29 | 5.01 |
| 2cX50 | 22 | 140 | 110 | 140 | 170 | 145 | 190 | 4.70 | 7.15 |
| 2cX70 | 25 | 170 | 140 | 176 | 210 | 175 | 235 | 6.58 | 10.01 |
| 2cX95 | 28 | 200 | 165 | 221 | 250 | 210 | 290 | 8.93 | 13.59 |
| 2cX120 | 31 | 225 | 185 | 258 | 285 | 240 | 330 | 11.28 | 17.16 |
| 2cX150 | 33 | 255 | 210 | 294 | 315 | 270 | 375 | 14.10 | 21.45 |
| 2cX185 | 37 | 285 | 235 | 339 | 355 | 300 | 435 | 17.39 | 26.46 |
| 2cX240 | 41 | 325 | 270 | 402 | 410 | 350 | 510 | 22.56 | 34.32 |
| 2cX300 | 44 | 370 | 305 | 461 | 460 | 390 | 590 | 28.20 | 42.90 |
| 2cX400 | 48 | 435 | 350 | 542 | 520 | 440 | 670 | 37.60 | 57.20 |
| 2cX500 | 54 | 481 | 405 | 624 | 580 | 480 | 750 | 47.00 | 71.50 |
| 2cX630 | 62 | 537 | 470 | 723 | 680 | 575 | 875 | 59.22 | 90.09 |
|
1.1 KV Two CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I) |
|||||||||
| Cross-sectional area (Sq MM) |
ARMOURED CABLE |
||||||||
|
Overall Diameter (mm) |
Normal Current Rating in Amps |
Short Circuit Current Rating for 1Sec.duration in K. Amps |
|||||||
|
Aluminums Conductor |
Copper Conductor |
Aluminums |
Copper |
||||||
| Ground | Duct | Air | Ground | Duct | Air | ||||
| 2cX4 | 15 | 34 | 28 | 30 | 44 | 37 | 39 | 0.376 | 0.572 |
| 2cX 6 | 16 | 43 | 37 | 40 | 55 | 47 | 50 | 0.564 | 0.858 |
| 2cX10 | 18 | 57 | 48 | 53 | 74 | 61 | 67 | 0.940 | 1.430 |
| 2cX16 | 19 | 78 | 61 | 70 | 94 | 78 | 85 | 1.50 | 2.29 |
| 2cX25 | 21 | 95 | 80 | 99 | 120 | 100 | 125 | 2.35 | 3.58 |
| 2cX35 | 23 | 116 | 94 | 117 | 145 | 120 | 155 | 3.29 | 5.01 |
| 2cX50 | 25 | 140 | 110 | 140 | 170 | 145 | 190 | 4.70 | 7.15 |
| 2cX70 | 28 | 170 | 140 | 176 | 210 | 175 | 235 | 6.58 | 10.1 |
| 2cX95 | 31 | 200 | 165 | 221 | 250 | 210 | 290 | 8.93 | 13.59 |
| 2cX120 | 34 | 225 | 185 | 258 | 285 | 240 | 330 | 11.28 | 17.16 |
| 2cX150 | 37 | 255 | 210 | 294 | 315 | 270 | 375 | 14.10 | 21.45 |
| 2cX185 | 40 | 285 | 235 | 339 | 355 | 300 | 435 | 17.39 | 26.46 |
| 2cX240 | 45 | 325 | 270 | 402 | 410 | 350 | 510 | 22.56 | 34.32 |
| 2cX300 | 49 | 370 | 305 | 461 | 460 | 390 | 590 | 28.20 | 42.90 |
| 2cX400 | 52 | 0.33 | 435 | 350 | 542 | 520 | 440 | 670 | 37.60 |
| 2cX500 | 60 | 0.34 | 481 | 405 | 624 | 580 | 480 | 750 | 47.00 |
| 2cX630 | 66 | 0.36 | 537 | 470 | 723 | 680 | 575 | 875 | 59.22 |
|
1.1 KV Three CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I) |
|||||||||
| Cross-sectional area (Sq MM) |
UN-ARMOURED CABLE |
||||||||
|
Overall Diameter (mm) |
Normal Current Rating in Amps |
Short Circuit Current Rating for 1Sec.duration in K. Amps |
|||||||
|
Aluminums Conductor |
Copper Conductor |
Aluminums |
Copper |
||||||
| Ground | Duct | Air | Ground | Duct | Air | ||||
| 3cX 4 | 14 | 34 | 28 | 30 | 44 | 37 | 39 | 0.376 | 0.572 |
| 3cX 6 | 16 | 43 | 37 | 40 | 55 | 47 | 50 | 0.564 | 0.858 |
| 3cX 10 | 18 | 57 | 48 | 53 | 74 | 61 | 67 | 0.940 | 1.430 |
| 3cX 16 | 18 | 78 | 61 | 70 | 94 | 78 | 85 | 1.50 | 2.29 |
| 3cX 25 | 21 | 95 | 80 | 99 | 120 | 100 | 125 | 2.35 | 3.58 |
| 3cX 35 | 22 | 116 | 94 | 117 | 145 | 120 | 155 | 3.29 | 5.01 |
| 3cX 50 | 25 | 140 | 110 | 140 | 170 | 145 | 190 | 4.70 | 7.15 |
| 3cX 70 | 30 | 170 | 140 | 176 | 210 | 175 | 235 | 6.58 | 10.01 |
| 3cX 95 | 32 | 200 | 165 | 221 | 250 | 210 | 290 | 8.93 | 13.59 |
| 3cX 120 | 35 | 225 | 185 | 258 | 285 | 240 | 330 | 11.28 | 17.16 |
| 3cX 150 | 39 | 255 | 210 | 294 | 315 | 270 | 375 | 14.10 | 21.45 |
| 3cX 185 | 43 | 285 | 235 | 339 | 355 | 300 | 435 | 17.39 | 26.46 |
| 3cX 240 | 49 | 325 | 270 | 402 | 410 | 350 | 510 | 22.56 | 34.32 |
| 3cX 300 | 53 | 370 | 305 | 461 | 460 | 390 | 590 | 28.20 | 42.90 |
| 3cX 400 | 59 | 435 | 350 | 542 | 520 | 440 | 670 | 37.60 | 57.20 |
| 3cX 500 | 66 | 481 | 405 | 624 | 580 | 480 | 750 | 47.00 | 71.50 |
| 3cX 630 | 73 | 537 | 470 | 723 | 680 | 575 | 875 | 59.22 | 90.09 |
|
1.1 KV Three CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I) |
|||||||||
| Cross-sectional area (Sq MM) |
ARMOURED CABLE |
||||||||
|
Overall Diameter (mm) |
Normal Current Rating in Amps |
Short Circuit Current Rating for 1Sec.duration in K. Amps |
|||||||
|
Aluminums Conductor |
Copper Conductor |
Aluminums |
Copper |
||||||
| Ground | Duct | Air | Ground | Duct | Air | ||||
| 3cX 4 | 18 | 34 | 28 | 30 | 44 | 37 | 39 | 0.376 | 0.572 |
| 3cX 6 | 19 | 43 | 37 | 40 | 55 | 47 | 50 | 0.564 | 0.858 |
| 3cX 10 | 20 | 57 | 48 | 53 | 74 | 61 | 67 | 0.940 | 1.430 |
| 3cX 16 | 20 | 78 | 61 | 70 | 94 | 78 | 85 | 1.50 | 2.29 |
| 3cX 25 | 23 | 95 | 80 | 99 | 120 | 100 | 125 | 2.35 | 3.58 |
| 3cX 35 | 25 | 116 | 94 | 117 | 145 | 120 | 155 | 3.29 | 5.01 |
| 3cX 50 | 29 | 140 | 110 | 140 | 170 | 145 | 190 | 4.70 | 7.15 |
| 3cX 70 | 32 | 170 | 140 | 176 | 210 | 175 | 235 | 6.58 | 10.01 |
| 3cX 95 | 35 | 200 | 165 | 221 | 250 | 210 | 290 | 8.93 | 13.59 |
| 3cX 120 | 39 | 225 | 185 | 258 | 285 | 240 | 330 | 11.28 | 17.16 |
| 3cX 150 | 43 | 255 | 210 | 294 | 315 | 270 | 375 | 14.10 | 21.45 |
| 3cX 185 | 48 | 285 | 235 | 339 | 355 | 300 | 435 | 17.39 | 26.46 |
| 3cX 240 | 53 | 325 | 270 | 402 | 410 | 350 | 510 | 22.56 | 34.32 |
| 3cX 300 | 58 | 370 | 305 | 460 | 460 | 390 | 590 | 28.20 | 42.90 |
| 3cX 400 | 65 | 435 | 350 | 542 | 520 | 440 | 670 | 37.60 | 57.20 |
| 3cX 500 | 72 | 481 | 405 | 624 | 580 | 480 | 750 | 47.00 | 71.50 |
| 3cX 630 | 81 | 537 | 470 | 723 | 680 | 575 | 875 | 59.22 | 90.09 |
|
1.1 KV Three CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I) |
|||||||||
| Cross-sectional area (Sq MM) |
UN-ARMOURED CABLE |
||||||||
|
Overall Diameter (mm) |
Normal Current Rating in Amps |
Short Circuit Current Rating for 1Sec.duration in K. Amps |
|||||||
|
Aluminums Conductor |
Copper Conductor |
Aluminums |
Copper |
||||||
| Ground | Duct | Air | Ground | Duct | Air | ||||
| 3.5X25 | 22 | 95 | 80 | 99 | 120 | 100 | 125 | 2.35 | 3.58 |
| 3.5X35 | 24 | 116 | 94 | 117 | 145 | 120 | 155 | 3.29 | 5.01 |
| 3.5X50 | 27 | 140 | 110 | 140 | 170 | 145 | 190 | 4.70 | 7.15 |
| 3.5X70 | 31 | 170 | 140 | 176 | 210 | 175 | 235 | 6.58 | 10.01 |
| 3.5X95 | 34 | 200 | 165 | 221 | 250 | 210 | 290 | 8.93 | 13.59 |
| 3.5X120 | 38 | 225 | 185 | 258 | 285 | 240 | 330 | 11.28 | 17.16 |
| 3.5X150 | 43 | 255 | 210 | 294 | 315 | 270 | 375 | 14.10 | 21.45 |
| 3.5X185 | 46 | 285 | 235 | 339 | 355 | 300 | 435 | 17.39 | 26.46 |
| 3.5X240 | 52 | 325 | 270 | 402 | 410 | 350 | 510 | 22.56 | 34.32 |
| 3.5X300 | 57 | 370 | 305 | 461 | 460 | 390 | 590 | 28.20 | 42.90 |
| 3.5X400 | 65 | 435 | 350 | 542 | 520 | 440 | 670 | 37.60 | 57.20 |
| 3.5X500 | 73 | 481 | 405 | 624 | 580 | 480 | 750 | 47.00 | 71.50 |
| 3.5X630 | 82 | 537 | 470 | 723 | 680 | 575 | 875 | 59.22 | 90.09 |
|
1.1 KV Three & Half CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I) |
|||||||||
| Cross-sectional area (Sq MM) |
ARMOURED CABLE |
||||||||
|
Overall Diameter (mm) |
Normal Current Rating in Amps |
Short Circuit Current Rating for 1Sec.duration in K. Amps |
|||||||
|
Aluminums Conductor |
Copper Conductor |
Aluminums |
Copper |
||||||
| Ground | Duct | Air | Ground | Duct | Air | ||||
| 3.5X25 | 25 | 95 | 80 | 99 | 120 | 100 | 125 | 2.35 | 3.58 |
| 3.5X35 | 27 | 116 | 94 | 117 | 145 | 120 | 155 | 3.29 | 5.01 |
| 3.5X50 | 30 | 140 | 110 | 140 | 170 | 145 | 190 | 4.70 | 7.15 |
| 3.5X70 | 35 | 170 | 140 | 176 | 210 | 175 | 235 | 6.58 | 10.01 |
| 3.5X95 | 38 | 200 | 165 | 221 | 250 | 210 | 290 | 8.93 | 13.59 |
| 3.5X120 | 42 | 225 | 185 | 258 | 285 | 240 | 330 | 11.28 | 17.16 |
| 3.5X150 | 46 | 255 | 210 | 294 | 315 | 270 | 375 | 14.10 | 21.45 |
| 3.5X185 | 51 | 285 | 235 | 339 | 355 | 300 | 435 | 17.39 | 26.46 |
| 3.5X240 | 56 | 325 | 270 | 402 | 410 | 350 | 510 | 22.56 | 34.32 |
| 3.5X300 | 60 | 370 | 305 | 461 | 460 | 390 | 590 | 28.20 | 42.90 |
| 3.5X400 | 71 | 435 | 350 | 542 | 520 | 440 | 670 | 37.60 | 57.20 |
| 3.5X500 | 79 | 481 | 405 | 624 | 580 | 480 | 750 | 47.00 | 71.50 |
| 3.5X630 | 88 | 537 | 470 | 723 | 680 | 575 | 875 | 59.22 | 90.09 |
|
1.1 KV Four CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I) |
|||||||||
| Cross-sectional area (Sq MM) |
UN-ARMOURED CABLE |
||||||||
|
Overall Diameter (mm) |
Normal Current Rating in Amps |
Short Circuit Current Rating for 1Sec.duration in K. Amps |
|||||||
|
Aluminums Conductor |
Copper Conductor |
Aluminums |
Copper |
||||||
| Ground | Duct | Air | Ground | Duct | Air | ||||
| 4cX4 | 17 | 34 | 28 | 30 | 44 | 37 | 39 | 0.376 | 0.572 |
| 4cX 6 | 18 | 43 | 37 | 40 | 55 | 47 | 50 | 0.564 | 0.858 |
| 4cX 10 | 20 | 57 | 48 | 53 | 74 | 61 | 67 | 0.940 | 1.430 |
| 4cX16 | 20 | 78 | 61 | 70 | 94 | 78 | 85 | 1.50 | 2.29 |
| 4cX 25 | 24 | 95 | 80 | 99 | 120 | 100 | 125 | 2.35 | 3.58 |
| 4cX35 | 26 | 116 | 94 | 117 | 145 | 120 | 155 | 3.29 | 5.01 |
| 4cX 50 | 29 | 140 | 110 | 140 | 170 | 145 | 190 | 4.70 | 7.15 |
| 4cX70 | 34 | 170 | 140 | 176 | 210 | 175 | 235 | 6.58 | 10.01 |
| 4cX 95 | 37 | 200 | 165 | 221 | 250 | 210 | 290 | 8.93 | 13.59 |
| 4cX 120 | 41 | 225 | 185 | 258 | 285 | 240 | 330 | 11.28 | 17.16 |
| 4cX 150 | 45 | 255 | 210 | 294 | 315 | 270 | 375 | 14.10 | 21.45 |
| 4cX 185 | 50 | 285 | 235 | 339 | 355 | 300 | 435 | 17.39 | 26.46 |
| 4cX 240 | 56 | 325 | 270 | 402 | 410 | 350 | 510 | 22.56 | 34.32 |
| 4cX 300 | 63 | 370 | 305 | 461 | 460 | 390 | 590 | 28.20 | 42.90 |
| 4cX 400 | 70 | 435 | 350 | 542 | 520 | 440 | 670 | 37.60 | 57.20 |
| 4cX 500 | 79 | 481 | 405 | 624 | 580 | 480 | 750 | 47.00 | 71.50 |
| 4cX 630 | 88 | 537 | 470 | 723 | 680 | 575 | 875 | 59.22 | 90.09 |
|
1.1 KV Four CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I) |
|||||||||
| Cross-sectional area (Sq MM) |
ARMOURED CABLE |
||||||||
|
Overall Diameter (mm) |
Normal Current Rating in Amps |
Short Circuit Current Rating for 1Sec.duration in K. Amps |
|||||||
|
Aluminums Conductor |
Copper Conductor |
Aluminums |
Copper |
||||||
| Ground | Duct | Air | Ground | Duct | Air | ||||
| 4cX4 | 18 | 34 | 28 | 30 | 44 | 37 | 39 | 0.376 | 0.572 |
| 4cX 6 | 19 | 43 | 37 | 40 | 55 | 47 | 50 | 0.564 | 0.858 |
| 4cX 10 | 21 | 57 | 48 | 53 | 74 | 61 | 67 | 0.940 | 1.430 |
| 4cX16 | 22 | 78 | 61 | 70 | 94 | 78 | 85 | 1.50 | 2.29 |
| 4cX 25 | 26 | 95 | 80 | 99 | 120 | 100 | 125 | 2.35 | 3.58 |
| 4cX35 | 28 | 116 | 94 | 117 | 145 | 120 | 155 | 3.29 | 5.01 |
| 4cX 50 | 32 | 140 | 110 | 140 | 170 | 145 | 190 | 4.70 | 7.15 |
| 4cX70 | 37 | 170 | 140 | 176 | 210 | 175 | 235 | 6.58 | 10.01 |
| 4cX 95 | 40 | 200 | 165 | 221 | 250 | 210 | 290 | 8.93 | 13.59 |
| 4cX 120 | 44 | 225 | 185 | 258 | 285 | 240 | 330 | 11.28 | 17.16 |
| 4cX 150 | 49 | 255 | 210 | 294 | 315 | 270 | 375 | 14.10 | 21.45 |
| 4cX 185 | 54 | 285 | 235 | 339 | 355 | 300 | 435 | 17.39 | 26.46 |
| 4cX 240 | 65 | 325 | 270 | 402 | 410 | 350 | 510 | 22.56 | 34.32 |
| 4cX 300 | 68 | 370 | 305 | 460 | 460 | 390 | 590 | 28.20 | 42.90 |
| 4cX 400 | 76 | 435 | 350 | 542 | 520 | 440 | 670 | 37.60 | 57.20 |
| 4cX 500 | 86 | 481 | 405 | 624 | 580 | 480 | 750 | 47.00 | 71.50 |
| 4cX 630 | 94 | 537 | 470 | 723 | 680 | 575 | 875 | 59.22 | 90.09 |




Dear Sir / Madam,
Please send me the cable size selection chart for Low voltage & Medium voltage. I will be very great full to you.
Regards
Syed
I have already given in XLPE, PVC Cable section
Hai good morning, You have done a good job. it’s very useful to me. Thank you
Ur information is very useful thank you
Dear sir, I Prakash Parmar from Suyog Electricals Ltd, 1 query about XLPE cable current rating base on on which IS standard & its calculation please provide information
Dear sir
please send cable chart – 596.8kw mens how much sq mm required AL /CU
regards
Harish
9850985429
plz send the details for cable sizing for primary and secondary side of 250 KVA transformer
Jignesh Ji can you please tell me how to calculate the power loss in single core cable.
regards
sandeep saini
sir i need list of motor hp fuse amps kw cable size gland size please i Will request you send me my mail sir.
total ratings previous publishing very nice am seened they
Thank you for this cable selection chart. Thank u verymuch. Do u have any information about conductor,s DC current carrying capacity .Please help me sir, Thank u.
dear sir,
ratinng cable size of 300kva to 450kva trasformer.
dear sir,
thanks.can you please give details of selecting UPS and generators rating.
Dear Sir
Will you please furnish me short time ratings of HT XLPE insulated cables e. g. 10% for XXX Hrs., 20% for XXX Hrs. and so on ?
Can a 10 guage XPLE insulated copper wire used as leads for oil immersed CTs withstand around 90 deg C continously in transformer oil? What is the compatability of XPLE wire with transformer oil? What is the specific density of XLPE insulation?
Can we get the standard from which the XLPE current values are derived / referred.
can you tell me the voltage drop calcultaion of 11KV XLPE cable around 600m long
Use Excel Base Program to Calculate LT-MV-HT Cable from “Electrical Tool” Page of This Blog
(1) Cable Designing Program:
DOWNLOAD:
Calculate Voltage drop of Cable.
Calculate Size of Cable.
Calculate Current Capacity of Cable.
Mr Jignesh,
what is the difference between MCCB,ACB and VCB..
I heard that above 630A we should use ACB ,but MCCB’s are available till 1600A.
So can you tell me from which rating we have to go for ACB and VCB
Is there any difference in the operation of MCCB and ACB.
Thanking you,
Paulson
i am engaged in arecanut leaf plate manufacturing activity which need heaters with die of 8000 watts.what specification of power cable can i put.
Dear Sir,
i what to learn the HT cable sizing. how to calculate it . Can you help me. If you have any excel Sheet kindly shear with me.
Dear Sir,
Really very happy…Your Calculation your explanation are very nice and useful for us.
please send details of
1-cable size with current rating data
2- cable gland size & type
3- rating of contractor & over load relay
This Topic is already covered.Read Electrical Notes Carefully
Dear Jignesh, I am nirav shah from hyderabad. i would like to know what is the difference between current carrying capacity for xlpe insulated single core copper flexible cables for AC and Dc applications. Benchmark being single core 240sqmm which can carry upto 550amps in AC application.
Dear Sir,
Details furnished by you are excellent.Sir, i need to buy the unlock version .Did you published any books on cable sizing,busbar calculation, breaker designing etc?My maid id is udai_kiran1983@yahoo.com
please can i get a copy of your book in ghana?
sir, i read to this cable size and current rating chart it is very use full for us so i request u please send this chart in my Email
RAMKEWAL
i will be hope full with this chart
Thank you.
RAMKEWAL
Dear Sir / Madam,
Please send me the cable size selection chart for Low voltage & Medium voltage(single phase and three phase indicating amps each size can carry. I will be very great full to you
can you please provid me for the current rating for 1C X 185 SQ MM copper cables
It is already Given on the following Post
http://electricalnotes.wordpress.com/2011/04/24/xlpe-cable-current-rating/
sorry i want the current carrying capacity in DC power( 750 V, and 440 V )
Thank you.
hi sir will you please tell me the calculation formula fo these & also i want to know the cable size for 11kv tranfomer to the panel
Dear
Plz confrim the Load and distance of TR. To panel
Regards Manoj Patil On Sep 20, 2015 5:21 PM, “Electrical Notes & Articles” wrote:
> Manojkumar commented: “hi sir will you please tell me the calculation > formula fo these & also i want to know the cable size for 11kv tranfomer to > the panel”
11kv/433v TFP-1000 kva/500kva/750kva the fl currents on LT side are 1333.3/1000/666.6 amps. what is size of 4 core xlpe alluminium is used pl tell me.
Download Excel base Sheet to decide Cable Size from “EXCEL TOOL” page.
To decide Cable Size We need two important Data
(1) Load
(2)Distance.
this chart about cables is nice but give us some information about OH cables, and underground cables .
WHAT IS THE BIS – IS CODE FOR 11 KV CROSS ARMOURED CABLE
Very useful….
Dear Jignesh,
Your cable selection table is very helpful. But i’ve a question to clarify? how do we determine the cable current capacity of cables running in parallel? for example if my breaker is rated at 1000A, what size of cable conductor should be terminating at the terminals per phase, can i terminate 2 x 1c x 400 per phase or how do we decide the conductor sizing? as i understand there is a derating factor of cables when connected in parallel? may be you can ellaborate further and may be send me details on the cable sizing formulation and other useful data on my email : manjarwalla@gmail.com
Use Equation
% Voltage Drop:=(1.732 X (Full Load Current)X(RCosØ+j SinØ)XLengthX100) / Line Voltage X No of Run X 1000.
Here No of Run cable is Either 1,2 or more in parallel.
You can also use “Cable Design” sheet of the Excel Tool Page of this Blog
Dear Jignesh,
Thank you for your prompt reply. I’ve also gone through your cable design excel sheet,wonderful program. On the cable design program how do you determine the starting and running cos and sin thetha? do you have any thumb rule for calculating the cable runs in a faster way? for example if my full load current is 1000A as incomer or any feeder load connected to my panel. As from the program i’ve to input the the respective KW to attain nearest full load current before i can get the runs of cables?
Dear Sir,
Plz.tel me this XLPE cables can we use 100% loading? for How much length cables are de rated?
Thanks.
this Rating is as per Standard Cable Catalog and IS. Cable Rating never indicate derating factor. Because Derating Factor depends upon Your Application.
It is depend upon Type of Laying Cable –
=In Air,Land, at 0.500mt depth at 1 meter depth,
=Air-Land Temperature,
=in bundle,=In separate,Distance between two Cable, etc.
If Cable Rating is 100 Amp It may be 80 Amp or 90 Amp or 100 Amp depend upon Laying of cable.
Pl. send me LT cable current carrying capacity charts
Already available on this Blog . Please Refer Post of “PVC Flexible Wire Rating”
I have already Put Cable/Wire Rating Starting from 430V to 66KV (Earthed/Unearthed Cable)
Varry importent for me this. Site
Good work, its very useful
sir,if i have 7.5kw unit then how can i select cable for that unit with out using chart.give me that formula for me.
Use Cable Size Program of this Blog. (Formula is given in the Program)
well done sir you have a great job and sacrifices for Electrical Engineering.
Hi,
I really appreciate your effort to share consolidated information..
dear
sir/madem
pleas send me cebel formula for given voltag and
also send me cabel and amp tebal
Download Cable selection Program from this Blog..here You can find Formulas and Table also…
i want to this information sir
It is very useful informations… Gr8
what is the thumb rule for above calcualtions..? please share the formula for approximate current ratings in 1.1 kv XLPE cables .
Mr. Jignesh, can you please tell me what size of cable is required for solar installation. My panel rating is Isc=8.5 A, Voc=36.5 V. I’m using two series panels in 3 arrays, basically an 2×3 system. Thanks. Length one way will be 30 feet from panels to inverter.
Electrical Rasio used
400 volt,528 amp and insulation xlpe ,cable size required
hiii sir, thanx for this information but sir pls tell me the formula or any thumb rule for calculating of cable/wire size as per given load…..
Thank you for this cable selection chart. Do u have any information about conductor,s DC current carrying capacity .Please mail me sir, Thank u.
sir
can u tell me the formula how to calculate the cable sizes corresponding amps..
why use mastic tape for 11 kv cable joint,please tell me sir.
Dear sir,
what is the function of cable fillers ? please reply.
sir ,
difference between round shape cable and delta shape cable please me understand
whats type of 11kv spout ?
electrical infrastructure construction Q&A for exp houseing scheme what are requrment of houesing scheme of all utlates and what are gape electrical serviese between water ,sewg,gas and other serviese in under ground
How to measure currenraings of armed & unarmed cables
Differance between kw,kvar and kva
I want to know that whats the current carrying capacity for 4 runs of 3.5 core 400 Sq.mm Al. armoured XLPE cable in ground . How it can be calculate. ( please send a copy of tables if any )
which means if 3.5 core 400sq.mm cable carries 370 amps in ground and when it is 2 runs it will not be double of 370. it will less than double. how it will calculate ???
Please give me a reply
with regards
By Anil
You are mixing two different topic ..
(1) If we laid cable in ground,air or trench it’s current capacity will be decrease due to surrounding temp.
(2) If we laid cable in group / single it’s current capacity will be decrease those effect called “derating factor of cable..
You find in Electrical Tool page.
If we run two cable for same phase obviously it’s capacity would be double…
How to measure capacitance&inductance in A.P.Transco meters and send formula of KW&KVAR&KVA.
KIRAN PATEL
dear sir what is service factor in motor and which kind machine in use same motor
Hai …
Dear Sir,
My doubt might sound silly to you, but I just wanted to clarify it. From the given cable ampacity ratings in the tables above, how can we calculate the maximum power rating for the respective multi-core cables.
Thank you.
Given Rating are single and Multi core cable..
For example: for a 4 core 120 sqmm Aluminium conductor cable, what is the maximum power capacity? Should we multiply the given ampacity with single phase voltage or 3 phase voltage to find out maximum load it can handle?
Use “Cable Size Calculation” sheet of this Blog
Dear Jignesh,
pl suggest me regarding cable rating across laying ground 700 running feet for 750A load bearing at resisdence building there jurk load AC. Pl give cable size.
Regards,
Suresh Chaudhary
there is no any power rating of cable.only current rating of cable are mentioned.power rating is concerned to the equipment.
Dear Jignesh,
Sir what’s the formula to select the cables sizes for the particular current ratings?
Refer “Cable Size” Excel base program from “Electrical Tools” Page
You did good , its very useful
dear jignesh how to calculate the busbar size in 630amps breaker 3ph ?
Dear Sir
Thanks for this information. this is very usefull for us.
Dear Sir,
Can you explain that the current rating you have mentioned in Ground ,Air, or duct is quite opposite to what manufacture state in their product catalogue.
regards
how many runs of 3.5C 240 sq.mm al. conductor xlpe pvc insulted cables to be laid to supply to a circuit which is maximum current draw is 800 A.
Distance !!!! Use Excel Cable Size Calculation sheet of this Blog..
Yes very use full.thank you.
Sir,
please let me know the current carrying capacity of 3C*2.5 sqmm copper cable in air.
sir,
if i want to select power cable for 2o hp motor. and i am going to use 3 core alluminium cable.
then what will be the cable size?
sir
3.5core 50 sqmm ki cabel par fes kitana amp legislative
sir,
if i want to select 50sq cable for 11kv. and i am going to use 3 core cable.
then what will be the cable size?
your table is very useful, thank you and I need the cable size of 22 kw, 3ph, 380volt for my deep well pump motor at a deep distance of 300 metrrs
Thank you & best regards,
Fetsum
thanks for this great cable chart…
Hi
Can I know how many runs of single core 630 mm are required for a 1000 KVA transformer ?
Dear Sir;
I would like to say thank you so much for the access you made open to get the size of power cables.
Teshome, from Ethiopia
Dear sir/ Madam
Please send me the cable size selection chart & amps details
Dear Sir,
Kindly give me chart for motor hp kw flc relay contactor mccb current carring capacity for all and cu and gland size.
hi…. i have find question about how to find current of 132kv,1200mm^2 cross sec area,in flat formation with 400 mm disc presnt btween them,,is there any formuala ,so guide me plzzzzz,thnkxxxx
Hi — Here 40 kw load 3 ph 415 v and length is 1 km so kindly suggest me which size of aluminum
cable to be laid in ground
Hello, what 33 KV cable size should I select for a 2000 KW Load on LT side. Transformer is 2.5 MVA, 33/0.433 KV.
बहुत अछछी जानकारी मिली।
You are such a wonderful Engineer, for the great opportunity you have given to people
UR NOTES IS SUCH WONDERFULL THANK U SO MUCH…
Dear Sir,
will you please suggest me from which website i can download Excel Base Program to Calculate LT-MV-HT Cable from Electrical tools.
Sir Thanks For your Valuble Information,I want know the Formula for To Measure Current For Any cable Ex:1x16sq.mm,3x4sqmm,3×16 sqmm
Sir Thanks For your Valuble Information,I want know the Formula for To Measure Current For Any cable Ex:1x16sq.mm,3x4sqmm,3×16 sqmm
CAN YOU TELL ME WHEN WE TAKE A 51MM COOPER CABLE THEN THIS COOPER CABLE HOW MUCH TAKE A LOAD IN HP
please can you tell me if total load is 140 Amp and length is 250 Meter. how much XLPE cable size and how much voltage drop. how i can calculate.
please advice which minimum width of 3 core xlpe cable should used for 7 KM long transmission with connected load of 3000
Sir
How much load can be layed on 1 kv line. Please give kv and load relation.
Sir
what’s the advantage of using 4 core cable over 3.5 core cable ? And then, what chang
Powar pf 1
sir,
Detail of Transformer primary & secondary testing please said me
Hello Sir.
Can a 4C 150mm armoured cable sustain 595A or a total power of 398Kva? If not, what cable size would be ideal? I seek for expert advice. Thanks.
Very good can I get this document through mail
It’s very useful for me
Thank you for this cable selection chart.
Thank u verymuch.
sir can you help me to size the cables for 5000A,3Phase,415Volts and the size of the cables for 2500KVA,415V, 3Phase diesel generator please help me for this
hello Sir,
I’m Ansh from lucknow , i wanted to know when cable insulation test carried out on one end R-N other end of cables R-N are shorted or not & why….???
Sir i
i want to know how to select copper and aluminium busar on current capacity
Hai
can you please tell me how to make the GRC-Group rating cables,
Regards
Shibu
Dear Sir,
Kindly share What is the standard parameters to be maintained daily in a transformer for both dry type and oil type & What is dielectric strength?
Respected Sir, Thanks For Supporting For Electrical Engineer
Sir i have Question to you sir
Can you give suitable CU. & Al. Cable Size of different rating starter like DOL & Stardelta Starter from above cable chart.
Dear sir,
i want to know will there be any change inside the conductor when the cable inssulation viltage is .4/.6kV…
Dear Sir,
Thanks for the useful chart… can u please guide me if these ratings are available in some standard or u have calculated the same using IEC 60287.
Regards
Dear sir,
Kindly give me how to test six nos of leads of motors to connect in delta.No identification.
Dear sir,
how to messring of current rate of contecter or cables
tell me the standard formula to calculate current carrying capacity of cable
Sir,
I require 4 core. rubberised cable for 200 HP 3phase motor 380/460 volts 226 amps if possible starter details.
Regards.
John
KINDLY SEND ME 33KV XLPE CABLE Current Rating Equivalent to Dog & panther conductor
Hello Sir,
Please tell me how to calculate the voltage drop of a 4C, 25 Sq. mm. Armoured Aluminium XLPE 1.1kv rating cable for 80M length having current rating of 200A.
If possible please involve the calculation also in reply.
kindly if I need underground cable I will consider current carrying from above table & proceed or should be multiply with derating factors also . ??? can you help me.
our site condition :-
ground temp. 35C >>>> factor = 0.89 as per IEC standard tables .
grouping factor >>>>>> 0.75 as per IEC standard tables .
depth laying factor >>>> 1.0 as per IEC standard tables .
soil thermal resistivity factor >>>> 1.17 as per IEC standard tables .
Super
Pls send me the LT &HT cable amps rating
Electrical notes are good. Pls send the transformer yard drawings
hI,
Main Cut-Out: 250 Amps
3 – Phases
Red : 163 Amps Incoming Main Load from Qatar Govt. is 105 KW
Yellow : 156 Amps Cable size 95 mm²
Blue : 105 Amps
Please let me know the Total Existing Load and alos tell me remedy to tripping off Problem.
Its very useful data. Highly appreciate you efforts. Thanks
Sir 3*400sqmm ug cable is laid in trench but cable termination is getting heating tell me reason
Dear sir u help me to amp to cable size formula & table send me my email id
Sir
thanks for info
can u provide any data regarding voltage drop by its length
Either the termination is lose or the connected load is more than your estimated load
SIr,
Can you help about how much the maximum outer diameter of can cable can be run in 50 mm 110 mm 160 mm 250 mm dia duct
Thank you
Pingback: Quora
Sir, why cant I find a Multi core cable 3.5 x 240 mm2 ?
For 140A load (Gas Analyser Heat Tracing System), 3cx150 sq mm 1.1kV Armoured Aluminium cable shall be sufficient?? Cable to be laid in Air.
can you tell me , the size of fuse wire which can be used in 25 kva 3 phase distribution transformer 11/.4kv
dear sir,
how to calculate the maximum output amps for 4c x 240sqmm size?
can anyone pls help me by sending the current carrying capacity of 3.5×35 Sq.mm aluminium cable ?
Sir, request you to please send excel based calculation sheet for selection
Dear Sir
I would like to know the amperes details of 1c,600 SQMM COPPER CABLE…
Dear sir ,
cable more type example armored , unarmored , flexible , how calculate running meter weight.
have any formula.
Dear sir ,
We have more type cable , armored , unarmored,flexible,instrumentation.
how calculate running mtr weight.
you have any formula.
Dear sir,
We have got new project. please let us know which cable use to 200KV UPS input
give details as below..
which size of cables are use in underground network ?
Total load is 200kw
as early as possible
thanks
Why do electricity board keep R N Y B phase wiring in street post and not in R Y B N in order?
Sir..!
Can you tell me the cable size in mm..
If i have to pass 500 amps of normal current and a surges of 100 amps could come to it..
Voltage is 440 V .
Cable length i need is 100 feet 1 side (single core) .
please provide the cable sizing for 1000kva DG set…we got information that -4 run of 240 sq mm cable ,single core for each phase is required.Is it like that?why?what is the calculation?
Sir,
How will calculate the cable size if load A and distance between load and source are known?
sir plz define. cable size increses current also increase in small dia cables but when dia increase but current not increase with dia . define this
Dear Sir kindly help in cable selection on AC side for a solar roof top system.
1).10kw pv system for a two floried villa
2).30 kw pv system for a 12 floried apartment.
Both the above cases ACDB is mounted on the roof.
Also please send me the cable selection chart…
Thanks!!
Sir,
We have wrongly purchased 3 core x 300 sq mm Aluminium armoured cable for main Incomer. What will be the solution to convert this cable in 3.5 Core x 300 Sq mm cable. Please help.
sir, for 690 volt vfd application motor is it suitable for 1.1kv xlp cable or shall we required any special cable
sir,
Please tell me if 2x3x400 sqmm XLPE cable maximum current carrying capacity will be same for 11kv,33kv and 66kv voltage level?
What is the maximum current carrying capacity?
sir,
Please tell me if 2x3x400 sqmm XLPE cable maximum current carrying capacity is same for 11KV,33KV,66KV?
what is the max current carrying capacity for 4km cable?
Thanks for providing such a list.
May I know the actual difference between LT & HT?
And what is the standard of choosing the LT power cable?
thanks for its
10sqmm×4core xlpe ug cable is ideal for a three floor building with total capacity of 15kilowatt?
This is very informative. Please let me also have table for xlpe cable ratings at 11kv.
In Your Electrical notes ( Rev 5,page 10), Thumb rule for cable current capacity says 4 times of cable size, 4 x 2.5 sq.mm = 9Amp. If I am not wrong then 2.5sq.mm can carry approx 22Amp
Can you please explain the basis of this thumb rule?
I need cable glend size chart as per cable size
Thank you
Dear sir.
I am working as Sr. section Engineer in Western Railway zone of Indian Railway.I have to scrutinise technically all material for traction distribution(Electrical branch) which is purchased by Railway.During Technically scrutiny I am facing a problem regarding type test certificate provided by firm for IS 7098 part II(2011)or part-I(1988).How can I considered category of cable i.e. 01, C1 or C2
please I want to know what cable diameter I can use for one motor 450 volt 3 ph 60 hz 237 A in one distance 295 meter , the cable passing from pipe with other cable together.
Thanks
How can I use cable size for 440 kW load? Please suggest Me?
how to select HT cables ?
2R*3.5C*240sqmm XLPE, Aluminium cable current carriynig capacity for 630Amp Incomer Feeder panel?
please i want to note chemical electrical earthing and were use & its advantages anther earthing system , how many cost of instalation of one chemical earthing
Can any one tell / explain the purpose of using 1.0 kV grade and 1.1 kV grade rating of PVC/XLPE insulated cable for low voltage since I am confused with it as some says 1.0 kV n some 1.1 kV. Logically how do we calculate? or it is differ from country to country?
Kindly send me these charts for cable selection , i will highly appreciate.
Kindly send me the charts for the cable selection, i will highly appreciate.
Hi Jignesh, I’d like to ask for your permission to reproduce two of your Tables in my blog as I’d need them for my personal quick reference. Am currently working on a cable installation for a raw water pump. Thanks in advance.
Hi Sir,
I want cable joint selection chart because I check its different catalogue number for every manufacturer, so is there any standard chart for it. Please if you have send me on my email id.
Thank you!
Very well detailed would like to have reference to a chart when paralleling cables
Good massage
What is Laminar insulation on Medium voltage cables, loss on Laminar insulation
Pingback: Diameter of 1100 Volts Grade XLPE, Insulated Cable (IS-7098- Part- I)
16sqmm 1100v aluminum armored xlpe cable mai.kitna hp ka motor lode de .
Sir,
For 100 amp load and 150 MTR distance . Single phase .. how many sq mm copper cable required..
Thank you so much sir your information is very useful..
Dear Sir .
Please send me the cable size selection chart for Low voltage & Medium voltage(pdf). I will be very great full to you.
Regards.
Eng. Abdolgabar Ahmed
We have 2200 kVA 11/0.415 kV transformer. What would be the proper cable size at 11 kV Side ? is it simply by current rating or we need to take 2 to 3 times..plz clarify..
hello,
am planning to set up a factory where i will need load for my machines upto 130 hp. can some one suggest what copper armour cable should be used??
Good evening sir,
Will you please send the 1.1kv 3core armoured xlpe cable current rating and. Is there any thumb rule(genral way) for calculating the current capacity (approximate) of the cable at site.(xlpe/pvc/pilca, 1c/2c/3c/3.5c/4c, copper/aluminum).
hello
can you guide Multi core cable Raw material calculation formula
Sir, please what is load capacity can 11kv aluminium xlpe power cable can carry
Sir I have confused all time in 0ne terms in 3.5*C in any cable amp rating are given per phase
hi
How to calculate derating factor. Give its formula
sir what does mean 1.1/kv Ac, 1core, 2run/phase-70 sq mm copper , xlpe, unarmoured cable.