XLPE Cable-Current Rating

XLPE Insulated Armored & Unarmored Cables:

1.1 KV SINGLE CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)

Cross-sectional area        (Sq MM)

UN-ARMOURED CABLE

Overall Diameter (mm)

Normal Current Rating in Amps

Short Circuit Current Rating for 1Sec.duration in K. Amps

Aluminums Conductor

Copper Conductor

Aluminums

Copper

Ground Duct Air Ground Duct Air
1cX4

8

 —  —  —  48  47  45  0.376  0.572
1cX 6  9  48  45  45  60  59  57  0.564  0.858
1cX10  10  62  62  61  80  78  77  0.940  1.430
1cX16  11  81  80  83  104  102  106  1.504  2.288
1cX25  12  99  90  115  130  115  145  2.350  3.575
1cX 35  13  117  110  135  155  140  175  3.290  5.005
1cX50  15  138  125  170  185  165  215  4.700  7.150
1cX70  16  168  155  210  225  200  270  6.580  10.01
1cX 95  18  204  185  255  265  235  330  8.930  13.59
1cX120  20  230  210  300  300  265  380  11.28  17.16
1cX150  22  265  230  342  335  300  430  14.10  21.45
1cX185  24  295  260  385  380  335  495  17.39  26.46
1cX240  27  340  300  450  435  385  590  22.56  34.32
1cX300  30  390  335  519  490  430  670  28.20  42.90
1cX400  33  450  380  605  550  480  780  37.60  57.20
1cX 500  36  500  430  700  610  530  900  47.00  71.50
1cX 630  40  555  485  809  680  590  1020  59.22  90.09
1cX800  47  625  530  935  740  630  1140  75.20  114.40
1cX1000  51  690  570  1065  780  660  1250  94.00  143.00
                   

1.1 KV SINGLE CORE AL/COPPER COND,XLPE INSULATED CABLES As per IS:7098 (Part-I)

Cross-sectional area        (Sq MM)

ARMOURED CABLE

Overall Diameter (mm)

Normal Current Rating in Amps

Short Circuit Current Rating for 1Sec.duration in K. Amps

Aluminums Conductor

Copper Conductor

Aluminums

Copper

Ground Duct Air Ground Duct Air
1cX4  10  —  —  —  48  47  45  0.376  0.572
1cX 6  11  45  45  40  60  59  57  0.56  0.858
1cX10  12  59  62  53  80  78  77  0.94  1.43
1cX16  13  76  80  73  104  102  106  1.50  2.29
1cX25  14  99  90  115  130  115  145  2.35  3.58
1cX 35  15  117  110  140  155  140  175  3.29  5.01
1cX50  17  138  125  170  185  165  215  4.70  7.15
1cX70  19  168  155  210  225  200  270  6.58  10.01
1cX 95  22  204  185  255  265  235  330  8.93  13.59
1cX120  24  230  210  300  300  265  380  11.28  17.16
1cX150  25  265  230  342  335  300  430  14.10  21.45
1cX185  28  295  260  385  380  335  495  17.39  26.46
1cX240  30  340  300  450  435  385  590  22.56  34.32
1cX300  33  390  335  519  490  430  670  28.20  42.90
1cX400  38  450  380  605  550  480  780  37.60  57.20
1cX 500  41  500  430  700  610  530  900  47.00  71.50
1cX 630  46  555  485  809  680  590  1020  59.22  90.09
1cX800  51  625  530  935  740  630  1140  75.20  114.40
1cX1000  56  690  570  1065  780  660  1250  94.00  143.00
                   

1.1 KV Two CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)

Cross-sectional area        (Sq MM)

UN-ARMOURED CABLE

Overall Diameter (mm)

Normal Current Rating in Amps

Short Circuit Current Rating for 1Sec.duration in K. Amps

Aluminums Conductor

Copper Conductor

Aluminums

Copper

Ground Duct Air Ground Duct Air
2cX4  13  34  28  30  44  37  39  0.376  0.572
 2cX 6  14  43  37  40  55  47  50  0.564  0.858
2cX10  17  57  48  53  74  61  67  0.940  1.430
2cX16  17  78  61  70  94  78  85  1.50  2.29
2cX25  19  95  80  99  120  100  125  2.35  3.58
2cX35  20  116  94  117  145  120  155  3.29  5.01
2cX50  22  140  110  140  170  145  190  4.70  7.15
2cX70  25  170  140  176  210  175  235  6.58  10.01
2cX95  28  200  165  221  250  210  290  8.93  13.59
2cX120  31  225  185  258  285  240  330  11.28  17.16
2cX150  33  255  210  294  315  270  375  14.10  21.45
2cX185  37  285  235  339  355  300  435  17.39  26.46
2cX240  41  325  270  402  410  350  510  22.56  34.32
2cX300  44  370  305  461  460  390  590  28.20  42.90
2cX400  48  435  350  542  520  440  670  37.60  57.20
2cX500  54  481  405  624  580  480  750  47.00  71.50
2cX630  62  537  470  723  680  575  875  59.22  90.09
                   
                   

1.1 KV Two CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)

Cross-sectional area        (Sq MM)

ARMOURED CABLE

Overall Diameter (mm)

Normal Current Rating in Amps

Short Circuit Current Rating for 1Sec.duration in K. Amps

Aluminums Conductor

Copper Conductor

Aluminums

Copper

Ground Duct Air Ground Duct Air
2cX4  15  34  28  30  44  37  39  0.376  0.572
 2cX 6  16  43  37  40  55  47  50  0.564  0.858
2cX10  18  57  48  53  74  61  67  0.940  1.430
2cX16  19  78  61  70  94  78  85  1.50  2.29
2cX25  21  95  80  99  120  100  125  2.35  3.58
2cX35  23  116  94  117  145  120  155  3.29  5.01
2cX50  25  140  110  140  170  145  190  4.70  7.15
2cX70  28  170  140  176  210  175  235  6.58  10.1
2cX95  31  200  165  221  250  210  290  8.93  13.59
2cX120  34  225  185  258  285  240  330  11.28  17.16
2cX150  37  255  210  294  315  270  375  14.10  21.45
2cX185  40  285  235  339  355  300  435  17.39  26.46
2cX240  45  325  270  402  410  350  510  22.56  34.32
2cX300  49  370  305  461  460  390  590  28.20  42.90
2cX400  52  0.33  435  350  542  520  440  670  37.60
2cX500  60  0.34  481  405  624  580  480  750  47.00
2cX630  66  0.36  537  470  723  680  575  875  59.22
                   

1.1 KV Three CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)

Cross-sectional area        (Sq MM)

UN-ARMOURED CABLE

Overall Diameter (mm)

Normal Current Rating in Amps

Short Circuit Current Rating for 1Sec.duration in K. Amps

Aluminums Conductor

Copper Conductor

Aluminums

Copper

Ground Duct Air Ground Duct Air
3cX 4  14  34  28  30  44  37  39  0.376  0.572
3cX 6  16  43  37  40  55  47  50  0.564  0.858
3cX 10  18  57  48  53  74  61  67  0.940  1.430
3cX 16  18  78  61  70  94  78  85  1.50  2.29
3cX 25  21  95  80  99  120  100  125  2.35  3.58
3cX 35  22  116  94  117  145  120  155  3.29  5.01
3cX 50  25  140  110  140  170  145  190  4.70  7.15
3cX 70  30  170  140  176  210  175  235  6.58  10.01
3cX 95  32  200  165  221  250  210  290  8.93  13.59
3cX 120  35  225  185  258  285  240  330  11.28  17.16
3cX 150  39  255  210  294  315  270  375  14.10  21.45
3cX 185  43  285  235  339  355  300  435  17.39  26.46
3cX 240  49  325  270  402  410  350  510  22.56  34.32
3cX 300  53  370  305  461  460  390  590  28.20  42.90
3cX 400  59  435  350  542  520  440  670  37.60  57.20
3cX 500  66  481  405  624  580  480  750  47.00  71.50
3cX 630  73  537  470  723  680  575  875  59.22  90.09
                   

1.1 KV Three CORE AL/COPPER COND., PVC INSULATED CABLES As per IS:1554 (Part-I)

Cross-sectional area        (Sq MM)

ARMOURED CABLE

Overall Diameter (mm)

Normal Current Rating in Amps

Short Circuit Current Rating for 1Sec.duration in K. Amps

Aluminums Conductor

Copper Conductor

Aluminums

Copper

Ground Duct Air Ground Duct Air
3cX 4  18  34  28  30  44  37  39  0.376  0.572
3cX 6  19  43  37  40  55  47  50  0.564  0.858
3cX 10  20  57  48  53  74  61  67  0.940  1.430
3cX 16  20  78  61  70  94  78  85  1.50  2.29
3cX 25  23  95  80  99  120  100  125  2.35  3.58
3cX 35  25  116  94  117  145  120  155  3.29  5.01
3cX 50  29  140  110  140  170  145  190  4.70  7.15
3cX 70  32  170  140  176  210  175  235  6.58  10.01
3cX 95  35  200  165  221  250  210  290  8.93  13.59
3cX 120  39  225  185  258  285  240  330  11.28  17.16
3cX 150  43  255  210  294  315  270  375  14.10  21.45
3cX 185  48  285  235  339  355  300  435  17.39  26.46
3cX 240  53  325  270  402  410  350  510  22.56  34.32
3cX 300  58  370  305  460  460  390  590  28.20  42.90
3cX 400  65  435  350  542  520  440  670  37.60  57.20
3cX 500  72  481  405  624  580  480  750  47.00  71.50
3cX 630  81  537  470  723  680  575  875  59.22  90.09
                   

1.1 KV Three CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)

Cross-sectional area (Sq MM)

UN-ARMOURED CABLE

Overall Diameter (mm)

Normal Current Rating in Amps

Short Circuit Current Rating for 1Sec.duration in K. Amps

Aluminums Conductor

Copper Conductor

Aluminums

Copper

Ground Duct Air Ground Duct Air
 3.5X25  22  95  80  99  120  100  125  2.35  3.58
 3.5X35  24  116  94  117  145  120  155  3.29  5.01
 3.5X50  27  140  110  140  170  145  190  4.70  7.15
 3.5X70  31  170  140  176  210  175  235  6.58  10.01
 3.5X95  34  200  165  221  250  210  290  8.93  13.59
 3.5X120  38  225  185  258  285  240  330  11.28  17.16
 3.5X150  43  255  210  294  315  270  375  14.10  21.45
 3.5X185  46  285  235  339  355  300  435  17.39  26.46
 3.5X240  52  325  270  402  410  350  510  22.56  34.32
 3.5X300  57  370  305  461  460  390  590  28.20  42.90
 3.5X400  65  435  350  542  520  440  670  37.60  57.20
 3.5X500  73  481  405  624  580  480  750  47.00  71.50
 3.5X630  82  537  470  723  680  575  875  59.22  90.09
                   
                   

1.1 KV Three & Half CORE AL/COPPER COND,XLPE INSULATED As per IS:7098(Part-I)

Cross-sectional area (Sq MM)

ARMOURED CABLE

Overall Diameter (mm)

Normal Current Rating in Amps

Short Circuit Current Rating for 1Sec.duration in K. Amps

Aluminums Conductor

Copper Conductor

Aluminums

Copper

Ground Duct Air Ground Duct Air
 3.5X25  25  95  80  99  120  100  125  2.35  3.58
 3.5X35  27  116  94  117  145  120  155  3.29  5.01
 3.5X50  30  140  110  140  170  145  190  4.70  7.15
 3.5X70  35  170  140  176  210  175  235  6.58  10.01
 3.5X95  38  200  165  221  250  210  290  8.93  13.59
 3.5X120  42  225  185  258  285  240  330  11.28  17.16
 3.5X150  46  255  210  294  315  270  375  14.10  21.45
 3.5X185  51  285  235  339  355  300  435  17.39  26.46
 3.5X240  56  325  270  402  410  350  510  22.56  34.32
 3.5X300  60  370  305  461  460  390  590  28.20  42.90
 3.5X400  71  435  350  542  520  440  670  37.60  57.20
 3.5X500  79  481  405  624  580  480  750  47.00  71.50
 3.5X630  88  537  470  723  680  575  875  59.22  90.09
 

1.1 KV Four CORE AL/COPPER COND,XLPE INSULATED  CABLES As per IS:7098 (Part-I)

Cross-sectional area (Sq MM)

UN-ARMOURED CABLE

Overall Diameter (mm)

Normal Current Rating in Amps

Short Circuit Current Rating for 1Sec.duration in K. Amps

Aluminums Conductor

Copper Conductor

Aluminums

Copper

Ground Duct Air Ground Duct Air
4cX4  17  34  28  30  44  37  39  0.376  0.572
4cX 6  18  43  37  40  55  47  50  0.564  0.858
4cX 10  20  57  48  53  74  61  67  0.940  1.430
4cX16  20  78  61  70  94  78  85  1.50  2.29
4cX 25  24  95  80  99  120  100  125  2.35  3.58
4cX35  26  116  94  117  145  120  155  3.29  5.01
4cX 50  29  140  110  140  170  145  190  4.70  7.15
4cX70  34  170  140  176  210  175  235  6.58  10.01
4cX 95  37  200  165  221  250  210  290  8.93  13.59
4cX 120  41  225  185  258  285  240  330  11.28  17.16
4cX 150  45  255  210  294  315  270  375  14.10  21.45
4cX 185  50  285  235  339  355  300  435  17.39  26.46
4cX 240  56  325  270  402  410  350  510  22.56  34.32
4cX 300  63  370  305  461  460  390  590  28.20  42.90
4cX 400  70  435  350  542  520  440  670  37.60  57.20
4cX 500  79  481  405  624  580  480  750  47.00  71.50
4cX 630  88  537  470  723  680  575  875  59.22  90.09
                   

1.1 KV Four CORE AL/COPPER COND,XLPE INSULATED  CABLES As per IS:7098 (Part-I)

Cross-sectional area (Sq MM)

ARMOURED CABLE

Overall Diameter (mm)

Normal Current Rating in Amps

Short Circuit Current Rating for 1Sec.duration in K. Amps

Aluminums Conductor

Copper Conductor

Aluminums

Copper

Ground Duct Air Ground Duct Air
4cX4  18  34  28  30  44  37  39  0.376  0.572
4cX 6  19  43  37  40  55  47  50  0.564  0.858
4cX 10  21  57  48  53  74  61  67  0.940  1.430
4cX16  22  78  61  70  94  78  85  1.50  2.29
4cX 25  26  95  80  99  120  100  125  2.35  3.58
4cX35  28  116  94  117  145  120  155  3.29  5.01
4cX 50  32  140  110  140  170  145  190  4.70  7.15
4cX70  37  170  140  176  210  175  235  6.58  10.01
4cX 95  40  200  165  221  250  210  290  8.93  13.59
4cX 120  44  225  185  258  285  240  330  11.28  17.16
4cX 150  49  255  210  294  315  270  375  14.10  21.45
4cX 185  54  285  235  339  355  300  435  17.39  26.46
4cX 240  65  325  270  402  410  350  510  22.56  34.32
4cX 300  68  370  305  460  460  390  590  28.20  42.90
4cX 400  76  435  350  542  520  440  670  37.60  57.20
4cX 500  86  481  405  624  580  480  750  47.00  71.50
4cX 630  94  537  470  723  680  575  875  59.22  90.09

200 Responses to XLPE Cable-Current Rating

  1. Syed Saif Ahmed's avatar Syed Saif Ahmed says:

    Dear Sir / Madam,
    Please send me the cable size selection chart for Low voltage & Medium voltage. I will be very great full to you.
    Regards
    Syed

  2. Ramachandra laxman's avatar Ramachandra laxman says:

    Thank you for this cable selection chart. Thank u verymuch. Do u have any information about conductor,s DC current carrying capacity .Please help me sir, Thank u.

  3. p.vadivel's avatar p.vadivel says:

    dear sir,
    ratinng cable size of 300kva to 450kva trasformer.

  4. shafeeq's avatar shafeeq says:

    dear sir,
    thanks.can you please give details of selecting UPS and generators rating.

  5. Ramchandra B Damle's avatar Ramchandra B Damle says:

    Dear Sir

    Will you please furnish me short time ratings of HT XLPE insulated cables e. g. 10% for XXX Hrs., 20% for XXX Hrs. and so on ?

  6. SHAMAUN HAKIM's avatar SHAMAUN HAKIM says:

    Can a 10 guage XPLE insulated copper wire used as leads for oil immersed CTs withstand around 90 deg C continously in transformer oil? What is the compatability of XPLE wire with transformer oil? What is the specific density of XLPE insulation?

  7. Gnana Reuben's avatar Gnana Reuben says:

    Can we get the standard from which the XLPE current values are derived / referred.

  8. paulson's avatar paulson says:

    can you tell me the voltage drop calcultaion of 11KV XLPE cable around 600m long

    • Use Excel Base Program to Calculate LT-MV-HT Cable from “Electrical Tool” Page of This Blog

      (1) Cable Designing Program:

      DOWNLOAD:

      Calculate Voltage drop of Cable.
      Calculate Size of Cable.
      Calculate Current Capacity of Cable.

      • paulson's avatar paulson says:

        Mr Jignesh,

        what is the difference between MCCB,ACB and VCB..

        I heard that above 630A we should use ACB ,but MCCB’s are available till 1600A.

        So can you tell me from which rating we have to go for ACB and VCB

        Is there any difference in the operation of MCCB and ACB.

        Thanking you,
        Paulson

      • karuppanasamy's avatar karuppanasamy says:

        i am engaged in arecanut leaf plate manufacturing activity which need heaters with die of 8000 watts.what specification of power cable can i put.

      • Amit Thakur's avatar Amit Thakur says:

        Dear Sir,

        i what to learn the HT cable sizing. how to calculate it . Can you help me. If you have any excel Sheet kindly shear with me.

      • Priya's avatar Priya says:

        Dear Sir,

        Really very happy…Your Calculation your explanation are very nice and useful for us.

  9. please send details of
    1-cable size with current rating data
    2- cable gland size & type
    3- rating of contractor & over load relay

    • This Topic is already covered.Read Electrical Notes Carefully

      • nirav shah's avatar nirav shah says:

        Dear Jignesh, I am nirav shah from hyderabad. i would like to know what is the difference between current carrying capacity for xlpe insulated single core copper flexible cables for AC and Dc applications. Benchmark being single core 240sqmm which can carry upto 550amps in AC application.

  10. Udaikiran's avatar Udaikiran says:

    Dear Sir,

    Details furnished by you are excellent.Sir, i need to buy the unlock version .Did you published any books on cable sizing,busbar calculation, breaker designing etc?My maid id is udai_kiran1983@yahoo.com

  11. ramkewal's avatar ramkewal says:

    sir, i read to this cable size and current rating chart it is very use full for us so i request u please send this chart in my Email
    RAMKEWAL

  12. ramkewal's avatar ramkewal says:

    i will be hope full with this chart
    Thank you.
    RAMKEWAL

  13. Ronald Mutambiranwa's avatar Ronald Mutambiranwa says:

    Dear Sir / Madam,
    Please send me the cable size selection chart for Low voltage & Medium voltage(single phase and three phase indicating amps each size can carry. I will be very great full to you

  14. Babji Duvva's avatar Babji Duvva says:

    can you please provid me for the current rating for 1C X 185 SQ MM copper cables

  15. nmr's avatar nmr says:

    11kv/433v TFP-1000 kva/500kva/750kva the fl currents on LT side are 1333.3/1000/666.6 amps. what is size of 4 core xlpe alluminium is used pl tell me.

  16. vamsi's avatar vamsi says:

    this chart about cables is nice but give us some information about OH cables, and underground cables .

  17. d s negi's avatar d s negi says:

    WHAT IS THE BIS – IS CODE FOR 11 KV CROSS ARMOURED CABLE

  18. Azad Anupam's avatar Azad Anupam says:

    Very useful….

  19. Mohammed's avatar Mohammed says:

    Dear Jignesh,

    Your cable selection table is very helpful. But i’ve a question to clarify? how do we determine the cable current capacity of cables running in parallel? for example if my breaker is rated at 1000A, what size of cable conductor should be terminating at the terminals per phase, can i terminate 2 x 1c x 400 per phase or how do we decide the conductor sizing? as i understand there is a derating factor of cables when connected in parallel? may be you can ellaborate further and may be send me details on the cable sizing formulation and other useful data on my email : manjarwalla@gmail.com

    • Use Equation
      % Voltage Drop:=(1.732 X (Full Load Current)X(RCosØ+j SinØ)XLengthX100) / Line Voltage X No of Run X 1000.
      Here No of Run cable is Either 1,2 or more in parallel.
      You can also use “Cable Design” sheet of the Excel Tool Page of this Blog

      • Mohammed's avatar Mohammed says:

        Dear Jignesh,

        Thank you for your prompt reply. I’ve also gone through your cable design excel sheet,wonderful program. On the cable design program how do you determine the starting and running cos and sin thetha? do you have any thumb rule for calculating the cable runs in a faster way? for example if my full load current is 1000A as incomer or any feeder load connected to my panel. As from the program i’ve to input the the respective KW to attain nearest full load current before i can get the runs of cables?

  20. B.R.Suryawanshi's avatar B.R.Suryawanshi says:

    Dear Sir,
    Plz.tel me this XLPE cables can we use 100% loading? for How much length cables are de rated?
    Thanks.

    • this Rating is as per Standard Cable Catalog and IS. Cable Rating never indicate derating factor. Because Derating Factor depends upon Your Application.
      It is depend upon Type of Laying Cable –
      =In Air,Land, at 0.500mt depth at 1 meter depth,
      =Air-Land Temperature,
      =in bundle,=In separate,Distance between two Cable, etc.
      If Cable Rating is 100 Amp It may be 80 Amp or 90 Amp or 100 Amp depend upon Laying of cable.

  21. A. A. Mahadik's avatar A. A. Mahadik says:

    Pl. send me LT cable current carrying capacity charts

    • Already available on this Blog . Please Refer Post of “PVC Flexible Wire Rating”
      I have already Put Cable/Wire Rating Starting from 430V to 66KV (Earthed/Unearthed Cable)

  22. Varry importent for me this. Site

  23. shine's avatar shine says:

    Good work, its very useful

  24. hariharan.v's avatar hariharan.v says:

    sir,if i have 7.5kw unit then how can i select cable for that unit with out using chart.give me that formula for me.

  25. zahid's avatar zahid says:

    well done sir you have a great job and sacrifices for Electrical Engineering.

  26. Hareesh R's avatar Hareesh R says:

    Hi,
    I really appreciate your effort to share consolidated information..

  27. sulaimant's avatar sulaimant says:

    dear
    sir/madem
    pleas send me cebel formula for given voltag and
    also send me cabel and amp tebal

  28. Jayaprakash.N's avatar Jayaprakash.N says:

    It is very useful informations… Gr8

  29. Ribhu Gaur's avatar Ribhu Gaur says:

    what is the thumb rule for above calcualtions..? please share the formula for approximate current ratings in 1.1 kv XLPE cables .

  30. kuruvilla's avatar kuruvilla says:

    Mr. Jignesh, can you please tell me what size of cable is required for solar installation. My panel rating is Isc=8.5 A, Voc=36.5 V. I’m using two series panels in 3 arrays, basically an 2×3 system. Thanks. Length one way will be 30 feet from panels to inverter.

  31. Nasir's avatar Nasir says:

    400 volt,528 amp and insulation xlpe ,cable size required

  32. Unknown's avatar vinod pol says:

    hiii sir, thanx for this information but sir pls tell me the formula or any thumb rule for calculating of cable/wire size as per given load…..

  33. Abdul Guffar's avatar Abdul Guffar says:

    Thank you for this cable selection chart. Do u have any information about conductor,s DC current carrying capacity .Please mail me sir, Thank u.

  34. prabhakar's avatar prabhakar says:

    sir
    can u tell me the formula how to calculate the cable sizes corresponding amps..

  35. Unknown's avatar mintu kumar pandit says:

    why use mastic tape for 11 kv cable joint,please tell me sir.

  36. Dear sir,
    what is the function of cable fillers ? please reply.

  37. sir ,
    difference between round shape cable and delta shape cable please me understand

    • mintu kumar pandit's avatar mintu kumar pandit says:

      whats type of 11kv spout ?

      • Anees Mustafa's avatar Anees Mustafa says:

        electrical infrastructure construction Q&A for exp houseing scheme what are requrment of houesing scheme of all utlates and what are gape electrical serviese between water ,sewg,gas and other serviese in under ground

  38. krishnamurthy's avatar krishnamurthy says:

    How to measure currenraings of armed & unarmed cables

    • krishnamurthy's avatar krishnamurthy says:

      Differance between kw,kvar and kva

      • Anil Thomas's avatar Anil Thomas says:

        I want to know that whats the current carrying capacity for 4 runs of 3.5 core 400 Sq.mm Al. armoured XLPE cable in ground . How it can be calculate. ( please send a copy of tables if any )

        which means if 3.5 core 400sq.mm cable carries 370 amps in ground and when it is 2 runs it will not be double of 370. it will less than double. how it will calculate ???

        Please give me a reply
        with regards
        By Anil

      • You are mixing two different topic ..
        (1) If we laid cable in ground,air or trench it’s current capacity will be decrease due to surrounding temp.
        (2) If we laid cable in group / single it’s current capacity will be decrease those effect called “derating factor of cable..
        You find in Electrical Tool page.
        If we run two cable for same phase obviously it’s capacity would be double…

      • KRISHNAMURTHY's avatar KRISHNAMURTHY says:

        How to measure capacitance&inductance in A.P.Transco meters and send formula of KW&KVAR&KVA.

  39. KIRAN PATEL's avatar KIRAN PATEL says:

    KIRAN PATEL
    dear sir what is service factor in motor and which kind machine in use same motor

  40. bj vijay's avatar bj vijay says:

    Hai …

  41. John's avatar John says:

    Dear Sir,

    My doubt might sound silly to you, but I just wanted to clarify it. From the given cable ampacity ratings in the tables above, how can we calculate the maximum power rating for the respective multi-core cables.

    Thank you.

  42. Suresh Chaudhary's avatar Suresh Chaudhary says:

    Dear Jignesh,
    pl suggest me regarding cable rating across laying ground 700 running feet for 750A load bearing at resisdence building there jurk load AC. Pl give cable size.

    Regards,
    Suresh Chaudhary

  43. bikram kaushik's avatar bikram kaushik says:

    there is no any power rating of cable.only current rating of cable are mentioned.power rating is concerned to the equipment.

  44. Shruthi's avatar Shruthi says:

    Dear Jignesh,
    Sir what’s the formula to select the cables sizes for the particular current ratings?

  45. Masoud Bu-Arbyay's avatar Masoud Bu-Arbyay says:

    You did good , its very useful

  46. mohamed's avatar mohamed says:

    dear jignesh how to calculate the busbar size in 630amps breaker 3ph ?

  47. Manoj Patil's avatar Manoj Patil says:

    Dear Sir

    Thanks for this information. this is very usefull for us.

  48. sunil's avatar sunil says:

    Dear Sir,

    Can you explain that the current rating you have mentioned in Ground ,Air, or duct is quite opposite to what manufacture state in their product catalogue.

    regards

  49. Perumalkonar's avatar Perumalkonar says:

    how many runs of 3.5C 240 sq.mm al. conductor xlpe pvc insulted cables to be laid to supply to a circuit which is maximum current draw is 800 A.

  50. shree raja's avatar shree raja says:

    Yes very use full.thank you.

  51. venu's avatar venu says:

    Sir,

    please let me know the current carrying capacity of 3C*2.5 sqmm copper cable in air.

  52. karan's avatar karan says:

    sir,
    if i want to select power cable for 2o hp motor. and i am going to use 3 core alluminium cable.
    then what will be the cable size?

  53. manoj singh's avatar manoj singh says:

    sir,
    if i want to select 50sq cable for 11kv. and i am going to use 3 core cable.
    then what will be the cable size?

    • Fetsum Asayehegn's avatar Fetsum Asayehegn says:

      your table is very useful, thank you and I need the cable size of 22 kw, 3ph, 380volt for my deep well pump motor at a deep distance of 300 metrrs
      Thank you & best regards,
      Fetsum

  54. PETER BIBIN M J's avatar PETER BIBIN M J says:

    thanks for this great cable chart…

  55. Fadi's avatar Fadi says:

    Hi

    Can I know how many runs of single core 630 mm are required for a 1000 KVA transformer ?

  56. Teshome's avatar Teshome says:

    Dear Sir;
    I would like to say thank you so much for the access you made open to get the size of power cables.
    Teshome, from Ethiopia

  57. shadab uddin's avatar shadab uddin says:

    Dear sir/ Madam
    Please send me the cable size selection chart & amps details

  58. J.P.Nandaniya's avatar J.P.Nandaniya says:

    Dear Sir,
    Kindly give me chart for motor hp kw flc relay contactor mccb current carring capacity for all and cu and gland size.

  59. fawad's avatar fawad says:

    hi…. i have find question about how to find current of 132kv,1200mm^2 cross sec area,in flat formation with 400 mm disc presnt btween them,,is there any formuala ,so guide me plzzzzz,thnkxxxx

  60. satish's avatar satish says:

    Hi — Here 40 kw load 3 ph 415 v and length is 1 km so kindly suggest me which size of aluminum
    cable to be laid in ground

  61. Virendra Singh's avatar Virendra Singh says:

    Hello, what 33 KV cable size should I select for a 2000 KW Load on LT side. Transformer is 2.5 MVA, 33/0.433 KV.

  62. sunil kumar's avatar sunil kumar says:

    बहुत अछछी जानकारी मिली।

  63. Engineer Habeeb's avatar Engineer Habeeb says:

    You are such a wonderful Engineer, for the great opportunity you have given to people

  64. UR NOTES IS SUCH WONDERFULL THANK U SO MUCH…

  65. Dear Sir,

    will you please suggest me from which website i can download Excel Base Program to Calculate LT-MV-HT Cable from Electrical tools.

  66. venkatesh's avatar venkatesh says:

    Sir Thanks For your Valuble Information,I want know the Formula for To Measure Current For Any cable Ex:1x16sq.mm,3x4sqmm,3×16 sqmm

  67. Jamshed's avatar Jamshed says:

    Sir Thanks For your Valuble Information,I want know the Formula for To Measure Current For Any cable Ex:1x16sq.mm,3x4sqmm,3×16 sqmm

  68. SARTHAK's avatar SARTHAK says:

    CAN YOU TELL ME WHEN WE TAKE A 51MM COOPER CABLE THEN THIS COOPER CABLE HOW MUCH TAKE A LOAD IN HP

  69. ali's avatar ali says:

    please can you tell me if total load is 140 Amp and length is 250 Meter. how much XLPE cable size and how much voltage drop. how i can calculate.

  70. Siddhartha's avatar Siddhartha says:

    please advice which minimum width of 3 core xlpe cable should used for 7 KM long transmission with connected load of 3000

  71. RAM's avatar RAM says:

    Sir
    How much load can be layed on 1 kv line. Please give kv and load relation.

  72. sanjay's avatar sanjay says:

    Sir
    what’s the advantage of using 4 core cable over 3.5 core cable ? And then, what chang
    Powar pf 1

  73. Suresh's avatar Suresh says:

    sir,
    Detail of Transformer primary & secondary testing please said me

  74. Obk.'s avatar Obk. says:

    Hello Sir.
    Can a 4C 150mm armoured cable sustain 595A or a total power of 398Kva? If not, what cable size would be ideal? I seek for expert advice. Thanks.

  75. Karan's avatar Karan says:

    Very good can I get this document through mail
    It’s very useful for me

  76. Mohammad ladlay's avatar Mohammad ladlay says:

    Thank you for this cable selection chart.
    Thank u verymuch.

  77. mike's avatar mike says:

    sir can you help me to size the cables for 5000A,3Phase,415Volts and the size of the cables for 2500KVA,415V, 3Phase diesel generator please help me for this

  78. Ansh's avatar Ansh says:

    hello Sir,
    I’m Ansh from lucknow , i wanted to know when cable insulation test carried out on one end R-N other end of cables R-N are shorted or not & why….???

  79. chauhan Devnarayan's avatar chauhan Devnarayan says:

    Sir i
    i want to know how to select copper and aluminium busar on current capacity

  80. shibu's avatar shibu says:

    Hai
    can you please tell me how to make the GRC-Group rating cables,
    Regards
    Shibu

  81. Harekrishna Parida's avatar Harekrishna Parida says:

    Dear Sir,
    Kindly share What is the standard parameters to be maintained daily in a transformer for both dry type and oil type & What is dielectric strength?

  82. Vishal Jayprakash Mistry's avatar Vishal Jayprakash Mistry says:

    Respected Sir, Thanks For Supporting For Electrical Engineer
    Sir i have Question to you sir
    Can you give suitable CU. & Al. Cable Size of different rating starter like DOL & Stardelta Starter from above cable chart.

  83. SEBIN's avatar SEBIN says:

    Dear sir,
    i want to know will there be any change inside the conductor when the cable inssulation viltage is .4/.6kV…

  84. Kanchan's avatar Kanchan says:

    Dear Sir,
    Thanks for the useful chart… can u please guide me if these ratings are available in some standard or u have calculated the same using IEC 60287.
    Regards

  85. Abhishek Kumar's avatar Abhishek Kumar says:

    Dear sir,
    Kindly give me how to test six nos of leads of motors to connect in delta.No identification.

  86. jayakumar's avatar jayakumar says:

    Dear sir,
    how to messring of current rate of contecter or cables

  87. manjunath patil's avatar manjunath patil says:

    tell me the standard formula to calculate current carrying capacity of cable

  88. John Lima's avatar John Lima says:

    Sir,
    I require 4 core. rubberised cable for 200 HP 3phase motor 380/460 volts 226 amps if possible starter details.

    Regards.
    John

  89. J Prasad's avatar J Prasad says:

    KINDLY SEND ME 33KV XLPE CABLE Current Rating Equivalent to Dog & panther conductor

  90. NILABJA BHATTACHARYA's avatar NILABJA BHATTACHARYA says:

    Hello Sir,

    Please tell me how to calculate the voltage drop of a 4C, 25 Sq. mm. Armoured Aluminium XLPE 1.1kv rating cable for 80M length having current rating of 200A.

    If possible please involve the calculation also in reply.

  91. omar's avatar omar says:

    kindly if I need underground cable I will consider current carrying from above table & proceed or should be multiply with derating factors also . ??? can you help me.

    our site condition :-

    ground temp. 35C >>>> factor = 0.89 as per IEC standard tables .
    grouping factor >>>>>> 0.75 as per IEC standard tables .
    depth laying factor >>>> 1.0 as per IEC standard tables .
    soil thermal resistivity factor >>>> 1.17 as per IEC standard tables .

  92. Sivakumar's avatar Sivakumar says:

    Super

  93. Sivakumar's avatar Sivakumar says:

    Pls send me the LT &HT cable amps rating

  94. Sivakumar's avatar Sivakumar says:

    Electrical notes are good. Pls send the transformer yard drawings

  95. Faizur Rehman's avatar Faizur Rehman says:

    hI,
    Main Cut-Out: 250 Amps
    3 – Phases

    Red : 163 Amps Incoming Main Load from Qatar Govt. is 105 KW
    Yellow : 156 Amps Cable size 95 mm²
    Blue : 105 Amps

    Please let me know the Total Existing Load and alos tell me remedy to tripping off Problem.

  96. Rajesh's avatar Rajesh says:

    Its very useful data. Highly appreciate you efforts. Thanks

  97. gouse's avatar gouse says:

    Sir 3*400sqmm ug cable is laid in trench but cable termination is getting heating tell me reason

  98. vanrajsinh's avatar vanrajsinh says:

    Dear sir u help me to amp to cable size formula & table send me my email id

  99. venkatesh's avatar venkatesh says:

    Sir
    thanks for info
    can u provide any data regarding voltage drop by its length

  100. azad's avatar azad says:

    Either the termination is lose or the connected load is more than your estimated load

  101. Edwin Iraola's avatar Edwin Iraola says:

    SIr,

    Can you help about how much the maximum outer diameter of can cable can be run in 50 mm 110 mm 160 mm 250 mm dia duct

    Thank you

  102. Pingback: Quora

  103. Jesper Moeller's avatar Jesper Moeller says:

    Sir, why cant I find a Multi core cable 3.5 x 240 mm2 ?

  104. K Soma Sekhar's avatar K Soma Sekhar says:

    For 140A load (Gas Analyser Heat Tracing System), 3cx150 sq mm 1.1kV Armoured Aluminium cable shall be sufficient?? Cable to be laid in Air.

  105. vineet kumar vishwakarma's avatar vineet kumar vishwakarma says:

    can you tell me , the size of fuse wire which can be used in 25 kva 3 phase distribution transformer 11/.4kv

  106. prabu's avatar prabu says:

    dear sir,

    how to calculate the maximum output amps for 4c x 240sqmm size?

  107. Siva Prasad K's avatar Siva Prasad K says:

    can anyone pls help me by sending the current carrying capacity of 3.5×35 Sq.mm aluminium cable ?

  108. R K Patel's avatar R K Patel says:

    Sir, request you to please send excel based calculation sheet for selection

  109. kandavel's avatar kandavel says:

    Dear Sir
    I would like to know the amperes details of 1c,600 SQMM COPPER CABLE…

  110. ramjas's avatar ramjas says:

    Dear sir ,

    cable more type example armored , unarmored , flexible , how calculate running meter weight.
    have any formula.

  111. ramjas's avatar ramjas says:

    Dear sir ,

    We have more type cable , armored , unarmored,flexible,instrumentation.
    how calculate running mtr weight.
    you have any formula.

  112. Prashant Jadhav's avatar Prashant Jadhav says:

    Dear sir,

    We have got new project. please let us know which cable use to 200KV UPS input

  113. rk's avatar rk says:

    give details as below..

    which size of cables are use in underground network ?
    Total load is 200kw

    as early as possible

    thanks

  114. Why do electricity board keep R N Y B phase wiring in street post and not in R Y B N in order?

  115. Junad ur Rehman's avatar Junad ur Rehman says:

    Sir..!
    Can you tell me the cable size in mm..
    If i have to pass 500 amps of normal current and a surges of 100 amps could come to it..
    Voltage is 440 V .
    Cable length i need is 100 feet 1 side (single core) .

  116. hari's avatar hari says:

    please provide the cable sizing for 1000kva DG set…we got information that -4 run of 240 sq mm cable ,single core for each phase is required.Is it like that?why?what is the calculation?

  117. AJU's avatar AJU says:

    Sir,

    How will calculate the cable size if load A and distance between load and source are known?

  118. sanjeev dhiman's avatar sanjeev dhiman says:

    sir plz define. cable size increses current also increase in small dia cables but when dia increase but current not increase with dia . define this

  119. Navin's avatar Navin says:

    Dear Sir kindly help in cable selection on AC side for a solar roof top system.
    1).10kw pv system for a two floried villa

    2).30 kw pv system for a 12 floried apartment.
    Both the above cases ACDB is mounted on the roof.

    Also please send me the cable selection chart…

  120. Arunpuri's avatar Arunpuri says:

    Thanks!!

  121. Maulik's avatar Maulik says:

    Sir,

    We have wrongly purchased 3 core x 300 sq mm Aluminium armoured cable for main Incomer. What will be the solution to convert this cable in 3.5 Core x 300 Sq mm cable. Please help.

  122. shiva s. h.'s avatar shiva s. h. says:

    sir, for 690 volt vfd application motor is it suitable for 1.1kv xlp cable or shall we required any special cable

  123. rakesh_19781978@rediffmail.com's avatar rakesh_19781978@rediffmail.com says:

    sir,
    Please tell me if 2x3x400 sqmm XLPE cable maximum current carrying capacity will be same for 11kv,33kv and 66kv voltage level?
    What is the maximum current carrying capacity?

  124. rakesh_19781978@rediffmail.com's avatar rakesh_19781978@rediffmail.com says:

    sir,
    Please tell me if 2x3x400 sqmm XLPE cable maximum current carrying capacity is same for 11KV,33KV,66KV?
    what is the max current carrying capacity for 4km cable?

  125. anil's avatar anil says:

    Thanks for providing such a list.
    May I know the actual difference between LT & HT?
    And what is the standard of choosing the LT power cable?

  126. Mohd Ahmad's avatar Mohd Ahmad says:

    thanks for its

  127. Nitesh's avatar Nitesh says:

    10sqmm×4core xlpe ug cable is ideal for a three floor building with total capacity of 15kilowatt?

  128. Chris's avatar Chris says:

    This is very informative. Please let me also have table for xlpe cable ratings at 11kv.

  129. Sushil's avatar Sushil says:

    In Your Electrical notes ( Rev 5,page 10), Thumb rule for cable current capacity says 4 times of cable size, 4 x 2.5 sq.mm = 9Amp. If I am not wrong then 2.5sq.mm can carry approx 22Amp
    Can you please explain the basis of this thumb rule?

  130. sukdeb chakraborty's avatar sukdeb chakraborty says:

    I need cable glend size chart as per cable size
    Thank you

  131. Dear sir.
    I am working as Sr. section Engineer in Western Railway zone of Indian Railway.I have to scrutinise technically all material for traction distribution(Electrical branch) which is purchased by Railway.During Technically scrutiny I am facing a problem regarding type test certificate provided by firm for IS 7098 part II(2011)or part-I(1988).How can I considered category of cable i.e. 01, C1 or C2

  132. papadopoulos Thanasis's avatar papadopoulos Thanasis says:

    please I want to know what cable diameter I can use for one motor 450 volt 3 ph 60 hz 237 A in one distance 295 meter , the cable passing from pipe with other cable together.

    Thanks

  133. How can I use cable size for 440 kW load? Please suggest Me?

  134. NIDHI BHUSHAN's avatar NIDHI BHUSHAN says:

    how to select HT cables ?

  135. Ravikant Goswami's avatar Ravikant Goswami says:

    2R*3.5C*240sqmm XLPE, Aluminium cable current carriynig capacity for 630Amp Incomer Feeder panel?

  136. hemant kumar's avatar hemant kumar says:

    please i want to note chemical electrical earthing and were use & its advantages anther earthing system , how many cost of instalation of one chemical earthing

  137. Rajesh Thapa's avatar Rajesh Thapa says:

    Can any one tell / explain the purpose of using 1.0 kV grade and 1.1 kV grade rating of PVC/XLPE insulated cable for low voltage since I am confused with it as some says 1.0 kV n some 1.1 kV. Logically how do we calculate? or it is differ from country to country?

  138. Bornfree Kalunga's avatar Bornfree Kalunga says:

    Kindly send me these charts for cable selection , i will highly appreciate.

  139. Bornfree Kalunga's avatar Bornfree Kalunga says:

    Kindly send me the charts for the cable selection, i will highly appreciate.

  140. floyd's avatar floyd says:

    Hi Jignesh, I’d like to ask for your permission to reproduce two of your Tables in my blog as I’d need them for my personal quick reference. Am currently working on a cable installation for a raw water pump. Thanks in advance.

  141. Gautam Ramdas's avatar Gautam Ramdas says:

    Hi Sir,
    I want cable joint selection chart because I check its different catalogue number for every manufacturer, so is there any standard chart for it. Please if you have send me on my email id.
    Thank you!

  142. Lennox's avatar Lennox says:

    Very well detailed would like to have reference to a chart when paralleling cables

  143. Madhukarreddy's avatar Madhukarreddy says:

    Good massage

  144. Hamsananthan's avatar Hamsananthan says:

    What is Laminar insulation on Medium voltage cables, loss on Laminar insulation

  145. Pingback: Diameter of 1100 Volts Grade XLPE, Insulated Cable (IS-7098- Part- I)

  146. Sachin's avatar Sachin says:

    16sqmm 1100v aluminum armored xlpe cable mai.kitna hp ka motor lode de .

  147. Brijesh kumar's avatar Brijesh kumar says:

    Sir,
    For 100 amp load and 150 MTR distance . Single phase .. how many sq mm copper cable required..

  148. harsh panchal's avatar harsh panchal says:

    Thank you so much sir your information is very useful..

  149. Eng. Abdolgabar Ahmed Mahmood's avatar Eng. Abdolgabar Ahmed Mahmood says:

    Dear Sir .
    Please send me the cable size selection chart for Low voltage & Medium voltage(pdf). I will be very great full to you.
    Regards.
    Eng. Abdolgabar Ahmed

  150. Bishnu Chapagai's avatar Bishnu Chapagai says:

    We have 2200 kVA 11/0.415 kV transformer. What would be the proper cable size at 11 kV Side ? is it simply by current rating or we need to take 2 to 3 times..plz clarify..

  151. vishal's avatar vishal says:

    hello,
    am planning to set up a factory where i will need load for my machines upto 130 hp. can some one suggest what copper armour cable should be used??

  152. Shubham mishra's avatar Shubham mishra says:

    Good evening sir,
    Will you please send the 1.1kv 3core armoured xlpe cable current rating and. Is there any thumb rule(genral way) for calculating the current capacity (approximate) of the cable at site.(xlpe/pvc/pilca, 1c/2c/3c/3.5c/4c, copper/aluminum).

  153. Shashi Vaidya's avatar Shashi Vaidya says:

    hello

    can you guide Multi core cable Raw material calculation formula

  154. Akinbode Josiah's avatar Akinbode Josiah says:

    Sir, please what is load capacity can 11kv aluminium xlpe power cable can carry

  155. SAMIR PRIYAVADAN's avatar SAMIR PRIYAVADAN says:

    Sir I have confused all time in 0ne terms in 3.5*C in any cable amp rating are given per phase

  156. dharmesh sapra's avatar dharmesh sapra says:

    hi
    How to calculate derating factor. Give its formula

  157. shekhar's avatar shekhar says:

    sir what does mean 1.1/kv Ac, 1core, 2run/phase-70 sq mm copper , xlpe, unarmoured cable.